Majestic Appliances DVB4136 manual Troubleshooting AF4000 Valve, Igniter operation

Page 35

DVB4136 Direct Vent Gas Fireplace

Troubleshooting AF4000 Valve (continued)

Figure 58: AF4000

MOD Module Right

Side

Continuous PIlot Off/On Switch

Remote/Off

SwitchAdjustment

Figure 59: AF4000 MOD Module Left Side

 

“I” Pilot

FP1762

“S” Pilot Connection

 

Connection

 

 

 

Learn Button

AUX Connection

FP1763

Pilot will not light/stay lit

Verify the gas supply is turned on.

 

Verify the receiver is receiving the signal from the transmitter by listening for a

 

beep from the receiver when ON is pressed on the transmitter. If you do not hear

 

a beep, ensure the module has learned the transmitter (see above).

 

Ensure the orange lead from the pilot assembly igniter is securely connected to

 

the terminal labeled “I” and the white lead from the flame rectification sensor is

 

securely connected to the terminal labeled “S” on the control module. (Fig. 58)

 

Make sure the orange and white leads from the module are securely connected to

 

the terminals labeled “PILOT” on the valve body. (Fig. 61)

 

Ensure the black GROUND wire is securely connected to an appropriate metal

 

portion of the valve or pilot assembly. A proper ground is essential to spark

 

igniter operation.

 

Make certain the pilot flame is in contact with the flame rectification sensor on the

 

pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig.

 

61) If the pilot flame is too small it will not contact the flame rectification sensor

 

and will not complete the safety circuit.

 

 

Pilot flame is always on/ will

Ensure the CONTINUOUS PILOT switch on the control module (Fig. 58) is set to

not extinguish

OFF.

 

 

Main flame will not light

Verify the gas supply is turned on.

 

Ensure the pilot flame will ignite. If not, see pilot flame troubleshooting above.

 

Make sure the green and white leads from the module are securely connected to

 

the terminals labeled “MAIN: on the valve body. (Fig. 61)

 

Make certain the pilot flame is in contact with the flame rectification sensor on the

 

pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig.

 

61) If the pilot flame is too small it will not contact the flame rectification sensor

 

and will not complete the safety circuit.

 

Ensure the pilot flame is properly located to ignite the main flame.

20012322

35

Image 35
Contents Direct Vent Gas Fireplace Table of Contents Please Read the Following Carefully Installation & Operating InstructionsGas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsRef. DVB4136 Fireplace Dimensions Installed as Top VentRef. DV4136 Fireplace Dimensions Installed as Rear VentFraming Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mm Hearth Locating Your FireplaceClearance to Combustibles MantelsGas Inlet and Manifold Pressures Gas Line InstallationFinal Finishing Gas SpecificationsEB-1 Electrical Box Remote ON/OFF Switch InstallationAlternate Switch Location EB-1 receptacle Complete conversion Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Flex Vent Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesRear Wall Vent Application How to Use the Vent GraphTwist Lock Pipes Zero clearance sleeve is only required for combustible walls Rear Wall Vent Installation Twist Lock PipeVertical Sidewall Application Rear Wall Vent Installations Flex Vent Pipe+ B = 17 Max Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeHorizontal length requirement Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationMaximum elbow usage Vertical Through-the-Roof InstallationMin 610 mm Venting Components Operating Instructions Logs ID # Replacement Ceramic Hearth Panels if providedInstallation of Logs Log Identification ChartLeft Log Top Center Log Top Front Log Top Right Log Inspecting the Venting System Flame & Temperature AdjustmentFlame Characteristics To Turn Off Gas To Heater Lighting and Operating InstructionsFor Fireplaces Equipped with the SIT 820 Valve Valve in the on position Lighting InstructionsTurning Off the Gas to the Appliance For Fireplaces equipped with AF4000 Gas Valve Lighting & Operating InstructionsSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveAF4000 MOD Module End Instructions for RF Comfort Control Valve Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeChange Between F/C Temperature Units Delay Timer ModeAuto Mode Fan Override During Auto ModeAuto Path LED Count Service ActionLocal Path On Path SkyTech Valve Conversions must be completed by qualified personnelFuel Conversion Instructions Burner Orifice ConversionPilot Orifice Conversion Installation PrecautionsConversion Procedure Model Fuel Type Front Rear Injector Orifice Size MatrixFront Rear Minimum Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Logs May Be HOTDescription DVB4136 DVB4136 Description Fuel Conversion Kits Hard Direct Wire Hook Up Optional AccessoriesFK12 Fan Assembly FK24 Fan AssemblyDecorative Bay Windows Remote ControlsInstallation Instructions Ceramic Refractory PanelsArch/Square Face Kit Battery BackupInstallation Procedure Limited Lifetime Warranty Efficiency Ratings