Quadra-Fire QV36-A, QV32-A Gas Supply Line, Gas Pressure Requirements, To Check for GAS Leaks

Page 33

Step 6. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality. (In the state of Massachusetts installation must be performed by a licensed plumber).

NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch (13mm) gas supply line. To install the gas supply line:

A listed (and State of Massachusetts approved) 1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substituting for these components, please consult local codes for compliance.

Locate the gas line access hole in the outer casing of the fireplace.

The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2” in diameter and it does not penetrate the actual firebox.

Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the shut-off valve.

When attaching the pipe, support the control so that the lines are not bent or torn.

After the gas line installation is complete, use a soap solution to carefully check all gas connections for leaks.

!

WARNING: DO NOT USE AN OPEN FLAME

TO CHECK FOR GAS LEAKS.

 

 

 

• Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.

• At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration.

FLEX CONNECTOR

MANUAL

SHUT-OFF VALVE

GAS VALVE

USE WRENCH ON SHUT-OFF

VALVE WHEN TIGHTENING GAS LINE

Figure 35. Gas Supply Line

Step 7. Gas Pressure Requirements

Pressure requirements for these gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

33

Image 33
Contents What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents Service Parts Standing Pilot Ignition / D’ALLUMAGE PAR Veilleuse Accessories / AccessoiresLog Set Assembly DF-36TS-BK High Altitude Installations Installation CodesAppliance Certification CertificationPre-install Preparation Introducing the Village Collection Gas FireplacesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the QV36-A Diagram of the QV-32-A Constructing the Fireplace Chase Locating the FireplaceClearance Requirements Framing the Fireplace Framing DimensionsDV-FLEX-10 47 3/4 Installing the Vent System Identifying Vent ComponentsVent System Approvals Straight UP Vertical Venting Use SL D-Series components onlyUse D-Series components only Use SL D-Series components only Venting with Two 90 Elbows Natural GAS MAX. = 16 FT 4.8m V + V1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H Venting with Four 90 elbows SET of Collars YOU are Using could Cause a Fire Continue Adding Vent Components Adding Venting Components Install Support BracketsCeiling Firestop Ceiling Side Positioned SO That the Arrow is Pointing UP Vent Termination191mm Minimum Trapezoid CAP TerminationVent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Positioning, Leveling, and Securing the Fireplace Gas Control SystemStanding Pilot Ignition System Gas Pressure Requirements Gas Supply LineTo Check for GAS Leaks PressureFor Standing Pilot Ignition Wiring Appliance Requirements Wiring the FireplaceOptional Accessories Wall SwitchFinishing Refractory Kit Placement BRICK-291, BRICK-293Glass Specifications Installing Trim, Logs Ember MaterialBefore Lighting the Fireplace Double-check for faulty componentsLighting the Appliance After the InstallationStanding Pilot Ignition What to do if YOU Smell GASImportant Turn OFF the GAS Before Servicing Your Fireplace Fireplace MaintenanceTroubleshooting Be Placed in this Opening Lifetime Warranty