Trane UNT-SVX07A-EN Digit 28 auxiliary control valve 0 = none, Digit 29 piping packages 0 = none

Page 6

general

Installation information

J= 2-way, modulating, 0.7 Cv (50 psig)*

K= 3-way, modulating, 0.7 Cv (50 psig)* L = 2-way, modulating, 1.1 Cv (60 psig)* M= 3-way, modulating, 1.1 Cv (60 psig)*

N= 2-way, modulating, 2.3 Cv (60 psig)*

P= 3-way, modulating, 2.7 Cv (60 psig)*

Q= 2-way, modulating, 3.3 Cv (60 psig)*

R= 3-way, modulating, 3.8 Cv (60 psig)*

X= field-supplied, NO

Y= field-supplied, NC

Z= field-supplied 3-wire modulating

Digit 28 — auxiliary control valve 0 = none

A= 2-way, 2-position, NO (30 psig)

B= 3-way, 2-position, NC (28 psig)

C= 2-way, 2-position, NC (30 psig)

D= 3-way, 2-position, NC (20 psig)

E= 2-way, 2-position, NO (50 psig)

F= 3-way, 2-position, NO (28 psig)

G= 2-way, 2-position, NC (50 psig)

H= 3-way, 2-position, NC (28 psig)

J= 2-way, modulating, 0.6 Cv (60 psig)

K= 3-way, modulating, 0.6 Cv (60 psig)

L= 2-way, modulating, 1.1 Cv (60 psig) M= 3-way, modulating, 1.1 Cv (60 psig)

N= 2-way, modulating, 2.3 Cv (60 psig)

P= 3-way, modulating, 2.7 Cv (60 psig)

Q= 2-way, modulating, 3.3 Cv (60 psig)

R= 3-way, modulating, 3.8 Cv (60 psig)

X= field-supplied, NO

Y= field-supplied, NC

Z= field-supplied 3-wire modulating

Digit 29 — piping packages 0 = none

A = basic ball valve S & R

B = basic ball valve S/man. crkt set

C = basic ball valve S & R w/auto crkt set D = deluxe ball valve S & R

E = deluxe ball valve S /man. crkt set R

F = deluxe ball valve S & R w/auto crkt set

Digit 30 — control type 0 = none

A = fan speed switch

E = Tracer ZN010

F = Tracer ZN510

G = Tracer ZN520

H = CSTI

Digit 31 — control option

D = unit mtd fan mode, unit voltage, K = wall mtd fan mode

V = unit mtd fan sp w/ setpnt

X = unit mtd fan sp w/ wall mtd setpnt Y = unit mtd fan sp & wall mtd setpnt w/

comm.

Z = unit mtd fan sp, on/cancel, setpnt w/ comm.

1 = wall mtd on/cancel w/ comm.

2 = wall mtd fan speed, setpnt, on/cancel w/ comm.

3 = unit mtd fan speed switch, low voltage 4 = wall mtd digital zone sensor, fan sp w/

setpnt, on/cancel, comm.

5 = wall mtd digital zone sensor, setpnt, on/cancel, comm.

Digit 32 — IAQ options 0 = none

1 = dehumidification

4 = dehumidification w/sensor

Digit 33 — cntrl function #1

0 = w/o exhaust fan/damper or alarm

Digit 34 — cntrl function #2

0 = w/o occupant call or IAQ status

Digit 35 — control function #3 0 = none

1 = occ/unocc control

2 = condensate overflow detection

3 = occ/unocc & condensate overflow

Digit 36 — cntrl function #4 0 = none

1 = smoke input

2 = low temperature detection

3 = smoke input & low limit sensor

Digits 37, 38 — future cntrl functions

Digit 39 — projection panel/falseback

0 = none

A = 5/8”standard vertical recessed panel B = 2” projection panel

C = 2.5” projection panel D = 3” projection panel E = 3.5” projection panel F = 4” projection panel G = 4.5” projection panel H = 5” projection panel J = 5.5”projection panel K = 6” projection panel L = 2”falseback

M = 3” falseback N = 4” falseback P = 5” falseback Q = 6” falseback R = 7” falseback T = 8” falseback

Digit 40 — main autoflow gpm

A = 0.5

G = 3.0

N = 7.0

B = 0.75

H = 3.5

P = 8.0

C = 1.0

J = 4.0

Q = 9.0

D = 1.5

K = 4.5

R = 10.0

E = 2.0

L = 5.0

T = 11.0

F = 2.5

M= 6.0

U = 12.0

Digit 41 — auxiliary autoflow gpm

A = 0.5

F = 2.5

L = 5.0

B = 0.75

G = 3.0

M= 6.0

C = 1.0

H = 3.5

N = 7.0

D = 1.5

J = 4.0

P = 8.0

E = 2.0

K = 4.5

 

Digit 42 — subbase

 

0 = none

 

 

A = 2” subbase

D =5” subbase

B = 3” subbase

E =6” subbase

C = 4” subbase

F =7” subbase

Digit 43 — recessed flange 0 = none

A = recessed flange

Digit 44 — wall boxes 0 = none

A = anodized wall box

6

UNT-SVX07A-EN

Image 6
Contents Installation, Operation, and Maintenance Models FC & FF ZO and later design sequenceGeneral information Common Hvac AcronymsContents General Model NumberGeneral Model Number DescriptionDigit 30 control type 0 = none Digit 28 auxiliary control valve 0 = noneDigit 29 piping packages 0 = none Digit 31 control optionTable I-GI-1. Fan-coil component data Table I-GI-2. Low vertical fan-coil component dataModel K low vertical cabinet Available ModelsModel E horizontal recessed Model M inverted vertical cabinetFactory-Installed Piping Packages Vertical Concealed Unit Dimensions & weights, in-lbs DimensionsInstallation Weights Vertical Concealed, Model aVertical Cabinet Unit Dimensions, in-lbs Vertical Cabinet, Model BHorizontal Concealed Unit Dimensions, in-lbs Horizontal Concealed, Model CHorizontal Cabinet Unit Dimensions, in-lbs Horizontal Cabinet, Model DInstallation Dimensions Weights Horizontal Recessed Unit Dimensions, in-lbsHorizontal Recessed, Model E Vertical wall hung cabinet unit dimensions & weights, in-lbs Vertical Wall Hung Cabinet, Model FVertical Recessed Unit Dimensions, in-lbs Vertical Recessed, Model HVertical Slope Top Unit Dimensions, in-lbs Vertical Slope Top, Model JLow Vertical Concealed Unit Dimensions, in-lbs Low Vertical Concealed, Model KLow Vertical Cabinet Unit Dimensions, in-lbs Low Vertical Cabinet, Model LInverted vertical cabinet unit dimensions & weights, in-lbs Inverted Vertical Cabinet, Model MInverted vertical recessed unit dimensions & weights, in-lbs Inverted Vertical Recessed, Model NFan-Coil Coil Connections Vertical Units Horizontal Units Force Flo Coil Connections Vertical Units Horizontal Units Inverted UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Dimensions Wall BoxProjection Panel Dimensions Projection PanelReceiving and Handling Pre-installation Installation considerationsInstallation Preparation Jobsite StorageService Access Pre-Installation ChecklistDuct Connections Connecting field piping to coilMechanical Piping ConsiderationsCondensate Drain Venting the Hydronic Coil Figure I-MR-4. Close-up view of the changeover sensorBalancing The Manual Circuit Setter Valve Figure I-MR-8. Manual circuit setter valveMechanical Code of System Components in Piping Diagram Steam PipingWall Mounted Control Interconnection Wiring Unit Wiring DiagramsSupply Power Wiring ElectricalTable I-ER-2. Low vertical free discharge motors, 115 volt Table I-ER-3. Decimal to fractional HP kW conversionTable I-ER-8. Fan-coil electric heat kW Table I-ER-9. Electric heat kWTable I-ER-10. Force Flo single-stage, max kW electric heat Table I-ER-11. Force Flo single stage, low kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installation Installing the UnitUnit Leveling Figure I-IP-3. Zone sensor with on/cancel Comm jack Figure I-IP-5. Zone sensor onlyFan Mode Switch Installation Installing Wall Mounted ControlsWiring Instructions Zone Sensor InstallationInstallation Checklist Unit LevelingPre-startup Communication WiringRecommended Communication Wiring Practices Device AddressingPre-Startup Checklist Installation startup Tracer ZN510 & ZN520 Unit StartupGeneral Information Manual Fan Mode SwitchGeneral Operation information Relay BoardTracer ZN010 & ZN510 Operation Fan Mode Switch OperationSequence Tracer ZN520 OperationBinary Inputs Binary OutputsZone Sensors Fan Mode SwitchAnalog Inputs Supply Fan OperationTracer ZN520 Sequence of Operation Cooling Operation Heating OperationDischarge Air Tempering Fan Mode Operation Continuous Fan OperationManual Fresh Air Damper Fan Start on High SpeedElectric Heat Operation Economizer Damper OptionData Sharing Table O-SO-12. Binary input configurationsTable O-SO-13. Binary output configuration Binary OutputsTable O-SO-14. Analog inputs Table O-SO-15. Analog inputsTable O-SO-16. Zone sensor wiring connections Fan SwitchOn/Cancel Buttons Zone SensorMaintenance diagnostics Table M-D-1. Tracer ZN520 DiagnosticsDiagnostic Reset Translating Multiple DiagnosticsResetting Diagnostics Cycling the Fan SwitchTable M-D-3. Fan outputs do not energize Table M-D-4. Valves Stay ClosedTable M-D-5. Valves Stay Open Table M-D-6. Electric Heat Not Operating Table M-D-7. Fresh Air Damper Stays OpenTable M-D-8. Fresh Air Damper Stays Closed Switch SW1 Controller Type Maintenance troubleshootingTroubleshooting the Relay Board Switch SW2 Electric HeatGreen Status LED Troubleshooting Tracer ZN010, ZN510 & ZN520Red Service LED Yellow Comm LEDTable M-T-1. Test sequence for 1-heat/1-cool configurations BOP5 BOP6Maintenance Maintenance ProceduresMain Drain Pan Coil Maintenance Steam and Hydronic Coil Cleaning ProcedureWinterizing the Coil Control Device Replacement Replacing the MotorMonthly Maintenance Periodic Maintenance ChecklistsMonthly Checklist Annual MaintenanceTypical wiring Csti Fan Speed SwitchCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN