9 Gas Information

A. Fuel Conversion

Make sure the appliance is compatible with available gas types.

Conversions must be made by a qualified technician (NFI certifi ed or factory-trained) using Hearth & Home Technologies specifi ed and approved parts.

B. Gas Pressure

Optimum appliance performance requires proper input pressures.

Gas line sizing requirements will be determined in ANSI Z223.1 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.

Pressure requirements are:

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

10.0 in. w.c.

13.0 in. w.c.

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

C. Gas Connection

Refer to Reference Section 15 for location of gas line access in appliance.

Gas line may be run through knockout(s) provided.

The gap between supply piping and gas access hole may be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.

Pipe incoming gas line into valve compartment.

Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.

WARNING! Risk of Fire/Explosion! Support control when attaching pipe to prevent bending gas line.

• A small amount of air will be in the gas supply lines.

WARNING! Risk of Fire/Explosion! Gas build-up during line purge could ignite.

WARNING! Risk of Fire/Explosion! High pressure will damage valve. Low pressure may cause explosion.

Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

WARNING

Fire Risk. Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter).

Note: A listed (and Commonwealth of Massachusetts ap- proved) 1/2 inch (13 mm) T-handle manual shut-off valve and fl exible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

Purge should be performed by technician certified by NFI or factory-trained.

Ensure adequate ventilation.

Ensure there are no ignition sources such as sparks or open flames.

Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.

WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loos- ened during shipping and handling.

WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.

D. High Altitude Installations

NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.

When installing above 2000 feet elevation:

In the USA: Reduce burner orifice 4% for each 1000 feet above 2000 feet.

In the CANADA: Reduce burner orifice 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.

24

Quadra-Fire • QFI30, QFI35 • 2227-900 Rev. H • 1/11

Image 24
Contents Models What to do if you smell gasHOT Surfaces Congratulations Homeowner Reference InformationXxxxxxxx Table of Contents User GuideLimited Lifetime Warranty Limited Lifetime Warranty Listing and Code Approvals Gas Fireplace Safety Operating Instructions User GuideYour Fireplace Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesIPI Battery Tray/Battery Installation Clear SpaceModule Reset Control Module OperationBefore Lighting Fireplace Lighting Instructions IPI Final inspection byWhat to do if YOU Smell GAS GAS ValveFrequently Asked Questions Issue SolutionsAfter Appliance is Lit Maintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Service Technician Gasket Seal and Glass Assembly InspectionVenting LogsBurner Ignition and Operation IPI Pilot Flame PatternsGetting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Fireplace Size Requirements Minimum Fireplace OpeningMinimum Fireplace Size QFI35 QFI30Mantel and Wall Projections Side View TOP ViewTermination Locations Vent Termination Minimum ClearancesInstallation Preparation Installing Vent Pipe and Appliance Connecting Vent PipeVent Limits Venting ComponentsPlacing, Securing and Leveling the Appli- ance IPI ModelsInstalling Adaptor and Termination Cap MasonryFactory Built Wood Burning Damper Flashing Kit OptionalGas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements IntelliFire Plus Ignition System WiringON/OFF Switch Electrical InformationOptional Accessories Requirements BLKFan Wiring with Remote AUX 300 Module FAN WHT GRN BLK BlowersFinishing Clearances to Mantels or other Combustibles above ApplianceAppliance Setup Log Set Assembly LOGS-QFI30 Models QFI30 Install the Log AssemblyFor LOG #6 Mates With Slot Mate Notch With Grate BARSlot Log Set Assembly LOGS-QFI35 Models QFI35 Install Back RefractorySlot on Log #2 LOG Slot Mate LOG Pins with LOG Slots Flat Spot For LOG #6 Air Shutter Setting Air Shutter SettingsQFI30 QFI35 Troubleshooting Symptom Possible Cause Corrective ActionIntelliFire Plus Ignition System To remove any contaminants that may have accumulated on flame Appliance Dimension Diagram Model DimensionsReference Materials Vent Kits Components Direct Vent Flex Liner KitsContact Information