IntelliFire Plus™ Ignition System (continued)
Symptom | Possible Cause | Corrective Action | |
|
|
| |
4. Pilot lights but con- | A. A shorted or loose connection in | Verify all connections to wiring diagram in manual. Verify connec- | |
tinues to spark, and | fl ame sensing rod. | tions underneath pilot assembly are tight. Verify flame sense or ig- | |
main burner will not |
| niter wires are not grounding out to metal chassis, pilot burner, pilot | |
ignite. (If the pilot |
| enclosure or screen if present, or any other metal object. | |
continues to spark |
|
| |
B. Poor fl ame rectifi cation or contami- | With fi xed glass assembly in place, verify that flame is engulfing | ||
after the pilot flame | |||
nated fl ame sensing rod. | fl ame sensing rod on left side of pilot hood. Flame sensing rod | ||
has been lit, flame | |||
| should glow shortly after ignition. With a | ||
rectifi cation has not |
| ||
| rent in series between module and sense lead is at least 0.14 mi- | ||
occurred.) |
| ||
| croamps. Verify correct pilot orifi ce is installed and gas inlet is set to | ||
|
| ||
|
| pressure specifi cations. Clean fl ame sensing rod with emery cloth | |
|
| to remove any contaminants that may have accumulated on flame | |
|
| sensing rod. | |
|
|
| |
| C. Module is not grounded. | Verify module is securely grounded to metal chassis of appliance. | |
|
| Verify that wire harness is fi rmly connected to the module. | |
|
|
| |
| D. Damaged pilot assembly or con- | Verify that ceramic insulator around the flame sensing rod is not | |
| taminated fl ame sensing rod. | cracked, damaged, or loose. Verify connection from flame sensing | |
|
| rod to white sensor wire. Clean fl ame sensing rod with emery cloth | |
|
| to remove any contaminants that may have accumulated on flame | |
|
| sensing rod. Verify continuity with a | |
|
| lowest range. Replace pilot if any damage is detected. | |
|
|
|
38 |