| With proper installation, operation, and maintenance your gas fireplace will |
| provide years of |
| troubleshooting guide will assist a qualified service person in the diagnosis |
Troubleshooting | of a problem and the corrective action to be taken. This troubleshooting |
guide can only be used by a qualified service technician. |
Symptom | Possible Cause | Corrective Action | |
1. After repeated | a. Defective ignitor. | Check the spark at the electrode and pilot. If no spark and electrode wire is | |
triggering of the red |
| properly connected, replace the ignitor. | |
or black piezo button, |
|
| |
b. Defective pilot or | Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or | ||
the spark ignitor will | |||
misaligned electrode | black piezo button again. If the pilot lights, an improper gas/air mixture caused the | ||
not light the pilot. | |||
(spark at electrode). | bad lighting and a longer purge period is recommended. If the pilot will not light, | ||
| |||
|
| ensure the the gap at the electrode and pilot is | |
|
| strong spark. If the gap is OK, replace the pilot. | |
|
|
| |
| c. No gas or low gas | Check the remote | |
| pressure. | the gas main. There can be more than one (1) valve between the fireplace and the | |
|
| main. | |
|
|
| |
| d. No LP in tank. | Check the LP (propane) tank. You may be out of fuel. | |
|
|
| |
2. The pilot will not | a. Defective | Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the | |
stay lit after carefully | thermocouple. | pilot for maximum flame impingement. | |
following the lighting |
|
| |
instructions. |
| Ensure that the thermocouple connection at the gas valve is fully inserted and tight | |
|
| (hand tighten plus 1/4 turn). | |
|
| Disconnect the thermocouple from the valve, place one millivolt meter lead wire on | |
|
| the tip of the thermcouple and the other meter lead wire on the thermocouple | |
|
| copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less | |
|
| than 15mV, replace the thermocouple. | |
|
|
| |
| b. Defective valve. | If the thermocouple is producing more than 15 millivolts, replace faulty valve. | |
|
|
| |
3. The pilot is | a. ON/OFF switch or | Check the ON/OFF switch and wires for proper connections. Place the jumper | |
burning, there is no | wires defective. | wires across the terminals at the switch. If the burner comes on, replace the | |
gas burner, the valve |
| defective switch. If the switch is OK, place the jumper wires across the switch wires | |
knob is in the ON |
| at the gas valve. If the burner comes on, the wires are faulty or connections are | |
position, and the |
| bad. | |
ON/OFF switch is in |
|
| |
b. Thermopile may | If the pilot flame is not close enough physically to the thermopile, adjust the pilot | ||
the ON position. | |||
not be generating | flame. | ||
| |||
| sufficient millivoltage. | Be sure the wire connections from the thermopile at the gas valve terminals are | |
|
| ||
|
| tight and that the thermopile is fully inserted into the pilot bracket. | |
|
| Check the thermopile with a millvolt meter. Take the reading at | |
|
| terminals of the gas valve. The meter should read 325 millivolts minimum, while | |
|
| holding the valve knob depressed in the pilot position, with the pilot lit, and the | |
|
| ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is | |
|
| below the specified minimum. | |
|
| With the pilot in the ON position, disconnect the thermopile leads from the valve. | |
|
| Take a reading at the thermopile leads. The reading should be 325 millivolts | |
|
| minimum. Replace the thermopile if the reading is below the minimum. | |
|
|
| |
| c. Defective valve. | Turn the valve knob to the ON position. Place the ON/OFF switch in the ON | |
|
| position. Check the millivolt meter a the thermopile terminals. The millivolt meter | |
|
| should read greater than 125mV. If the reading is acceptable, and if the burner | |
|
| does not come on, replace the gas valve. | |
|
|
| |
| d. Plugged burner | Check the burner orifice for stoppage. Remove stoppage. | |
| orifice. |
| |
|
|
| |
| e. Wall switch or | Follow the corrective action in Symptom and Possible Cause 1.a above. Check | |
| wires are defective. | the switch and wiring. Replace where defective. | |
|
|
|
40