Vertical Sidewall Installation

Twist Lock Pipe

Step 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 31) (For combustible walls first frame in opening.)

NOTE: When using flex vent, the opening will have to be measured according to the 1/2” (13 mm) rise in 12” (305 mm) vent run.

Combustible Walls: Cut a 9³⁄”H x 9³⁄”W (240 mm x 240 mm) hole through the exterior wall and frame as shown. (Fig. 31)

Noncombustible Walls: Hole opening must be 7¹⁄” (191 mm) in diameter.

Vent Opening for Combustible Walls

DVB4136 Direct Vent Gas Fireplace

Adjustable Zero

Max. Length

Clearance Sleeve

12” (305 mm)

 

 

#8 Screws (2)

#8 Screws

 

(2)

 

 

#8 Screws

 

(2)

Firestop

Adjustable Zero

 

Clearance Sleeve

ZCS101

Fig. 32 Adjustable zero clearance sleeve.

 

9³⁄

(240 mm)

9³⁄

(240 mm)

Fireplace Hearth

Framing Detail

FP1181

Fig. 33 Vertical height requirements.

Step 4

Opening for Noncombustible Wall

7¹⁄

(190 mm)

Fireplace Hearth

VO584-100

Fig. 31 Locate vent opening on wall.

Step 2

Measure wall thickness and cut zero clearance sleeve parts to proper length (MAXIMUM 12” / 305 mm). Assemble sleeve and attach to firestop with #8 sheet metal screws (supplied). Install firestop assembly. (Fig. 32)

Zero clearance sleeve is only required for combustible walls.

Step 3

Place fireplace into position. Measure the vertical height

(X)required from the base of the flue collars to the cen- ter of the wall opening. (Fig. 33)

Apply a band of silicone to the inner and outer flue collars of the fireplace and using appropriate length of pipe section(s) attach to fireplace with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints with three (3) sheet metal screws. Wipe off any excess high temperature sealant.

Step 5

Measure the horizontal length requirement including a 2” (51mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51mm) (or the distance required if installing a second 90° elbow). (Fig. 34)

Always install horizontal venting on a level plane.

Step 6

Use appropriate length of pipe sections - telescopic or fixed - and install. The sections which go through the wall are packaged with the starter kit, and can be cut to suit if necessary.

Sealing vent pipe and firestop gaps with high tem- perature sealant will restrict cold air being drawn in around fireplace.

20012322

19

Image 19
Contents Direct Vent Gas Fireplace Table of Contents Please Read the Following Carefully Installation & Operating InstructionsGas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsRef. DVB4136 Fireplace Dimensions Installed as Top VentFraming Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mm Fireplace Dimensions Installed as Rear VentRef. DV4136 Hearth Locating Your FireplaceClearance to Combustibles MantelsGas Inlet and Manifold Pressures Gas Line InstallationFinal Finishing Gas SpecificationsAlternate Switch Location Remote ON/OFF Switch InstallationEB-1 Electrical Box EB-1 receptacle Complete conversion Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Flex Vent Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesTwist Lock Pipes How to Use the Vent GraphRear Wall Vent Application Zero clearance sleeve is only required for combustible walls Rear Wall Vent Installation Twist Lock PipeVertical Sidewall Application Rear Wall Vent Installations Flex Vent Pipe+ B = 17 Max Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeHorizontal length requirement Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationMaximum elbow usage Vertical Through-the-Roof InstallationMin 610 mm Venting Components Operating Instructions Logs ID # Replacement Ceramic Hearth Panels if providedInstallation of Logs Log Identification ChartLeft Log Top Center Log Top Front Log Top Right Log Flame Characteristics Flame & Temperature AdjustmentInspecting the Venting System For Fireplaces Equipped with the SIT 820 Valve Lighting and Operating InstructionsTo Turn Off Gas To Heater Turning Off the Gas to the Appliance Lighting InstructionsValve in the on position For Fireplaces equipped with AF4000 Gas Valve Lighting & Operating InstructionsSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveAF4000 MOD Module End Instructions for RF Comfort Control Valve Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeChange Between F/C Temperature Units Delay Timer ModeAuto Mode Fan Override During Auto ModeAuto Path LED Count Service ActionLocal Path On Path SkyTech Valve Conversions must be completed by qualified personnelFuel Conversion Instructions Burner Orifice ConversionConversion Procedure Installation PrecautionsPilot Orifice Conversion Front Rear Minimum Injector Orifice Size MatrixModel Fuel Type Front Rear Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Logs May Be HOTDescription DVB4136 DVB4136 Description Fuel Conversion Kits Hard Direct Wire Hook Up Optional AccessoriesFK12 Fan Assembly FK24 Fan AssemblyDecorative Bay Windows Remote ControlsInstallation Instructions Ceramic Refractory PanelsInstallation Procedure Battery BackupArch/Square Face Kit Limited Lifetime Warranty Efficiency Ratings