KHLDV Series Gas Fireplace

ventING installation

 

 

termination clearances for buildings with combustible and noncombustible exteriors

G G=6" (152mm)

V

Combustible – 6" (152 mm)

Noncombustible – 2" (51mm)

Inside Corner

G

V

G = Combustible 24"(610mm) Noncombustible 18"(457mm)

V

F F=6" (152mm)

Outside Corner

H

V

J

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

 

D

C

C

 

V

E

C = Maximum depth of 48" (1219mm) for alcove location

D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)

E = Clearance from corner in alcove location

Combustible - 6" (152mm)

Noncombustible - 2" (51mm)

Balcony with No Side Wall

Balcony with Perpendicular

Figure 9 -

Side Wall

 

Allowable Venting Chart

 

How To Use The Vent Graph

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimensions of the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimen- sion on the Sidewall Vent Graph below, locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fire- place in accordance with same.

Example: If the vertical dimension from the floor of the fireplace is 11' (3.4 m) the horizontal run to the face of the outer wall must not exceed 16' (4.9 m).

Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system.

Alcove Location

 

 

Dimensions in

 

40

 

 

Feet

 

 

 

 

Vertical

38

 

 

 

36

 

 

 

34

 

 

 

 

 

 

Dimension

32

 

 

 

30

 

 

 

28

 

 

 

26

 

 

 

 

 

 

From the Floor of Unit

24

 

 

 

22

 

 

 

20

 

 

 

18

 

 

eg: A

16

 

 

14

 

 

PipeVentHorizontal

12

 

 

 

 

 

to

10

 

 

 

 

 

 

the

8

 

 

 

 

 

 

Center

6

 

 

 

4

 

 

 

2

 

 

 

of

 

 

 

the

2

4

6

8 10 1214 16 1820

 

 

Horizontal dimension from the finished outside wall

Figure 10 -

to the center of the pipe on the fireplace

 

