Majestic Appliances DVB4136 manual + B = 17 Max

Page 18

DVB4136 Direct Vent Gas Fireplace

 

3 x 90°

3 x 90°

 

Elbows

Elbows

 

 

FP1176

Fig. 26

Maximum three (3) 90° elbows per installation.

 

 

36"

 

 

(914mm)

 

 

Max.

 

 

36"

 

 

(914mm)

 

 

Max.

FP1177

Fig. 27 Maximum horizontal run with no rise.

If a 90° elbow is used in the horizontal vent run (level height maintained) the horizontal vent length is reduced by 36” (914 mm). (Fig. 28, 29) This does not apply if the 90° elbows are used to increase or redirect a vertical rise. (Fig. 26)

Example: According to the vent graph (Page 14) the maximum horizontal vent length in a system with a 7¹⁄₂’ (2.3 m) rise is 20’ (6 m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17’ (5.2 m).

A B

A + B = 17' (Max.)

(5.2m)

7'6"

(2.3m)

FP1178

Fig. 28 Horizontal run reduction.

18

7’

(2.1 m)

A10’

(3 m)

B

 

8’

(2.4 m)

V584-201

Fig. 29 Maximum vent run with elbows.

In Figures 28 & 29, dimension A plus B must not be greater than 17’ (5.2m)

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (457 mm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system is 270°. (Fig. 30)

Example:

 

Elbow 1

= 90°

 

 

Elbow 2

= 45°

 

 

Elbow 3

= 45°

 

 

Elbow 4

= 90°

 

Total angular variation

= 270°

 

1

 

1

 

2

 

2

 

3

 

3

 

4

 

4

 

 

1 + 2 + 3 + 4 = 270°

FP1180

Fig. 30

Maximum elbow usage.

 

 

 

 

20012322

Image 18
Contents Direct Vent Gas Fireplace Table of Contents Installation & Operating Instructions Please Read the Following CarefullyRequirements for the Commonwealth of Massachusetts Gas Equipment Venting System not ProvidedFireplace Dimensions Installed as Top Vent Ref. DVB4136Fireplace Dimensions Installed as Rear Vent Framing Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mmRef. DV4136 Mantels Locating Your FireplaceClearance to Combustibles HearthGas Specifications Gas Line InstallationFinal Finishing Gas Inlet and Manifold PressuresRemote ON/OFF Switch Installation Alternate Switch LocationEB-1 Electrical Box EB-1 receptacle Optional Top Vent Application Complete conversionGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationGeneral Information Assembling Vent Pipes Canadian InstallationsUSA Installations Flex Vent PipesHow to Use the Vent Graph Twist Lock PipesRear Wall Vent Application Rear Wall Vent Installation Twist Lock Pipe Zero clearance sleeve is only required for combustible wallsRear Wall Vent Installations Flex Vent Pipe Vertical Sidewall Application+ B = 17 Max Vertical Sidewall Installation Twist Lock Pipe Always install horizontal venting on a level planeVertical Sidewall Installation Flex Vent Pipe Horizontal length requirementBelow Grade Installation Vertical Through-the-Roof ApplicationVertical Through-the-Roof Installation Maximum elbow usageMin 610 mm Venting Components Operating Instructions Log Identification Chart Replacement Ceramic Hearth Panels if providedInstallation of Logs Logs ID #Left Log Top Center Log Top Front Log Top Right Log Flame & Temperature Adjustment Flame CharacteristicsInspecting the Venting System Lighting and Operating Instructions For Fireplaces Equipped with the SIT 820 ValveTo Turn Off Gas To Heater Lighting Instructions Turning Off the Gas to the ApplianceValve in the on position Lighting & Operating Instructions For Fireplaces equipped with AF4000 Gas ValveTroubleshooting the Gas Control System SIT Nova 820 Millivolt ValveTroubleshooting AF4000 ValveTroubleshooting AF4000 Valve Igniter operationAF4000 MOD Module End On Manual Mode Shut Off ProcedureTransmitter Operation Off Mode Instructions for RF Comfort Control ValveFan Override During Auto Mode Delay Timer ModeAuto Mode Change Between F/C Temperature UnitsLED Count Service Action Auto PathLocal Path On Path Burner Orifice Conversion Conversions must be completed by qualified personnelFuel Conversion Instructions SkyTech ValveInstallation Precautions Conversion ProcedurePilot Orifice Conversion Injector Orifice Size Matrix Front Rear MinimumModel Fuel Type Front Rear Logs May Be HOT MaintenanceCleaning the Standing Pilot Control System Burner and Burner CompartmentDescription DVB4136 DVB4136 Description Fuel Conversion Kits FK24 Fan Assembly Optional AccessoriesFK12 Fan Assembly Hard Direct Wire Hook UpCeramic Refractory Panels Remote ControlsInstallation Instructions Decorative Bay WindowsBattery Backup Installation ProcedureArch/Square Face Kit Limited Lifetime Warranty Efficiency Ratings