Quadra-Fire QV32-A, QV36-A manual Use SL D-Series components only

Page 18

V

 

H

1' MIN. (305mm)

2'

MAX. (610mm)

2' MIN. (610mm)

4'

MAX. (1.22m)

3' MIN. (914mm)

6'

MAX. (1.86m)

4' MIN. (1.22m)

8'

MAX. (2.4m)

V+H=40' MAX. (12.4m)

H = 8' MAX. (2.4m)

Use D-Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

V

H

Figure 12. Venting with One 90° Elbow

H

Use SL D-Series components only.

VENTING WITH ONE (1) 90o ELBOW NATURAL GAS

V (MIN.)

H (MAX.)

90o Elbow on Top

2 FT (610mm)

1 FT (305mm)

3 FT (914mm)

2 FT (610mm)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

H MAX. = 16 FT (4.8m)

V + H MAX. = 40 FT (12.2m)

VENTING WITH ONE (1) 90o ELBOW

PROPANE

V (MIN.)

H (MAX.)

 

90o Elbow on Top

NOT ALLOWED

1 FT (305mm)

2 FT (610mm)

2 FT (610mm)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

H MAX. = 16 FT (4.8m)V + H MAX. = 40 FT (12.2m)

Figure 13. Venting with One 90° Elbow

18

V

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

Image 18
Contents Installers Guide What to do if you smell gasSafety and Warning Information Table of Contents Service Parts Accessories / Accessoires Standing Pilot Ignition / D’ALLUMAGE PAR VeilleuseLog Set Assembly DF-36TS-BK Appliance Certification Installation CodesHigh Altitude Installations CertificationPre-install Preparation Introducing the Village Collection Gas FireplacesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the QV36-A Diagram of the QV-32-A Constructing the Fireplace Chase Locating the FireplaceClearance Requirements Framing Dimensions Framing the FireplaceDV-FLEX-10 47 3/4 Installing the Vent System Identifying Vent ComponentsVent System Approvals Straight UP Vertical Venting Use SL D-Series components onlyUse D-Series components only Use SL D-Series components only Venting with Two 90 Elbows Natural GAS MAX. = 16 FT 4.8m V + V1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H Venting with Four 90 elbows SET of Collars YOU are Using could Cause a Fire Adding Venting Components Install Support Brackets Continue Adding Vent ComponentsCeiling Firestop Ceiling Side 191mm Vent TerminationPositioned SO That the Arrow is Pointing UP Minimum Trapezoid CAP TerminationVent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Positioning, Leveling, and Securing the Fireplace Gas Control SystemStanding Pilot Ignition System To Check for GAS Leaks Gas Supply LineGas Pressure Requirements PressureOptional Accessories Wiring the FireplaceFor Standing Pilot Ignition Wiring Appliance Requirements Wall SwitchRefractory Kit Placement BRICK-291, BRICK-293 FinishingInstalling Trim, Logs Ember Material Glass SpecificationsDouble-check for faulty components Before Lighting the FireplaceStanding Pilot Ignition After the InstallationLighting the Appliance What to do if YOU Smell GASFireplace Maintenance Important Turn OFF the GAS Before Servicing Your FireplaceTroubleshooting Be Placed in this Opening Lifetime Warranty