Majestic Appliances DVB4136 Troubleshooting the Gas Control System, SIT Nova 820 Millivolt Valve

Page 33

DVB4136 Direct Vent Gas Fireplace

Troubleshooting the Gas Control System

SIT NOVA 820 Millivolt Valve

NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

WARNING: Before doing any gas control service work, remove glass front.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

 

electrode at pilot.

pilot and push the red button again. If pilot will not

 

 

light - check gap at electrode and pilot-

 

 

should be 1/8” to have a strong spark.

 

B. Defective ignitor

Push Piezo Ignitor Button. Check for spark at

 

(Push button)

electrode and pilot. If no spark to pilot, and elec-

 

 

trode wire is properly connected, replace ignitor.

2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermo-

carefully following

(thermocouple), remote wall

couple/thermopile. Note: this pilot burner

lighting instructions.

switch

assembly utilizes both-a thermocouple and a ther-

 

 

mopile. The thermocouple operates the main valve

 

 

operation (On and Off). Clean and or adjust pilot for

 

 

maximum flame impingement on thermopile and

 

 

thermocouple.

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot;

 

 

milivolt meter should read greater than 10 mV.

 

 

If the reading is okay and the pilot does not stay on,

 

 

replace the gas valve. Note: An interrupter block

 

 

(not supplied) must be used to conduct this test.

3. Pilot burning, no gas to

A. Wall switch or wires

Check wall switch and wires for proper connections

main burner

defective

Jumper wire accross terminals at wall switch, if

 

 

burner comes on, replace defective wall switch. If

 

 

okay, jumper wires across wall switch wires at valve,

 

 

if burner comes on, wires are faulty or connections

 

 

are bad.

 

B. Thermopile may not be

1. Be sure wire connections from thermopile at gas

 

generating sufficient

valve terminals are tight and thermopile is fully

 

millivoltage

inserted into pilot bracket.

 

 

2. One of the wall switch wires may be grounded.

 

 

Remove wall switch wires from valve terminals if

 

 

pilot now stays lit, trace wall switch wiring for

 

 

ground. May be grounded to fireplace or gas

 

 

supply.

 

 

3. Check thermopile with millivolt meter. Take

 

 

reading at thermopile terminals of gas valve.

 

 

Should read 250-300 millivolts (minimum 150)

 

 

while holding valve knob depressed in pilot

 

 

position and wall switch “Off”. Replace faulty

 

 

thermopile if reading is below specified minimum.

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

D. Defective automatic valve

Turn valve knob to “On”, place wall switch to “On”

 

operator.

millivolt meter should read greater than 100 mV. If

 

 

the reading is okay and the burner does not come

 

 

on, replace the gas valve.

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

pilot safety to drop out.

 

 

B. Possible blockage of the

Check the vent terminal for blockage (recycling the

 

vent terminal.

flue gases)

 

 

 

20012322

33

Image 33
Contents Direct Vent Gas Fireplace Table of Contents Please Read the Following Carefully Installation & Operating InstructionsGas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsRef. DVB4136 Fireplace Dimensions Installed as Top VentFireplace Dimensions Installed as Rear Vent Framing Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mmRef. DV4136 Clearance to Combustibles Locating Your FireplaceMantels HearthFinal Finishing Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresRemote ON/OFF Switch Installation Alternate Switch LocationEB-1 Electrical Box EB-1 receptacle Complete conversion Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes Flex Vent PipesHow to Use the Vent Graph Twist Lock PipesRear Wall Vent Application Zero clearance sleeve is only required for combustible walls Rear Wall Vent Installation Twist Lock PipeVertical Sidewall Application Rear Wall Vent Installations Flex Vent Pipe+ B = 17 Max Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeHorizontal length requirement Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationMaximum elbow usage Vertical Through-the-Roof InstallationMin 610 mm Venting Components Operating Instructions Installation of Logs Replacement Ceramic Hearth Panels if providedLog Identification Chart Logs ID #Left Log Top Center Log Top Front Log Top Right Log Flame & Temperature Adjustment Flame CharacteristicsInspecting the Venting System Lighting and Operating Instructions For Fireplaces Equipped with the SIT 820 ValveTo Turn Off Gas To Heater Lighting Instructions Turning Off the Gas to the ApplianceValve in the on position For Fireplaces equipped with AF4000 Gas Valve Lighting & Operating InstructionsSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveAF4000 MOD Module End Transmitter Operation Off Mode Shut Off ProcedureOn Manual Mode Instructions for RF Comfort Control ValveAuto Mode Delay Timer ModeFan Override During Auto Mode Change Between F/C Temperature UnitsAuto Path LED Count Service ActionLocal Path On Path Fuel Conversion Instructions Conversions must be completed by qualified personnelBurner Orifice Conversion SkyTech ValveInstallation Precautions Conversion ProcedurePilot Orifice Conversion Injector Orifice Size Matrix Front Rear MinimumModel Fuel Type Front Rear Cleaning the Standing Pilot Control System MaintenanceLogs May Be HOT Burner and Burner CompartmentDescription DVB4136 DVB4136 Description Fuel Conversion Kits FK12 Fan Assembly Optional AccessoriesFK24 Fan Assembly Hard Direct Wire Hook UpInstallation Instructions Remote ControlsCeramic Refractory Panels Decorative Bay WindowsBattery Backup Installation ProcedureArch/Square Face Kit Limited Lifetime Warranty Efficiency Ratings