Rear Wall Venting Graph

14

73D0024

Image 14
Contents Khldv Series Direct Vent Gas Fireplace Operating Instructions Signature Command Signature Command System Operation InstructionsInstaller OwnerNever connect unit to private non Important Safety Information and Code ApprovalCode Approval Utility gas wells. This gas is commonlyHigh Elevations Product featuresGas Specifications & Orifice Size GAS pressuresFireplace and Framing Dimensions KHLDV400 KHLDV500Firebox framing PRE-INSTALLATION InformationBefore You Start Cold Climate InsulationPRE-INSTALLATION Information Fireplace LocationMantel clearances ClearancesClearances to combustibles Side ViewFinishing Material Never install combustible materialsSECURe Fireplace to floor or framing Over front face of fireplaceFailure to follow these instructions will void Warranty Venting InstallationInstallation precautions LifeFor horizontal termination Installation planningInstalling a vent system in an outside chase For vertical terminationCanadian Installations1 US Installations2 General Venting Information Termination LocationHow To Use The Vent Graph Outside CornerStep Vertical Sidewall InstallationAlways install horizontal venting on a level plane VERTICAL/Horizontal termination configurations 610 mm Mm MaxTo be installed around the termination area VentING installationBelow Grade Installations VentNG installation Vertical through-the-roof applica- tionsExample Installation for vertical termina- tionFlat ceiling installation Termination Heights for Vents Above Flat or Sloped Roofs Check gas type Fireplace installationInstalling gas piping to fireplace / burner system location Natural Gas Propane/LPMillivolt Checking GAS Pressure and Electrical installation Do not connect wall switch to a 110V circuit Millivolt Remote Wall Switch InstallationRemote Wall mounted Switch Optional Fan/Blower System BlotkhlMillivolt Optional FAN/BLOWER System WA RNI GNBlower Access Covers Initial lighting Millivolt Operating InstructionsWhat to do if YOU Smell GAS Never use an open flame to check for gas leakApproved leak testing method Never check for gas leak with open flamePilot position Main burner switchLighting the burner Connecting to main electrical power supply Optional Accessory RequirementsElectrician. Main power must be off when Or performing service. All wiring shall beWall Switch Installation Junction BOX WiringCommand Center Wall Installation Do not connect wall switch to 110Electrical Installation Signature command Optional fan blower system Blotkhlsc Signature Command BlowerSignature command Operating Instructions Command Center OPERATing InstructionsCommand Center FeaturesBattery Installation Function Operation Default Setting System CONFIGURATION/SETUPKey Combinations for System Settings Function Operation Command Center OperationsSelf Diagnostics Chart For accurate temperature readings to appear on Due to the sensitive temperature monitoringPerature before accurate room temperatures Turn appliance OFF at the Master Switch ifCode setting, as they will communicate with Setting Privacy Code on TransmitterDo not use two 2 or more remote control sys Resetting the transmitterSmart Mode Option for Thermostat Mode Figure Timer ModeThermostat Mode Light Brightness Control Blower On Delay Time and Off Delay Time Setup FigureBlower Speed Control AUX Control Rear Burner On/Off Control Safety FeaturesSetting up Blank Screen or Constant Display in Idle Using the Mounting Base Symptom Causes ActionGlass removal Glass Frame RemovalRock wool placement Final installationBRICK, light bulb, and lens placement Log placement LOG placementPlace the upper right rear log over the rear log Cleaning and maintenance Burner, Pilot and Control Compart- mentGlass Door Cleaning and maintenanceVent SysteM LogsPoSSIBLE Cause TroubleshootingStanding Pilot Ignition Troubleshooting Signature Command System TroubleshootingAccessories / Field Installed Options Replacement PartsFirebox components and accessories Description QtyReplacement Parts Standing Pilot Millivolt controlLP to Natural Gas AccessoriesFuel Conversion Kits Millivolt Control Natural Gas to LP Signature Command System KHLDV400 KHLDV500 Logs VENTing components Or Mhsc Selkirk Box Description Venting Components for 5xCurrent Old Simpson Duravent Requirements for the Commonwealth of Massachusetts Manufacturer RequirementsBasic Warranty Lifetime WarrantyFive Year Warranty Mhsc Model EnerGuide Ratings
Related manuals
Manual 1 pages 58.97 Kb Manual 1 pages 53.14 Kb

KHLDV500, KHLDV400 specifications

The Monessen Hearth KHLDV400 is a high-performance gas fireplace designed to provide both warmth and aesthetic appeal to any living space. This unit is engineered with modern technology, making it an excellent choice for homeowners looking to enhance their home’s atmosphere while enjoying the benefits of efficient heating.

One of the standout features of the KHLDV400 is its impressive heating capability. With an input of 40,000 BTUs, this gas fireplace is capable of heating spaces effectively, making it perfect for medium to large rooms. This fireplace utilizes a direct vent system, ensuring that combustion gases are efficiently expelled outside, while fresh air is drawn from the exterior to support the flame. This makes for a safe and environmentally friendly operation, as it minimizes indoor air pollution.

The KHLDV400 also boasts an innovative burner design that creates realistic flames, mimicking the look of traditional wood-burning fires. The fireplace comes with a choice of decorative media options, including glowing embers and fire glass, allowing homeowners to customize the look of their fireplace to match their personal style.

Another notable characteristic of the KHLDV400 is its intuitive control system. It can be operated via a handheld remote or wall switch, providing convenience and ease of use. Homeowners can adjust the flame height and heat output with simple controls, ensuring comfort at all times. Additionally, it features a standing pilot option that enhances its reliability and safety during operation.

Durability and quality craftsmanship are hallmarks of the Monessen brand, and the KHLDV400 is no exception. The fireplace is built with high-quality materials designed to withstand the test of time. Its sleek, contemporary design features a clean-face appearance that enhances any decor, while the glass front allows for an unobstructed view of the beautiful flame display.

With its combination of style, advanced technology, and efficient heating capabilities, the Monessen Hearth KHLDV400 is an exceptional choice for those looking to invest in a gas fireplace that delivers both performance and elegance to their home.