Trane UniTrane Fan-Coil & Force Flo Air Conditioners, UNT-SVX07A-EN Binary Inputs, Binary Outputs

Page 51

sequence of

Operation operation

Sequence of Operation Tracer ZN010 and ZN510

Note: this section applies only to units with a Tracer ZN010 or ZN510 controller.

Power-Up Sequence

When 24 VAC power is initially applied to the Tracer ZN010 or ZN510, the following sequence occurs:

Table O-SO-1. Unit mode as related to water temperature

unit type

EWT sensor required?

coil water temperature

 

 

2-pipe changeover

yes

COOLS if: space temp - EWT

 

5°F

 

 

HEATS if: EWT - space temp

 

5°F

4-pipe changeover

yes

COOLS if: space temp - EWT

5°F

 

 

HEATS if: EWT - space temp

5°F

 

 

 

 

 

2-pipe heating only

no

hot water assumed

 

 

2-pipe cooling only

no

cold water assumed

 

 

4-pipe heat/cool

no

cold water assumed in main coil

 

 

hot water assumed in aux. coil

1.All outputs are controlled off.

2.Tracer ZN010 and ZN510 reads all input values to detemine initial values.

3.The random start time (0-25 seconds) expires.

4.Normal operation begins.

Entering Water Temperature Sampling Function

Both Tracer ZN010 and ZN510 use an entering water temperature sampling function to test for the correct water temperature for the unit operating mode. For all applications not involving changeover, the water temperature does not affect unit operation.

The entering water temperature sam- pling function opens the main hydronic valve, waits no more than three minutes to allow the water temperature to stabilize, then measures the entering water temperature to see if the correct water temperature is available.

The entering water must be five degrees or more above the space temperature to allow hydronic heating and five degrees or more below the space temperature to allow hydronic cooling.

If the correct water temperature is available, the unit begins normal heating or cooling operation. If the measured entering water temperature is too low or high, the controller closes the valve and waits 60 minutes before attempting to sample the entering water. Reference Table O-SO-1.

Binary Inputs

BIP1: Low Temperature Detection Option

The factory hard wires the low temperature detection sensor to binary input #1 (BIP1) on the Tracer ZN010 and ZN510. The sensor defaults normally closed (N.C.), and will trip off the unit on a low temperature diagnostic when detecting low temperature. In addition, the Tracer ZN010 and ZN510 control unit devices as listed below:

fan: off

valves: open

electric heat: off

damper: closed

Note: See the “Diagnostics” section for more information.

BIP2: Condensate Overflow Detection Option

The factory hard wires the condensate overflow sensor to binary input #2 (BIP2) on the Tracer ZN010 and ZN510. The sensor defaults normally closed (N.C.), and will trip off the unit on a condensate overflow diagnostic if condensate reaches the trip point. In addition, the Tracer ZN010 and ZN510 control unit devices as listed below:

fan: off

valves: closed

electric heat: off

BIP3: Occupancy Sensor

Binary input #3 (BIP3) on Tracer ZN010 and ZN510 is available for field- wiring an occupancy sensor, such as a binary switch or a timeclock, to detect occupancy. The sensor can be either normally open or normally closed. Reference Table O-SO-2.

Binary Outputs

Reference Table O-SO-3 for the Tracer ZN010 and ZN510’s six binary outputs.

Table O-SO-3. Binary outputs

binary output

description

pin

BOP1

fan high speed

J1-1

BOP2

fan medium speed

J1-2

BOP3

fan low speed

J1-4

BOP4

main valve

J1-5

BOP5

auxiliary valve/electric heat

J1-6

BOP6

2-position fresh air damper

J1-7

Notes:

1.In a four-pipe application, BOP4 is used for cooling and BOP5 is used for heating.

2.If no valves are ordered with the unit, the factory default for the Tracer ZN010 and ZN510 controller are:

BOP4 configured as normally closed BOP5 configured as normally open

3.If the fresh air damper option is not ordered on the unit, BOP6 will be configured as none.

