GAS PRESSURE

1.Check gas line pressure with unit firing at maximum rate. A minimum of 5.0” w.c. for natural gas or 10.9” w.c. for LP/ propane gas should be maintained for proper unit operation.

2.After line pressure has been checked and adjusted, check manifold pressure. Correct manifold pressure is shown on the unit rating plate. See figure 10 for gas pressure adjustment screw location. A natural gas to LP/propane gas changeover kit is required to convert unit. Refer to installation instructions provided with changeover kit for conversion procedure.

TABLE 4

NATURAL GAS MANIFOLD PRESSURES - IN.WG. (KPA)

 

 

ALTITUDE FT. (M)

 

 

 

 

MHU 50/80

 

0-2000

2000-4500

 

 

(0-610)

(610-1370)

 

 

 

 

 

 

 

 

50/80

 

4.0”WC (0.99 kPa)*

3.6”WC (0.89 kPa)

 

 

 

 

*No adjustment required.

TABLE 5

LP/PROPANE GAS MANIFOLD PRESSURES - IN.WG. (KPA)

 

 

ALTITUDE FT. (M)

 

 

 

 

MHU 50/80

 

0-2000

2000-4500

 

 

(0-610)

(610-1370)

 

 

 

 

 

 

 

 

50/80

 

10.5”WC (2.62 kPa)*

8.5”WC (2.12 kPa)

 

 

 

 

*No adjustment required.

LIMIT CONTROL

The limit control switch is factory set and not field adjustable.

LOUVER VANE ADJUSTMENTS

Rotate louver vanes to direct airflow upward, downward, straight, or any combination of these directions. When unit is installed

in an inverted position, louvers may be positioned in the same

manner.

COMBUSTION AIR PRESSURE SWITCH

This pressure switch checks for proper combustion air blower operation before allowing an ignition trial. The switch is factory set

and no field adjustment is necessary.

FLAME ROLLOUT SWITCH

The flame rollout switch(es) are located on the burner box top, behind the ignition control board. This normally closed switch opens on a temperature rise. Check for adequate combustion air

before manually resetting switch.

SERVICE

CAUTION Turn off gas and electrical power to unit before performing any maintenance or service operations on this unit. Remember to follow lighting instructions when putting unit back

into operation after service or maintenance.

If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a

temperature rating of at least 105°C.

Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any gas control which has been under

water.

BURNERS

1.Periodically examine burner flames for proper appearance during the heating season.

2.Before each heating season examine the burners for any deposits or blockage that may have occurred.

3.Clean burners as follows:

Turn off both electrical and gas supplies to unit.

Disconnect gas supply piping, high tension and sensor leads. Remove gas manifold. Remove burner tray.

Clean burners as necessary. Make sure that burner heads line up properly to ensure flame crossover. Check spark gap on electrode and adjust if required. The gap should be between 0.110 inch and 0.140 inch (2.79mm to 3.56mm). The gap may be checked with appropriately sized twist drills or feeler gauges.

Reinstall burner tray, gas manifold, high tension and sensor leads. Reconnect gas supply piping.

Restore electrical power and gas supply. Follow lighting instructions to light unit. Check burner flame.

4.Clean burner filter screen as follows:

Turn off both electrical and gas supply to unit.

Remove the filter screen from the inlet to the burner housing by squeezing and pulling out.

With screen out of the heater, clean with light soap and water or blow out with compressed air (blowing away from you).

Dry screen thoroughly with air and make sure all air passages in the screen are fully opened.

Replace screen into burner housing opening.

Restore electrical and gas supply.

Follow lighting instructions to light the heater. Check burner flame.

FLUE PASSAGEWAY AND FLUE BOX

The flue passages and flue box should be inspected and cleaned prior to each heating season. The sequence of operation should be as follows:

1.Turn off both electrical and gas supply to unit.

2.Disconnect combustion air blower wiring.

3.Remove screws securing flue box to unit. Remove flue box. If necessary, remove blower assembly from flue box. Clean flue box with wire brush.

4.Remove turbulator retention bracket and turbulators. Clean turbulators with wire brush.

5.Remove burners as described in section “BURNERS” section.

6.Clean tubes with a wire brush.

7.Reassemble unit. The combustion air and flue box gaskets should also be replaced during reassembly.

8.Restore electrical power and gas supply. Follow lighting instructions to light unit. Check operation of unit.

COMBUSTION AIR BLOWER

Under normal operating conditions, the combustion air blower should be checked and cleaned prior to the heating season with the power supply disconnected. Use a small brush to clean blower wheel.

Compact Unit / Utility Heater

E-12Operating Instructions and Owner’s Manual

Image 12
Contents For Your Safety MR. HEATER, INC., 4560 W TH ST., CLEVELAND, Ohio 44135Contents General Hazard WarningMHU 50/MHU 80 Unit Dimensions DimensionTOP View Side ViewGarage Installations ShippingRequirements CSA in the USA Requirements CSA in CanadaUnit Heater Installation Combustion and Ventilation AIRVenting General Recommendations and RequirementsHorizontal Venting General Vent Termination on Single Wall VentHorizontal Venting Commercial Horizontal Venting ResidentialCondensate Drain Through TEE Pipe and Drain Loop Venting Using a Masonry Chimney Horizontal Venting Residential InstallationRemoval of Unit from Common Vent Line Voltage Field Wiring Electrical ConnectionsGAS Supply Connection GAS Supply to Unit HeaterLeak Check Start UP and OperationGAS Connection Unit START-UPAdjustments Service Ladder Diagram Optional Thermostat InstallationRepair Parts ElectricalFlue and Chimney Failure to OperateParts List See Back page for Parts Ordering InformationFor Information Regarding Service Limited WarrantyParts Ordering Information Instrucciones DE USO Y Manual DEL Usuario Para SU SeguridadAdvertencia ContenidoEL Estado DE California Exige LAS Siguientes Advertencias Dimensiones DE LAS Unidades MHU 50/MHU Vista SuperiorVista Posterior DimensiónEnvío Requisitos CSA EN EE. UURequisitos CSA EN Canadá Instalaciones EN GarajeAire DE Combustión Y Ventilación VentilaciónInstalación DEL Calentador Requisitos Y Recomendaciones GeneralesVentilación Horizontal General Ventilación Horizontal Comercial Ventilación Horizontal ResidencialVentilación CON UNA Chimenea DE Mampostería Quitar LA Unidad DE UNA Ventilación ComúnVentilación Horizontal Instalación Residencial Conexiones Eléctricas Cableado DEL Inductor DE Voltaje DE LíneaConexión DE GAS Verificación DE FugasEncendido Y Funcionamiento Encendido DE LA UnidadAjustes Mantenimiento Diagrama DE Escalones Instalación DEL Termostato OpcionalSoplador DE Aire DE Combustión Sistema EléctricoGAS DE Combustión Y Chimenea Falla DE FuncionamientoLista DE Piezas VER AL Dorso LA Información Para Ordenar PartesInformación Para Realizar Pedidos DE Piezas SI Desea Obtener Información Acerca DE ReparacionesGarantía Limitada Guide D’UTILISATION ET Manuel DU Propriétaire Pour Votre SécuritéAvertissement Table DES MatièresAvertissement Général DE Danger Dimension DES Appareils MHU 50/MHU VUE EN PlanInstallations Dans UN Garage ExpéditionExigences CSA AUX É.-U Exigences CSA AU CanadaExigences ET Recommandations Générales VentilationAIR DE Combustion ET DE Ventilation Appareil DE Chauffage / Radiateur UtilitaireVentilation Horizontale Générale Ventilation Horizontale Commerciale Ventilation Horizontale Installation Résidentielle Ventilation Utilisant UNE Cheminée EN MaçonnerieRetrait DUN Appareil DE LA Ventilation Commune Connexions Électriques Câblage SUR Place À LA Tension DE LigneRaccordement À Lalimentation EN GAZ Alimentation EN GAZ Vers Lappareil DE ChauffageAvertissement Raccordement AU GAZ Vérification DE Fuites DE GAZDémarrage ET Fonctionnement Démarrage DE LappareilRéglages Entretien ET Réparation Diagramme EN Escalier Installation DU Thermostat EN OptionVentilateur DE Lair DE Combustion Circuit ÉlectriqueConduit DE Cheminée ET Cheminée Lappareil NE Fonctionne PASListe DES Pièces 50 000 et 80 000 BTU F26016350 000 et 80 000 BTU F260164 Informations SUR LA Commande DE Pièces Fournisseur DE Services Dentretien QualifiéPour Plus D’INFORMATIONS Concernant L’ENTRETIEN Garantie Limitée