Trane UNT-SVX07A-EN Mechanical, Duct Connections, Piping Considerations, Hydronic Coil Piping

Page 30

mechanical

Installation requirements

Duct Connections

Install all air ducts according to National Fire Protection Association standards for the Installation of Air Conditioning and Ventilating Systems (NFPA 90A and 90B). Install all air ducts according to the National Fire Protection Association standards for the “Installation of Air Conditioning and Ventilation Systems other than Residence Type (NFPA 90A) and Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B).

WARNING Hazardous

Voltage w/Capacitors! Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

The unit’s airflow configuration varies dependent on the model and options ordered. A one-inch duct collar is provided on units with a ducted return and/or discharge to attach ductwork to the unit.

Trane recommends using galvanized sheet metal ductwork with fan-coil and cabinet heater units. Slide the sheetmetal duct over the duct collar flange of the unit, seal the joint and fasten with sheetmetal screws.

Note: Do not run screws through the removable front panel on concealed units.

Ductwork Recommendations Follow the general recommendations listed below when installing ductwork for the unit.

1.Discharge ductwork should run in a straight line, unchanged in size or direction, for a minimum equivalent distance of three fan diameters from the unit (approximately 20 inches).

2.When making duct turns and transitions avoid sharp turns and use proportional splits, turning vanes, and air scoops when necessary.

3.When possible, construct, and orient supply ductwork turns in the same direction as the fan rotation.

Piping Considerations

Hydronic Coil Piping

Before installing field piping to the coil, consider the following .

All coil connections are 5/8-inch O.D. (or 1/2-inch nominal) female copper connections.

The supply and return piping should not interfere with the auxiliary drain pan or condensate line. See “Connecting the Condensate Drain” section for more detailed information.

The installer must provide adequate piping system filtration and water treatment.

Exterior condensate may be an issue (fan-coils only) if field piping does not have a control valve. Refer to the supply and return header locations in the “Dimensions and Weights” section.

Note: When using a field supplied piping package in a fan-coil unit, allow sufficient room to install the auxiliary drain pan. In addition, piping package must not extend over edges of auxiliary drain pan.

Connecting field piping to coil

1.Remove the auxiliary drain pan, if it is in place, to prevent exposureto dripping solder or excessive temperatures.

2.Slide a 1/2-inch sweat connection coupling (installer provided) onto the coil headers.

Note: For vertical fan-coil units, push the main condensate drain hose and overflow condensate drain hose through the inside of the chassis end panel to prevent them from getting burned when making sweat connections. Be sure to pull the hoses back through and route to the auxiliary drain pan when the end panel has cooled.

3.Solder the joint using bridgit lead-free solder (ASTM B32-89) to provide a watertight connection. Avoid overheating factory soldered joints when soldering field connections to the coil to prevent leakage from occurring.

4.Insulate all piping to coil connections as necessary after connections are complete.

Note: Maintain a minimum distance of one foot between the reduction fitting for the 1/2-inch diameter line and the fan-coil unit piping connections.

5.Install the optional auxiliary drain pan, which ships in the accessory packet.

