
mechanical
Installation requirements
Duct Connections
Install all air ducts according to National Fire Protection Association standards for the Installation of Air Conditioning and Ventilating Systems (NFPA 90A and 90B). Install all air ducts according to the National Fire Protection Association standards for the “Installation of Air Conditioning and Ventilation Systems other than Residence Type (NFPA 90A) and Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B).
WARNING Hazardous
Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
The unit’s airflow configuration varies dependent on the model and options ordered. A
Trane recommends using galvanized sheet metal ductwork with
Note: Do not run screws through the removable front panel on concealed units.
Ductwork Recommendations Follow the general recommendations listed below when installing ductwork for the unit.
1.Discharge ductwork should run in a straight line, unchanged in size or direction, for a minimum equivalent distance of three fan diameters from the unit (approximately 20 inches).
2.When making duct turns and transitions avoid sharp turns and use proportional splits, turning vanes, and air scoops when necessary.
3.When possible, construct, and orient supply ductwork turns in the same direction as the fan rotation.
Piping Considerations
Hydronic Coil Piping
Before installing field piping to the coil, consider the following .
•All coil connections are
•The supply and return piping should not interfere with the auxiliary drain pan or condensate line. See “Connecting the Condensate Drain” section for more detailed information.
•The installer must provide adequate piping system filtration and water treatment.
•Exterior condensate may be an issue
Note: When using a field supplied piping package in a
Connecting field piping to coil
1.Remove the auxiliary drain pan, if it is in place, to prevent exposureto dripping solder or excessive temperatures.
2.Slide a
Note: For vertical
3.Solder the joint using bridgit
4.Insulate all piping to coil connections as necessary after connections are complete.
Note: Maintain a minimum distance of one foot between the reduction fitting for the
5.Install the optional auxiliary drain pan, which ships in the accessory packet.
30 |