Mr. Heater MHU 80, MHU 50 Combustion and Ventilation AIR, Venting, Unit Heater Installation

Page 5

These units are certified for residential applications. For installation in a residential garage, these units must be installed so that burners and ignition source are located no less than 18” (457mm) above floor. Heater must be located or protected to avoid physical damage by vehicles. Refer to CSA B149.1, Natural Gas and Propane Installation Code current edition.

In a confined area, the heater must be installed in accordance with the CSA B149.1, Natural Gas and Propane Installation Code. Be sure to check with local codes and ordinances for additional requirements.

UNIT HEATER INSTALLATION

Unit is shipped ready for installation. Unit may be installed as shown in figure 1 or inverted 180o depending on desired location as governed by clearances, vent connection, air direction, gas supply, electrical supply and service accessibility.

1.If installing unit in an inverted position: Remove and retain screws securing door and rotate door 180o. Secure with retained screws. Rotate louvers directing airflow as desired.

2.Choose location for mounting brackets.

3.Remove and retain three screws along top edge (bottom edge when inverted) of front of unit.

4.Align screw holes on mounting bracket with holes along top edge (either upright or inverted) of unit. Secure one mounting bracket to front of unit with retained screws.

Secure other mounting bracket to back of unit with screws provided in bag assembly containing flue transition.

5.To support unit, secure mounting bracket to ceiling joist or truss. Unit may also hang on rods as shown in figure 1.

FIGURE 1

INSTALL UNIT / UTILITY HEATER

SUPPORT

MOUNTINGRODS BRACKETS (2)

COMBUSTION AND VENTILATION AIR

Adequate facilities for supplying air for combustion and ventilation must be provided in accordance with the latest edition of section 5.3, Air for Combustion and Ventilation, of the National Fuel

Gas Code, ANSI Z223.1, in the U.S.A., CSA B149.1 Natural Gas and Propane Installation Code, or applicable provisions of local building codes.

All gas fired appliances require air to be used for the combustion process. In many buildings today, there is a negative indoor air pressure caused by exhaust fans, etc. If sufficient quantities of combustion air are not available, the heater or another appliance will operate in an inefficient manner, resulting in incomplete combustion which can result in the production of excessive carbon monoxide.

CAUTION Insufficient combustion air can cause headaches, nausea, dizziness, asphyxiation or death.

If indoor air is to be used for combustion, it must be free of the following substances or the life of the heat exchanger will be adversely affected: chlorine, carbon tetrachloride, cleaning solvent, halogen refrigerants, acids, cements and glues, printing inks, fluorides, paint removers, varnishes, or any other corrosives.

VENTING

A – GENERAL RECOMMENDATIONS AND REQUIREMENTS

NOTE: The vent is a passageway, vertical or nearly so, used to convey flue gases from an appliance, or its vent connector, to the outside atmosphere. The vent connector is the pipe or duct that connects a fuel-gas burning appliance to a vent or chimney.

Unit heaters must be vented in compliance with all local codes or requirements of the local utility, the current standards of the (American) National Fuel Gas Code, ANSI Z223.1 or (Canada)

CSA B149.1 Natural Gas and Propane Installation Code, and the following instructions.

A metal stamped/extruded transition is supplied with this certified unit. It must not be modified or altered and must be installed

on the outlet of the induced draft blower assembly prior to the installation of the vent or vent connector. Failure to comply with this requirement will void the certification of the unit by the approval agencies. All joints shall be secured with at least two corrosion resistant screws. All joints must be checked for gas tightness after installation.

TABLE 2

MAXIMUM VENT LENGTHS

HORIZONTAL VENTS

No. of

ft

m

Elbows

 

 

 

 

 

 

 

 

1

25

7.6

 

 

 

2

20

6.1

 

 

 

3

15

4.6

 

 

 

4

10

3.0

 

 

 

5

5

1.5

 

 

 

Maximum length of vent connector not to exceed 30 ft. (9.1m).

Compact Unit / Utility Heater

E-5

Operating Instructions and Owner’s Manual

Image 5
Contents MR. HEATER, INC., 4560 W TH ST., CLEVELAND, Ohio 44135 For Your SafetyGeneral Hazard Warning ContentsDimension MHU 50/MHU 80 Unit DimensionsTOP View Side ViewShipping Garage InstallationsRequirements CSA in the USA Requirements CSA in CanadaCombustion and Ventilation AIR Unit Heater InstallationVenting General Recommendations and RequirementsVent Termination on Single Wall Vent Horizontal Venting GeneralCondensate Drain Through TEE Pipe and Drain Loop Horizontal Venting CommercialHorizontal Venting Residential Removal of Unit from Common Vent Venting Using a Masonry ChimneyHorizontal Venting Residential Installation Electrical Connections Line Voltage Field WiringGAS Supply Connection GAS Supply to Unit HeaterStart UP and Operation Leak CheckGAS Connection Unit START-UPAdjustments Service Optional Thermostat Installation Ladder DiagramElectrical Repair PartsFlue and Chimney Failure to OperateSee Back page for Parts Ordering Information Parts ListParts Ordering Information For Information Regarding ServiceLimited Warranty Para SU Seguridad Instrucciones DE USO Y Manual DEL UsuarioEL Estado DE California Exige LAS Siguientes Advertencias AdvertenciaContenido Vista Superior Dimensiones DE LAS Unidades MHU 50/MHUVista Posterior DimensiónRequisitos CSA EN EE. UU EnvíoRequisitos CSA EN Canadá Instalaciones EN GarajeVentilación Aire DE Combustión Y VentilaciónInstalación DEL Calentador Requisitos Y Recomendaciones GeneralesVentilación Horizontal General Ventilación Horizontal Residencial Ventilación Horizontal ComercialVentilación Horizontal Instalación Residencial Ventilación CON UNA Chimenea DE MamposteríaQuitar LA Unidad DE UNA Ventilación Común Cableado DEL Inductor DE Voltaje DE Línea Conexiones EléctricasVerificación DE Fugas Conexión DE GASEncendido Y Funcionamiento Encendido DE LA UnidadAjustes Mantenimiento Instalación DEL Termostato Opcional Diagrama DE EscalonesSistema Eléctrico Soplador DE Aire DE CombustiónGAS DE Combustión Y Chimenea Falla DE FuncionamientoVER AL Dorso LA Información Para Ordenar Partes Lista DE PiezasGarantía Limitada Información Para Realizar Pedidos DE PiezasSI Desea Obtener Información Acerca DE Reparaciones Pour Votre Sécurité Guide D’UTILISATION ET Manuel DU PropriétaireAvertissement Général DE Danger AvertissementTable DES Matières VUE EN Plan Dimension DES Appareils MHU 50/MHUExpédition Installations Dans UN GarageExigences CSA AUX É.-U Exigences CSA AU CanadaVentilation Exigences ET Recommandations GénéralesAIR DE Combustion ET DE Ventilation Appareil DE Chauffage / Radiateur UtilitaireVentilation Horizontale Générale Ventilation Horizontale Commerciale Retrait DUN Appareil DE LA Ventilation Commune Ventilation Horizontale Installation RésidentielleVentilation Utilisant UNE Cheminée EN Maçonnerie Câblage SUR Place À LA Tension DE Ligne Connexions ÉlectriquesRaccordement À Lalimentation EN GAZ Alimentation EN GAZ Vers Lappareil DE ChauffageVérification DE Fuites DE GAZ Avertissement Raccordement AU GAZDémarrage ET Fonctionnement Démarrage DE LappareilRéglages Entretien ET Réparation Installation DU Thermostat EN Option Diagramme EN EscalierCircuit Électrique Ventilateur DE Lair DE CombustionConduit DE Cheminée ET Cheminée Lappareil NE Fonctionne PAS50 000 et 80 000 BTU F260164 Liste DES Pièces50 000 et 80 000 BTU F260163 Fournisseur DE Services Dentretien Qualifié Informations SUR LA Commande DE PiècesPour Plus D’INFORMATIONS Concernant L’ENTRETIEN Garantie Limitée