Table O-SO-2. Occupancy sensor state table

sensor type

sensor position

unit occupancy mode

normally open

open

occupied

normally open

closed

unoccupied

normally closed

open

unoccupied

normally closed

closed

occupied

UNT-SVX07A-EN

51

Image 51
Contents Models FC & FF ZO and later design sequence Installation, Operation, and MaintenanceCommon Hvac Acronyms General informationContents Model Number GeneralModel Number Description GeneralDigit 31 control option Digit 28 auxiliary control valve 0 = noneDigit 29 piping packages 0 = none Digit 30 control type 0 = noneTable I-GI-2. Low vertical fan-coil component data Table I-GI-1. Fan-coil component dataModel M inverted vertical cabinet Available ModelsModel E horizontal recessed Model K low vertical cabinetFactory-Installed Piping Packages Vertical Concealed, Model a DimensionsInstallation Weights Vertical Concealed Unit Dimensions & weights, in-lbsVertical Cabinet, Model B Vertical Cabinet Unit Dimensions, in-lbsHorizontal Concealed, Model C Horizontal Concealed Unit Dimensions, in-lbsHorizontal Cabinet, Model D Horizontal Cabinet Unit Dimensions, in-lbsInstallation Dimensions Weights Horizontal Recessed Unit Dimensions, in-lbsHorizontal Recessed, Model E Vertical Wall Hung Cabinet, Model F Vertical wall hung cabinet unit dimensions & weights, in-lbsVertical Recessed, Model H Vertical Recessed Unit Dimensions, in-lbsVertical Slope Top, Model J Vertical Slope Top Unit Dimensions, in-lbsLow Vertical Concealed, Model K Low Vertical Concealed Unit Dimensions, in-lbsLow Vertical Cabinet, Model L Low Vertical Cabinet Unit Dimensions, in-lbsInverted Vertical Cabinet, Model M Inverted vertical cabinet unit dimensions & weights, in-lbsInverted Vertical Recessed, Model N Inverted vertical recessed unit dimensions & weights, in-lbsFan-Coil Coil Connections Vertical Units Horizontal Units Horizontal Units Inverted Units Force Flo Coil Connections Vertical UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Wall Box DimensionsProjection Panel Projection Panel DimensionsJobsite Storage Pre-installation Installation considerationsInstallation Preparation Receiving and HandlingPre-Installation Checklist Service AccessPiping Considerations Connecting field piping to coilMechanical Duct ConnectionsCondensate Drain Figure I-MR-4. Close-up view of the changeover sensor Venting the Hydronic CoilFigure I-MR-8. Manual circuit setter valve Balancing The Manual Circuit Setter ValveMechanical Steam Piping Code of System Components in Piping DiagramElectrical Unit Wiring DiagramsSupply Power Wiring Wall Mounted Control Interconnection WiringTable I-ER-3. Decimal to fractional HP kW conversion Table I-ER-2. Low vertical free discharge motors, 115 voltTable I-ER-9. Electric heat kW Table I-ER-8. Fan-coil electric heat kWTable I-ER-11. Force Flo single stage, low kW electric heat Table I-ER-10. Force Flo single-stage, max kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installing the Unit InstallationUnit Leveling Figure I-IP-5. Zone sensor only Figure I-IP-3. Zone sensor with on/cancel Comm jackZone Sensor Installation Installing Wall Mounted ControlsWiring Instructions Fan Mode Switch InstallationUnit Leveling Installation ChecklistDevice Addressing Communication WiringRecommended Communication Wiring Practices Pre-startupPre-Startup Checklist Tracer ZN510 & ZN520 Unit Startup Installation startupRelay Board Manual Fan Mode SwitchGeneral Operation information General InformationTracer ZN520 Operation Fan Mode Switch OperationSequence Tracer ZN010 & ZN510 OperationBinary Outputs Binary InputsSupply Fan Operation Fan Mode SwitchAnalog Inputs Zone SensorsTracer ZN520 Sequence of Operation Cooling Operation Heating OperationDischarge Air Tempering Continuous Fan Operation Fan Mode OperationEconomizer Damper Option Fan Start on High SpeedElectric Heat Operation Manual Fresh Air DamperBinary Outputs Table O-SO-12. Binary input configurationsTable O-SO-13. Binary output configuration Data SharingTable O-SO-15. Analog inputs Table O-SO-14. Analog inputsZone Sensor Fan SwitchOn/Cancel Buttons Table O-SO-16. Zone sensor wiring connectionsTable M-D-1. Tracer ZN520 Diagnostics Maintenance diagnosticsCycling the Fan Switch Translating Multiple DiagnosticsResetting Diagnostics Diagnostic ResetTable M-D-3. Fan outputs do not energize Table M-D-4. Valves Stay ClosedTable M-D-5. Valves Stay Open Table M-D-6. Electric Heat Not Operating Table M-D-7. Fresh Air Damper Stays OpenTable M-D-8. Fresh Air Damper Stays Closed Switch SW2 Electric Heat Maintenance troubleshootingTroubleshooting the Relay Board Switch SW1 Controller TypeYellow Comm LED Troubleshooting Tracer ZN010, ZN510 & ZN520Red Service LED Green Status LEDBOP5 BOP6 Table M-T-1. Test sequence for 1-heat/1-cool configurationsMaintenance Maintenance ProceduresMain Drain Pan Coil Maintenance Steam and Hydronic Coil Cleaning ProcedureWinterizing the Coil Replacing the Motor Control Device ReplacementAnnual Maintenance Periodic Maintenance ChecklistsMonthly Checklist Monthly MaintenanceCsti Fan Speed Switch Typical wiringCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN