Quadra-Fire QF130 owner manual Mantel and Wall Projections, Side View TOP View

Page 18

SIDE VIEW

TOP VIEW

1-1/2 IN.

BD

CD

SURROUND

APPLIANCE

AD

SURROUND

APPLIANCE

MINIMUM FIREPLACE SIZE

 

Location

QFI35

 

 

QFI30

 

 

 

 

 

 

 

 

Inches

 

Millimeters

Inches

 

Millimeters

 

 

 

 

 

 

 

 

 

 

 

 

AD

Alternate Unit Width

33-3/16

 

843

29-1/16

 

738

 

 

 

 

 

 

 

 

BD

Alternate Unit Depth

15-1/16

 

383

13-7/8

 

352

 

 

 

 

 

 

 

 

CD

Alternate Unit Height

22-9/16

 

573

19-1/16

 

484

 

 

 

 

 

 

 

 

*Note: If exhaust collar on insert and fi replace damper do not line up, add 4 inches (102 mm) to minimum

replace height for bends in vent pipe.

Figure 5.2 Fireplace Opening - Deep Surround

B. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances to combustibles as specified. Framing or finishing material closer than the minimums listed must be construct- ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).

Clearance to combustible material under the insert is 1/4 inch (6 mm). Clearance from top of fireplace opening for combustibles extending 12 inches max. is 12 inches.

Use leveling legs to raise insert minimum 1/4 inch (6 mm) above combustible material or outer wrap of factory built firebox.

Combustible facings must not extend behind the insert surround. For non-combustible material specifications refer to section 1.E.

EXISTING NON-COMBUSTIBLE FACING

12 IN. MAX.

12 IN. MIN.

Figure 5.3 Mantel Clearances

18

Quadra-Fire • QFI30, QFI35 • 2227-900 Rev. H • 1/11

Image 18
Contents Models What to do if you smell gasHOT Surfaces Congratulations Homeowner Reference InformationXxxxxxxx Table of Contents User GuideLimited Lifetime Warranty Limited Lifetime Warranty Listing and Code Approvals Gas Fireplace Safety Operating Instructions User GuideYour Fireplace IPI Battery Tray/Battery Installation Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceModule Reset Control Module OperationBefore Lighting Fireplace What to do if YOU Smell GAS Lighting Instructions IPIFinal inspection by GAS ValveFrequently Asked Questions Issue SolutionsAfter Appliance is Lit Glass Cleaning Maintenance and ServiceMaintenance Tasks-Homeowner Remote ControlVenting Maintenance Tasks-Service TechnicianGasket Seal and Glass Assembly Inspection LogsBurner Ignition and Operation IPI Pilot Flame PatternsGetting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Minimum Fireplace Size Fireplace Size RequirementsMinimum Fireplace Opening QFI35 QFI30Mantel and Wall Projections Side View TOP ViewTermination Locations Vent Termination Minimum ClearancesInstallation Preparation Vent Limits Installing Vent Pipe and ApplianceConnecting Vent Pipe Venting ComponentsPlacing, Securing and Leveling the Appli- ance IPI ModelsFactory Built Wood Burning Installing Adaptor and Termination CapMasonry Damper Flashing Kit OptionalGas Pressure Gas InformationFuel Conversion Gas ConnectionON/OFF Switch Wiring RequirementsIntelliFire Plus Ignition System Wiring Electrical InformationOptional Accessories Requirements BLKFan Wiring with Remote AUX 300 Module FAN WHT GRN BLK BlowersFinishing Clearances to Mantels or other Combustibles above ApplianceAppliance Setup Log Set Assembly LOGS-QFI30 Models QFI30 Install the Log AssemblyFor LOG #6 Mates With Slot Mate Notch With Grate BARSlot Log Set Assembly LOGS-QFI35 Models QFI35 Install Back RefractorySlot on Log #2 LOG Slot Mate LOG Pins with LOG Slots Flat Spot For LOG #6 Air Shutter Setting Air Shutter SettingsQFI30 QFI35 Troubleshooting Symptom Possible Cause Corrective ActionIntelliFire Plus Ignition System To remove any contaminants that may have accumulated on flame Appliance Dimension Diagram Model DimensionsReference Materials Vent Kits Components Direct Vent Flex Liner KitsContact Information