Majestic Appliances DVB4136 manual Twist Lock Pipes, How to Use the Vent Graph

Page 15

Twist Lock Pipes

When using twist lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of any telescopic vent section used in the system.

To join twist lock pipes together, simply align the beads of the male end with the grooves of the female end, twisting the pipe until the flange on the female end contacts external flange on the male end. It is recom- mended that you secure the joints with three (3) sheet metal screws, however, this is not mandatory with twist lock pipe. (Fig. 17)

To make it easier to assembly the joints, we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.

Male End

Female End

 

Screw Holes

TWL100

 

 

Fig. 17

Twist-lock pipe joints.

 

How to Use the Vent Graph

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimen- sions fo the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 18), locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fireplace in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 11’ (3.4 m) the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7’ (2.1m), the horizontal run to the face of the outer wall must not exceed 8¹⁄₂’ (2.6 m).

DVB4136 Direct Vent Gas Fireplace

 

 

30

 

 

 

29

 

 

 

28

 

 

 

27

 

to

 

26

 

formdimensionthe floor of the unit

horizontaltheofcenter vent pipe

25

 

11

 

 

 

24

 

 

 

23

 

 

 

22

 

 

 

21

 

 

 

20

 

 

 

19

 

 

 

18

 

 

 

17

 

 

 

16

 

 

 

15

 

 

 

14

 

 

 

13

 

Vertical

the

12

eg: A

8

 

 

 

10

 

 

 

9

 

7

eg: B

6

 

5

 

4

 

3

 

34 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Horizontal dimension from the outside face of the

wall to the center of the fireplace vent flange

Fig. 18 Sidewall venting graph. (Dimensions in feet)

Refer to Page 20 for venting requirements for snor- kels.

Rear Wall Vent Application

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.

Only CFM Corporation venting components are approved to be used in these applications (See ‘Venting Components’ listed for different installation requirements).

The maximum horizontal distance between the rear of the appliance (or end of the transition elbow in a corner application) and the outside face of the rear wall is 20” (508 mm). (Fig. 19, 20)

Only one 45° elbow is allowed in these installations.

Minimum clearances between vent pipe and com- bustible materials are as follows:

Top - 2” (51 mm) Sides - 1” (25 mm)

Bottom - 1” (25 mm)

20012322

15

Image 15
Contents Direct Vent Gas Fireplace Table of Contents Please Read the Following Carefully Installation & Operating InstructionsGas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsRef. DVB4136 Fireplace Dimensions Installed as Top VentFireplace Dimensions Installed as Rear Vent Framing Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mmRef. DV4136 Hearth Locating Your FireplaceClearance to Combustibles MantelsGas Inlet and Manifold Pressures Gas Line InstallationFinal Finishing Gas SpecificationsRemote ON/OFF Switch Installation Alternate Switch LocationEB-1 Electrical Box EB-1 receptacle Complete conversion Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Flex Vent Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesHow to Use the Vent Graph Twist Lock PipesRear Wall Vent Application Zero clearance sleeve is only required for combustible walls Rear Wall Vent Installation Twist Lock PipeVertical Sidewall Application Rear Wall Vent Installations Flex Vent Pipe+ B = 17 Max Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeHorizontal length requirement Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationMaximum elbow usage Vertical Through-the-Roof InstallationMin 610 mm Venting Components Operating Instructions Logs ID # Replacement Ceramic Hearth Panels if providedInstallation of Logs Log Identification ChartLeft Log Top Center Log Top Front Log Top Right Log Flame & Temperature Adjustment Flame CharacteristicsInspecting the Venting System Lighting and Operating Instructions For Fireplaces Equipped with the SIT 820 ValveTo Turn Off Gas To Heater Lighting Instructions Turning Off the Gas to the ApplianceValve in the on position For Fireplaces equipped with AF4000 Gas Valve Lighting & Operating InstructionsSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveAF4000 MOD Module End Instructions for RF Comfort Control Valve Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeChange Between F/C Temperature Units Delay Timer ModeAuto Mode Fan Override During Auto ModeAuto Path LED Count Service ActionLocal Path On Path SkyTech Valve Conversions must be completed by qualified personnelFuel Conversion Instructions Burner Orifice ConversionInstallation Precautions Conversion ProcedurePilot Orifice Conversion Injector Orifice Size Matrix Front Rear MinimumModel Fuel Type Front Rear Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Logs May Be HOTDescription DVB4136 DVB4136 Description Fuel Conversion Kits Hard Direct Wire Hook Up Optional AccessoriesFK12 Fan Assembly FK24 Fan AssemblyDecorative Bay Windows Remote ControlsInstallation Instructions Ceramic Refractory PanelsBattery Backup Installation ProcedureArch/Square Face Kit Limited Lifetime Warranty Efficiency Ratings