Quadra-Fire QV36-A, QV32-A manual Straight UP Vertical Venting, Use SL D-Series components only

Page 17

Flex Vent

The flex vent must be supported with the spacing between support intervals not exceeding 4 feet, with no more than ½ inch sag between supports.

A support is required at each change in venting direction, and in any location where it is necessary to maintain the necessary clearance to combustibles. A simple “up and out” installation (Figure 9) requires only enough support to main- tain the necessary clearance to combustibles. However, the vent attachment point and the firestop location are consid- ered to be supports.

STRAIGHT UP

VERTICAL VENTING

V (FT.)

45' MAX. (13.7m)

NOTE: For vertical venting over 20 feet a restrictor plate is recommended for improved

3” CLEARANCE

FLEX-VENT

TERMINATION

CAP

1”

CLEARANCE

flame appearance.

Use SL D-Series components only.

Figure 9.

STRAIGHT OUT HORIZONTAL VENTING

H

Max. Run

36" (914 mm)

Note: Use two 90o elbows for corner installations.

Use D-Series components only.

Figure 10. Straight up Vertical Venting

90-DEGREE ELBOWS

H

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

Figure 11. Straight Out Horizontal Venting

17

Image 17
Contents What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents Service Parts Standing Pilot Ignition / D’ALLUMAGE PAR Veilleuse Accessories / AccessoiresLog Set Assembly DF-36TS-BK High Altitude Installations Installation CodesAppliance Certification CertificationANY Such Action MAY Possibly Cause a Fire Hazard Pre-install PreparationIntroducing the Village Collection Gas Fireplaces Diagram of the QV36-A Diagram of the QV-32-A Clearance Requirements Constructing the Fireplace ChaseLocating the Fireplace Framing the Fireplace Framing DimensionsDV-FLEX-10 47 3/4 Vent System Approvals Installing the Vent SystemIdentifying Vent Components Use D-Series components only Straight UP Vertical VentingUse SL D-Series components only Use SL D-Series components only Venting with Two 90 Elbows Natural GAS MAX. = 16 FT 4.8m V + V1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H Venting with Four 90 elbows SET of Collars YOU are Using could Cause a Fire Continue Adding Vent Components Adding Venting Components Install Support BracketsCeiling Firestop Ceiling Side Positioned SO That the Arrow is Pointing UP Vent Termination191mm Minimum Trapezoid CAP TerminationVent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Standing Pilot Ignition System Positioning, Leveling, and Securing the FireplaceGas Control System Gas Pressure Requirements Gas Supply LineTo Check for GAS Leaks PressureFor Standing Pilot Ignition Wiring Appliance Requirements Wiring the FireplaceOptional Accessories Wall SwitchFinishing Refractory Kit Placement BRICK-291, BRICK-293Glass Specifications Installing Trim, Logs Ember MaterialBefore Lighting the Fireplace Double-check for faulty componentsLighting the Appliance After the InstallationStanding Pilot Ignition What to do if YOU Smell GASImportant Turn OFF the GAS Before Servicing Your Fireplace Fireplace MaintenanceTroubleshooting Be Placed in this Opening Lifetime Warranty