Majestic Appliances DVB4136 Locating Your Fireplace, Clearance to Combustibles, Mantels, Hearth

Page 7

Locating Your Fireplace

 

E

A

B

 

Y

 

 

 

 

 

 

C

X

 

 

 

 

D

 

 

 

Y

 

B

 

 

 

 

 

F

 

 

 

 

LU584-1

Fig. 3

Locating gas fireplace.

 

A) Flat on wall

B) Cross corner

C)

**Island

D) *Room divider

E) *Flat on wall corner

F)

Chase installation

Y) 0” minimum (Check minimum if mantel leg is used)

NOTE (Fig. 3):

**Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (X) does not exceed 20’ (6 m). See details in Venting Section.

* When you install your fireplace in(D) Room divider or (E) Flat on wall corner positions (Y), a minimum of 6“ (152 mm) clearance must be maintained from the perpendicular wall and the front of the fireplace.

Clearance to Combustibles

Top of unit to ceiling

36” (914 mm)

Front of unit to combustibles

36” (914 mm)

Appliance

 

Top of standoff

0” (0 mm)

Bottom

0” (0 mm)

Side

0” (0 mm)

Back

0” (0 mm)

Venting

 

Concentric sections of DV Vent

1” (25 mm)

Nonconcentric sections of DV Vent

 

Sides and bottom

1” (25 mm)

Top

2” (51 mm)

Mantels

The height that a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if fitted) and the fireplace.

For the correct mounting height and widths, refer to Figures 4a, 4b and the Mantel Chart below.

The distances and reference points are not affected by the fitting of a bay window front trim kit.

Noncombustible mantels and legs may be installed at any height and width around the appliance. When using paint or lacquer, it must be heat resistant to prevent discoloration.

DVB4136 Direct Vent Gas Fireplace

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

Noncombstible

 

 

 

 

 

 

 

 

 

 

 

 

 

Z

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standoff

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

C

D

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4” (19 mm) Scribe moulding

 

 

 

 

 

 

 

 

 

 

 

for use with CFMCabinets

 

 

 

 

 

 

 

 

 

 

 

Fireplace

 

 

 

 

 

 

 

 

 

 

 

 

Louvre Assembly

 

 

 

 

 

 

 

 

 

 

 

top

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Combustion

 

 

 

 

 

 

 

 

 

 

 

 

Chamber

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom of Door Trim

 

 

 

 

 

CFM146

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Chart

 

 

 

 

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

Mantel from Top

Ref.

or Breast Plate

 

Ref.

 

of Comb. Chamber

 

 

 

 

Depth

 

 

 

 

 

 

V

10”

 

(254 mm)

 

A

 

 

19”

(483 mm)

W

8”

 

(203 mm)

 

B

 

 

17”

(432 mm)

X

6”

 

(152 mm)

 

C

 

 

15”

(381 mm)

Y

4”

 

(101 mm)

 

D

 

 

13”

(330 mm)

Z

2”

 

(51 mm)

 

E

 

 

11”

(279 mm)

Fig. 4a

Combustible mantel minimum installation.

Hearth

A hearth is not mandatory, but is recommended for aesthetic purposes. We recommend a noncombustible hearth which projects out 12” (305 mm) or more from the front of the fireplace.

Cold climate installation recommendation:

When installing this unit against a non-in- sulated exterior wall or chase, it is manda- tory that the outer walls be insulated to conform to applicable insulation codes.

Framing and Finishing

Check fireplace to make sure it is levelled and properly positioned.

To mount the appliance: Choose the location. (Fig. 5)

1.This unit comes with four (4) flanges pre-mounted on both sides of the fireplace to allow two different drywall thicknesses to be used. Flange “A” is for 1/2” drywall while flange “B“ is for 5/8” drywall.

2.Bend the desired flanges out 90° on both sides of the fireplace. Slide the fireplace into the framed opening until the flanges contact the front surfaces of the framing. Level the unit and secure it firmly in place.

20012322

7

Image 7
Contents Direct Vent Gas Fireplace Table of Contents Please Read the Following Carefully Installation & Operating InstructionsGas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsRef. DVB4136 Fireplace Dimensions Installed as Top VentFraming Dimensions Q 40³⁄₈ 1026 mm R 40¹⁄₄ 1022 mm Fireplace Dimensions Installed as Rear VentRef. DV4136 Hearth Locating Your FireplaceClearance to Combustibles MantelsGas Inlet and Manifold Pressures Gas Line InstallationFinal Finishing Gas SpecificationsAlternate Switch Location Remote ON/OFF Switch InstallationEB-1 Electrical Box EB-1 receptacle Complete conversion Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Flex Vent Pipes Canadian InstallationsUSA Installations General Information Assembling Vent PipesTwist Lock Pipes How to Use the Vent GraphRear Wall Vent Application Zero clearance sleeve is only required for combustible walls Rear Wall Vent Installation Twist Lock PipeVertical Sidewall Application Rear Wall Vent Installations Flex Vent Pipe+ B = 17 Max Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeHorizontal length requirement Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationMaximum elbow usage Vertical Through-the-Roof InstallationMin 610 mm Venting Components Operating Instructions Logs ID # Replacement Ceramic Hearth Panels if providedInstallation of Logs Log Identification ChartLeft Log Top Center Log Top Front Log Top Right Log Flame Characteristics Flame & Temperature AdjustmentInspecting the Venting System For Fireplaces Equipped with the SIT 820 Valve Lighting and Operating InstructionsTo Turn Off Gas To Heater Turning Off the Gas to the Appliance Lighting InstructionsValve in the on position For Fireplaces equipped with AF4000 Gas Valve Lighting & Operating InstructionsSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemAF4000 Valve TroubleshootingIgniter operation Troubleshooting AF4000 ValveAF4000 MOD Module End Instructions for RF Comfort Control Valve Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeChange Between F/C Temperature Units Delay Timer ModeAuto Mode Fan Override During Auto ModeAuto Path LED Count Service ActionLocal Path On Path SkyTech Valve Conversions must be completed by qualified personnelFuel Conversion Instructions Burner Orifice ConversionConversion Procedure Installation PrecautionsPilot Orifice Conversion Front Rear Minimum Injector Orifice Size MatrixModel Fuel Type Front Rear Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Logs May Be HOTDescription DVB4136 DVB4136 Description Fuel Conversion Kits Hard Direct Wire Hook Up Optional AccessoriesFK12 Fan Assembly FK24 Fan AssemblyDecorative Bay Windows Remote ControlsInstallation Instructions Ceramic Refractory PanelsInstallation Procedure Battery BackupArch/Square Face Kit Limited Lifetime Warranty Efficiency Ratings