30

UNT-SVX07A-EN

Image 30
Contents Installation, Operation, and Maintenance Models FC & FF ZO and later design sequenceGeneral information Common Hvac AcronymsContents General Model NumberGeneral Model Number DescriptionDigit 30 control type 0 = none Digit 28 auxiliary control valve 0 = noneDigit 29 piping packages 0 = none Digit 31 control optionTable I-GI-1. Fan-coil component data Table I-GI-2. Low vertical fan-coil component dataModel K low vertical cabinet Available ModelsModel E horizontal recessed Model M inverted vertical cabinetFactory-Installed Piping Packages Vertical Concealed Unit Dimensions & weights, in-lbs DimensionsInstallation Weights Vertical Concealed, Model aVertical Cabinet Unit Dimensions, in-lbs Vertical Cabinet, Model BHorizontal Concealed Unit Dimensions, in-lbs Horizontal Concealed, Model CHorizontal Cabinet Unit Dimensions, in-lbs Horizontal Cabinet, Model DInstallation Dimensions Weights Horizontal Recessed Unit Dimensions, in-lbsHorizontal Recessed, Model E Vertical wall hung cabinet unit dimensions & weights, in-lbs Vertical Wall Hung Cabinet, Model FVertical Recessed Unit Dimensions, in-lbs Vertical Recessed, Model HVertical Slope Top Unit Dimensions, in-lbs Vertical Slope Top, Model JLow Vertical Concealed Unit Dimensions, in-lbs Low Vertical Concealed, Model KLow Vertical Cabinet Unit Dimensions, in-lbs Low Vertical Cabinet, Model LInverted vertical cabinet unit dimensions & weights, in-lbs Inverted Vertical Cabinet, Model MInverted vertical recessed unit dimensions & weights, in-lbs Inverted Vertical Recessed, Model NFan-Coil Coil Connections Vertical Units Horizontal Units Force Flo Coil Connections Vertical Units Horizontal Units Inverted UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Dimensions Wall BoxProjection Panel Dimensions Projection PanelReceiving and Handling Pre-installation Installation considerationsInstallation Preparation Jobsite StorageService Access Pre-Installation ChecklistDuct Connections Connecting field piping to coilMechanical Piping ConsiderationsCondensate Drain Venting the Hydronic Coil Figure I-MR-4. Close-up view of the changeover sensorBalancing The Manual Circuit Setter Valve Figure I-MR-8. Manual circuit setter valveMechanical Code of System Components in Piping Diagram Steam PipingWall Mounted Control Interconnection Wiring Unit Wiring DiagramsSupply Power Wiring ElectricalTable I-ER-2. Low vertical free discharge motors, 115 volt Table I-ER-3. Decimal to fractional HP kW conversionTable I-ER-8. Fan-coil electric heat kW Table I-ER-9. Electric heat kWTable I-ER-10. Force Flo single-stage, max kW electric heat Table I-ER-11. Force Flo single stage, low kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installation Installing the UnitUnit Leveling Figure I-IP-3. Zone sensor with on/cancel Comm jack Figure I-IP-5. Zone sensor onlyFan Mode Switch Installation Installing Wall Mounted ControlsWiring Instructions Zone Sensor InstallationInstallation Checklist Unit LevelingPre-startup Communication WiringRecommended Communication Wiring Practices Device AddressingPre-Startup Checklist Installation startup Tracer ZN510 & ZN520 Unit StartupGeneral Information Manual Fan Mode SwitchGeneral Operation information Relay BoardTracer ZN010 & ZN510 Operation Fan Mode Switch OperationSequence Tracer ZN520 OperationBinary Inputs Binary OutputsZone Sensors Fan Mode SwitchAnalog Inputs Supply Fan OperationTracer ZN520 Sequence of Operation Cooling Operation Heating OperationDischarge Air Tempering Fan Mode Operation Continuous Fan OperationManual Fresh Air Damper Fan Start on High SpeedElectric Heat Operation Economizer Damper OptionData Sharing Table O-SO-12. Binary input configurationsTable O-SO-13. Binary output configuration Binary OutputsTable O-SO-14. Analog inputs Table O-SO-15. Analog inputsTable O-SO-16. Zone sensor wiring connections Fan SwitchOn/Cancel Buttons Zone SensorMaintenance diagnostics Table M-D-1. Tracer ZN520 DiagnosticsDiagnostic Reset Translating Multiple DiagnosticsResetting Diagnostics Cycling the Fan SwitchTable M-D-3. Fan outputs do not energize Table M-D-4. Valves Stay ClosedTable M-D-5. Valves Stay Open Table M-D-6. Electric Heat Not Operating Table M-D-7. Fresh Air Damper Stays OpenTable M-D-8. Fresh Air Damper Stays Closed Switch SW1 Controller Type Maintenance troubleshootingTroubleshooting the Relay Board Switch SW2 Electric HeatGreen Status LED Troubleshooting Tracer ZN010, ZN510 & ZN520Red Service LED Yellow Comm LEDTable M-T-1. Test sequence for 1-heat/1-cool configurations BOP5 BOP6Maintenance Maintenance ProceduresMain Drain Pan Coil Maintenance Steam and Hydronic Coil Cleaning ProcedureWinterizing the Coil Control Device Replacement Replacing the MotorMonthly Maintenance Periodic Maintenance ChecklistsMonthly Checklist Annual MaintenanceTypical wiring Csti Fan Speed SwitchCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN