Majestic Appliances DVB4136 manual Below Grade Installation, Vertical Through-the-Roof Application

Page 21

Below Grade Installation

When it is not possible to meet the required vent ter- minal clearances of 12” (305 mm) above grade level, a snorkel kit is recommended. It allows installation depth down to 7” (178 mm) below grade level. The 7” (178

mm)is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are ob- served. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termina- tion area.

DVB4136 Direct Vent Gas Fireplace

Do not back fill around snorkel.

A clearance of at least 4” must be main- tained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fas- ten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. (Fig. 38)

If installing a snorkel, a minimum 24” (610 mm) vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36” (914 mm). This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24” (610 mm).

1.

Establish vent hole through the wall (Fig. 31)

2.

Remove soil to a depth of approximately 16”

 

(406mm) below base of snorkel. Install drain pipe.

Foundation

Recess

Watertight

Seal Around

PIpe

Snorkel

Wall Screws

Sheet Metal Screws

BG401

 

Install window well (not supplied). Refill hole with 12”

 

(305 mm) of coarse gravel leaving a clearance of ap-

 

proximately 4” (102 mm) below snorkel. (Fig. 37)

3.

Install vent system.

4.

Ensure a watertight seal is made around the vent

 

pipe coming through the wall.

5.

Apply high temperature sealant caulking (supplied)

 

around the 4” and 7” snorkel collars.

6.

Slide the snorkel into the vent pipes and secure to

 

the wall.

7.

Level the soil so as to maintain a 4” (102 mm) clear-

 

ance below snorkel. (Fig. 37)

Fig. 38 Snorkel installation, recessed foundation.

Vertical Through-the-Roof Application

This gas fireplace has been approved for:

Vertical installations up to 40’ (12 m) in height. Up to a 10’ (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. (Fig. 39)

Up to two 45° elbows may be used within the hori- zontal run. For each 45° elbow used on the horizon- tal plane, the maximum horizontal length must be reduced by 18” (450 mm).

Zero Clearance Sleeve

(if required)

Firestop

7” Pipe

24” (610mm) Minimum*

Screws

7TDVSNORK

(Snorkel)

4” (102mm) Clearance Min.

Window

Well

Gravel

Drain

Foundation Wall

*A minimum of 24” (610 mm) vertical pipe must be installed when using the 7TDVSNORK Kit.

Example: Maximum horizontal length:

No elbows

= 10’ (3 m)

1 x 45° elbow

= 8.5’ (2.6 m)

2 x 45° elbows = 7’ (2.1 m)

A minimum of an 8’ (2.5 m) vertical rise is required.

Two sets of 45° elbow offsets may be used within the vertical sections. From 0 to a maximum of 8’ (2.5 m) of vent pipe can be used between elbows. (Fig. 40)

7DVCS supports offsets. (Fig. 42) This application will require that you first determine the roof pitch and use the appropriate starter kit. (Refer to Venting Components List)

The maximum angular variation allowed in the sys- tem is 270°. (Fig. 40)

The minimum height of the vent above the highest point of penetration through the roof is 2’ (610 mm). (Fig. 43) Refer to note 2, Page 14.

BG402a

Fig. 37 Below grade installation.

20012322

21

Image 21
Contents Direct Vent Gas Fireplace Table of Contents Please Read the Following Carefully Installation & Operating InstructionsGas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsRef. DVB4136 Fireplace Dimensions Installed as Top VentFireplace Dimensions Installed as Rear Vent Framing Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mmRef. DV4136 Clearance to Combustibles Locating Your FireplaceMantels HearthFinal Finishing Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresRemote ON/OFF Switch Installation Alternate Switch LocationEB-1 Electrical Box EB-1 receptacle Complete conversion Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes Flex Vent PipesHow to Use the Vent Graph Twist Lock PipesRear Wall Vent Application Zero clearance sleeve is only required for combustible walls Rear Wall Vent Installation Twist Lock PipeVertical Sidewall Application Rear Wall Vent Installations Flex Vent Pipe+ B = 17 Max Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeHorizontal length requirement Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationMaximum elbow usage Vertical Through-the-Roof InstallationMin 610 mm Venting Components Operating Instructions Installation of Logs Replacement Ceramic Hearth Panels if providedLog Identification Chart Logs ID #Left Log Top Center Log Top Front Log Top Right Log Flame & Temperature Adjustment Flame CharacteristicsInspecting the Venting System Lighting and Operating Instructions For Fireplaces Equipped with the SIT 820 ValveTo Turn Off Gas To Heater Lighting Instructions Turning Off the Gas to the ApplianceValve in the on position For Fireplaces equipped with AF4000 Gas Valve Lighting & Operating InstructionsSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveAF4000 MOD Module End Transmitter Operation Off Mode Shut Off ProcedureOn Manual Mode Instructions for RF Comfort Control ValveAuto Mode Delay Timer ModeFan Override During Auto Mode Change Between F/C Temperature UnitsAuto Path LED Count Service ActionLocal Path On Path Fuel Conversion Instructions Conversions must be completed by qualified personnelBurner Orifice Conversion SkyTech ValveInstallation Precautions Conversion ProcedurePilot Orifice Conversion Injector Orifice Size Matrix Front Rear MinimumModel Fuel Type Front Rear Cleaning the Standing Pilot Control System MaintenanceLogs May Be HOT Burner and Burner CompartmentDescription DVB4136 DVB4136 Description Fuel Conversion Kits FK12 Fan Assembly Optional AccessoriesFK24 Fan Assembly Hard Direct Wire Hook UpInstallation Instructions Remote ControlsCeramic Refractory Panels Decorative Bay WindowsBattery Backup Installation ProcedureArch/Square Face Kit Limited Lifetime Warranty Efficiency Ratings