H. Control Module Operation

1.The control module has an ON/OFF/REMOTE selector switch that must be set. See Figure 2.3.

OFF Position: Appliance will ignore all power inputs and will not respond to any commands from a wall switch or remote. The unit should be in the OFF position during installation, service, battery installation, fuel conversion, and in the event that the control goes into LOCK-OUT mode as a result of an error code.

ON Position: Appliance will ignite and run continuously in the HI flame setting, with no adjustment in flame output. This mode of operation is primarily used for initial installation or power outage operation with battery backup.

REMOTE Position: Appliance will initiate commands from an optional wired wall switch and/or the wireless remote (RC300).

2.If using a wired wall switch with the module in REMOTE mode, the fl ame output can be adjusted with the HI/LO selector switch on the module. See Figure 2.3. Note that the flame HI/LO selector switch will become inactive once an optional remote control (RC200/RC300) is programmed to the control module. Note that the control module will always ignite the fireplace on HI and remain so for the initial 10 seconds of operation. If the HI/LO is switched to the LO position, the flame output will automatically drop to the lowest setting after the flame has been established for 10 sec. After this 10 second period, the fl ame can be adjusted from HI to LO with the switch.

3.The control module has safety feature that automatically shuts down the fi replace after 9 hours of continuous operation without receiving a command from the RC300 remote.

4.If you intend to use both an optional wired wall switch and the RC300 remote control to operate your fireplace, the wall switch will override any commands given by the remote.

 

SELECTOR

 

SWITCH

STATUS INDICATOR LED

FLAME HI/LO SWITCH

NG/LP SETTING

Figure 2.3 Control Module

5.Module Reset

This module may lock-out under certain conditions. When this occurs, the appliance will not ignite or respond to commands. The module will go into lock-out mode by emitting three audible beeps, then continuously displaying a RED/GREEN error code at its status indicator LED.

• Check battery tray. Remove batteries if installed.

Batteries should only be installed for use during power

 

outages. See Section G.

 

• Locate the module selector switch. (See Figure 2.3).

 

• Set the module selector switch to the OFF position.

 

• Wait five (5) minutes to allow possible accumulated gas

 

to clear.

 

• Set the module selector switch to ON or REMOTE

 

position.

 

• Start the appliance.

 

WARNING! Risk of Explosion! DO NOT press the mod-

ule reset switch more than one time within a five minute

 

time period. Gas may accumulate in firebox. Call a quali-

 

fied service technician.

 

I. Before Lighting Fireplace

Before operating this fi replace for the fi rst time, have a qualified technician:

Verify all shipping materials have been removed from inside and/or underneath the fi rebox.

Review proper placement of logs, ember material and/ or other decorative materials.

Check the wiring.

Check the air shutter adjustment.

Ensure that there are no gas leaks.

Ensure that the glass is sealed and in the proper position and that the integral barrier is in place.

WARNING! Risk of Fire/Asphyxiation! DO NOT oper- ate fireplace with fixed glass assembly removed.

An Intellifi re Plusignition system is standard with this appliance.

Quadra-Fire • QFI30, QFI35 • 2227-900 Rev. H • 1/11

9

Image 9
Contents Models What to do if you smell gasHOT Surfaces Congratulations Homeowner Reference InformationXxxxxxxx User Guide Table of ContentsLimited Lifetime Warranty Limited Lifetime Warranty Listing and Code Approvals Gas Fireplace Safety Operating Instructions User GuideYour Fireplace Remote Controls, Wall Controls and Wall Switches Fixed Glass AssemblyIPI Battery Tray/Battery Installation Clear SpaceModule Reset Control Module OperationBefore Lighting Fireplace Final inspection by Lighting Instructions IPIWhat to do if YOU Smell GAS GAS ValveFrequently Asked Questions Issue SolutionsAfter Appliance is Lit Maintenance Tasks-Homeowner Maintenance and ServiceGlass Cleaning Remote ControlGasket Seal and Glass Assembly Inspection Maintenance Tasks-Service TechnicianVenting LogsIPI Pilot Flame Patterns Burner Ignition and OperationTypical Appliance System Getting StartedDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Minimum Fireplace Opening Fireplace Size RequirementsMinimum Fireplace Size QFI35 QFI30Side View TOP View Mantel and Wall ProjectionsVent Termination Minimum Clearances Termination LocationsInstallation Preparation Connecting Vent Pipe Installing Vent Pipe and ApplianceVent Limits Venting ComponentsIPI Models Placing, Securing and Leveling the Appli- anceMasonry Installing Adaptor and Termination CapFactory Built Wood Burning Damper Flashing Kit OptionalFuel Conversion Gas InformationGas Pressure Gas ConnectionIntelliFire Plus Ignition System Wiring Wiring RequirementsON/OFF Switch Electrical InformationBLK Optional Accessories RequirementsAUX 300 Module FAN WHT GRN BLK Blowers Fan Wiring with RemoteClearances to Mantels or other Combustibles above Appliance FinishingAppliance Setup Install the Log Assembly Log Set Assembly LOGS-QFI30 Models QFI30Mates With Slot Mate Notch With Grate BAR For LOG #6Slot Install Back Refractory Log Set Assembly LOGS-QFI35 Models QFI35Slot on Log #2 LOG Slot Mate LOG Pins with LOG Slots Flat Spot For LOG #6 Air Shutter Setting Air Shutter SettingsQFI30 QFI35 Troubleshooting Symptom Possible Cause Corrective ActionIntelliFire Plus Ignition System To remove any contaminants that may have accumulated on flame Appliance Dimension Diagram Model DimensionsReference Materials Direct Vent Flex Liner Kits Vent Kits ComponentsContact Information