Trane UniTrane Fan-Coil & Force Flo Air Conditioners Data Sharing, Binary Outputs, Binary Inputs

Page 57
Note 1

sequence of

Operation operation

Note: If the unit is in the unoccupied mode, the dehumidification routine will not operate.

Data Sharing

Because this controller utilizes LonWorks™ technology, the controller can send or receive data (setpoint, heat/ cool mode, fan request, space temperature, etc.) to and from other controllers on the communication link, with or without the existence of a building automation system. This applies to applications where multiple unit controllers share a single space temperature sensor (for rooms with multiple units but only one zone sensor) for both standalone (with communication wiring between units) and building automation system applications. For this

Note: The generic binary input can be used with a Tracer Summit® building automation system only.

Each binary input default configuration (including normally open/closed) is set at the factory. However, you can configure each of the four binary inputs as normally open or normally closed. The controller will be set properly for each factory- supplied binary input end-device. When no device is connected to the input, configure the controller’s input as not used.

Binary Outputs

Binary outputs are configured to support the following:

Three fan stages (when one or two fan stages are present, medium fan speed can be configured as exhaust fan)

One hydronic cooling stage

One hydronic heating stage (dehumidification requires this to be in the reheat position)

One DX cooling stage

One or two-stage electric heat (dehumidification requires this to be in the reheat position)

Face and bypass damper

Modulating outdoor air damper

One baseboard heat stage

For more information, see Table O-SO-13.

application you will need to use the Rover service tool. For more information on setup, refer to the Trane publication EMTX-IOP-2.

Binary Inputs

The Tracer ZN520 controller has four available binary inputs. See Table O-SO-

12.Normally, these inputs are factory- configured for the following functions:

• Binary input 1: Low temperature detection (freezestat)

• Binary input 2: Condensate overflow

• Binary input 3: Occupancy/ Generic

• Binary input 4: Fan status

Table O-SO-12. Binary input configurations

binary

 

 

controller operation

input

description

configuration

contact closed

contact open

BI 1

low temperature detection Note 1

normally closed

normal

diagnostic Note 5

BI 2

condensate overflow Note 1

normally closed

normal

diagnostic Note 5

BI 3

occupancy

normally open

unoccupied

occupied

BI 3

generic binary input

normally open

normal Note 3

normal Note 3

BI 4

fan status Note 1

normally open

normal

diagnostic Note 4

Note 1 During low temperature, condensate overflow, and fan status diagnostics, the Tracer ZN520 control disables all normal unit operation of the fan, valves, and damper. Note 2The occupancy binary input is for standalone unit controllers as an occupied/unoccupied input. However, when the controller receives a communicated occupied/unoccupied request, the communicated request has priority over the hardwired input. Note 3 The generic binary input does not affect unit operation. A building automation system reads this input as a generic binary input. Note 4 If the fan mode input is in the off position or the controller is in the unoccupied mode with the fan off, the fan status input will be open. A diagnostic will not be generated when the controller commands the fan off. A diagnostic will only be generated if the fan status input does not close after one minute from energizing a fan output or any time the input is open for one minute. The controller waits up to one minute after energizing a fan output to allow the differential pressure to build up across the fan. Note 5 The table below shows the controller’s response to low temperature detection, condensate overflow, and fan status diagnostics.

Table O-SO-13. Binary output configuration

binary output

configuration

J1-1

fan high

J1-2

fan medium

J1-3

fan low

J1-4

(Key)

J1-5

cool valve – open, or 2-position valve Note 1

J1-6

cool valve – close Note 1

J1-9

heat valve – open, or 2 position valve, or 1st electric heat stage Note 1

J1-10

heat valve – close or 2nd Electric heat stage Note 1

J1-11

fresh air damper - open

J1-12

fresh air damper - close

TB4-1

generic / baseboard heat output

TB4-2

24VAC

For Tracer ZN520 units configured and applied as 2-pipe hydronic heat/cool changeover, terminals J1-5 and J1-6 are used to control the primary valve for both heating and cooling. For Tracer ZN520 units configured and applied as 2-pipe hydronic heat/cool changeover with electric heat, terminals J1-5 and J1-6 are used to control the primary valve (for both cooling and heating), and terminals J1-9 and J1-10 are used only for the electric heat stage. For those 2-pipe changeover units, electric heat will not be energized while the hydronic supply is hot (5° or more above the space temperature).

UNT-SVX07A-EN

57

Image 57
Contents Models FC & FF ZO and later design sequence Installation, Operation, and MaintenanceCommon Hvac Acronyms General informationContents Model Number GeneralModel Number Description GeneralDigit 29 piping packages 0 = none Digit 28 auxiliary control valve 0 = noneDigit 30 control type 0 = none Digit 31 control optionTable I-GI-2. Low vertical fan-coil component data Table I-GI-1. Fan-coil component dataModel E horizontal recessed Available ModelsModel K low vertical cabinet Model M inverted vertical cabinetFactory-Installed Piping Packages Installation Weights DimensionsVertical Concealed Unit Dimensions & weights, in-lbs Vertical Concealed, Model aVertical Cabinet, Model B Vertical Cabinet Unit Dimensions, in-lbsHorizontal Concealed, Model C Horizontal Concealed Unit Dimensions, in-lbsHorizontal Cabinet, Model D Horizontal Cabinet Unit Dimensions, in-lbsInstallation Dimensions Weights Horizontal Recessed Unit Dimensions, in-lbsHorizontal Recessed, Model E Vertical Wall Hung Cabinet, Model F Vertical wall hung cabinet unit dimensions & weights, in-lbsVertical Recessed, Model H Vertical Recessed Unit Dimensions, in-lbsVertical Slope Top, Model J Vertical Slope Top Unit Dimensions, in-lbsLow Vertical Concealed, Model K Low Vertical Concealed Unit Dimensions, in-lbsLow Vertical Cabinet, Model L Low Vertical Cabinet Unit Dimensions, in-lbsInverted Vertical Cabinet, Model M Inverted vertical cabinet unit dimensions & weights, in-lbsInverted Vertical Recessed, Model N Inverted vertical recessed unit dimensions & weights, in-lbsFan-Coil Coil Connections Vertical Units Horizontal Units Horizontal Units Inverted Units Force Flo Coil Connections Vertical UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Wall Box DimensionsProjection Panel Projection Panel DimensionsInstallation Preparation Pre-installation Installation considerationsReceiving and Handling Jobsite StoragePre-Installation Checklist Service AccessMechanical Connecting field piping to coilDuct Connections Piping ConsiderationsCondensate Drain Figure I-MR-4. Close-up view of the changeover sensor Venting the Hydronic CoilFigure I-MR-8. Manual circuit setter valve Balancing The Manual Circuit Setter ValveMechanical Steam Piping Code of System Components in Piping DiagramSupply Power Wiring Unit Wiring DiagramsWall Mounted Control Interconnection Wiring ElectricalTable I-ER-3. Decimal to fractional HP kW conversion Table I-ER-2. Low vertical free discharge motors, 115 voltTable I-ER-9. Electric heat kW Table I-ER-8. Fan-coil electric heat kWTable I-ER-11. Force Flo single stage, low kW electric heat Table I-ER-10. Force Flo single-stage, max kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installing the Unit InstallationUnit Leveling Figure I-IP-5. Zone sensor only Figure I-IP-3. Zone sensor with on/cancel Comm jackWiring Instructions Installing Wall Mounted ControlsFan Mode Switch Installation Zone Sensor InstallationUnit Leveling Installation ChecklistRecommended Communication Wiring Practices Communication WiringPre-startup Device AddressingPre-Startup Checklist Tracer ZN510 & ZN520 Unit Startup Installation startupGeneral Operation information Manual Fan Mode SwitchGeneral Information Relay BoardSequence Fan Mode Switch OperationTracer ZN010 & ZN510 Operation Tracer ZN520 OperationBinary Outputs Binary InputsAnalog Inputs Fan Mode SwitchZone Sensors Supply Fan OperationTracer ZN520 Sequence of Operation Cooling Operation Heating OperationDischarge Air Tempering Continuous Fan Operation Fan Mode OperationElectric Heat Operation Fan Start on High SpeedManual Fresh Air Damper Economizer Damper OptionTable O-SO-13. Binary output configuration Table O-SO-12. Binary input configurationsData Sharing Binary OutputsTable O-SO-15. Analog inputs Table O-SO-14. Analog inputsOn/Cancel Buttons Fan SwitchTable O-SO-16. Zone sensor wiring connections Zone SensorTable M-D-1. Tracer ZN520 Diagnostics Maintenance diagnosticsResetting Diagnostics Translating Multiple DiagnosticsDiagnostic Reset Cycling the Fan SwitchTable M-D-3. Fan outputs do not energize Table M-D-4. Valves Stay ClosedTable M-D-5. Valves Stay Open Table M-D-6. Electric Heat Not Operating Table M-D-7. Fresh Air Damper Stays OpenTable M-D-8. Fresh Air Damper Stays Closed Troubleshooting the Relay Board Maintenance troubleshootingSwitch SW1 Controller Type Switch SW2 Electric HeatRed Service LED Troubleshooting Tracer ZN010, ZN510 & ZN520Green Status LED Yellow Comm LEDBOP5 BOP6 Table M-T-1. Test sequence for 1-heat/1-cool configurationsMaintenance Maintenance ProceduresMain Drain Pan Coil Maintenance Steam and Hydronic Coil Cleaning ProcedureWinterizing the Coil Replacing the Motor Control Device ReplacementMonthly Checklist Periodic Maintenance ChecklistsMonthly Maintenance Annual MaintenanceCsti Fan Speed Switch Typical wiringCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN