Trane UNT-SVX07A-EN, UniTrane Fan-Coil & Force Flo Air Conditioners Venting the Hydronic Coil

Page 32

mechanical

Installation requirements

Figure I-MR-3. Attach the changeover sensor to the entering water pipe as shown for changeover to work properly

Figure I-MR-4. Close-up view of the changeover sensor

Figure I-MR-5. Manual coil air vent with set screw

Figure I-MR-6. Manual coil air vent with Shrader fitting

Automatic Electric Heat Lockout Switch Two-pipefan-coil units with auxiliary electric heat have an automatic electric heat lockout switch that disengages the electric heat when hydronic heat enables. If the unit has a factory piping package and electric heat, the factory attaches the switch to the supply water pipe. When the lockout switch detects the supply water temperature above 95°F, it disengages the electric heat. This eliminates electric heat and hydronic heat working simultaneously.

If the fan-coil unit does not have a factory piping package, the switch and coiled lead wires ship inside the piping side end panel. The installer should position the lockout switch on the supply water line of the unit by sliding its spring connector over the pipe. See I-MR-7.

Venting the Hydronic Coil

The hydronic coil contains a vent, either manual or automatic, to release air from the unit. This vent is not sufficient for venting the water piping system in the building.

The coil air vent is on the piping side, above the coil connections on the unit. See Figure I-MR-5 and I-MR-6. Perform the following steps to vent the coil after installing the unit.

1.Pressurize the building piping system with water and vent any trapped air at system vents.

2.For units with manual air vents, back the set screw out to expel air from the unit and then re-tighten the set screw.

The automatic air vent should require no adjustment for the coil to vent. However, if the coil does not vent immediately, unscrew the outer portion of the fitting to expel air from the port.

If debris has become trapped in the vent, completely remove the outer portion of the fitting and clean.

Figure I-MR-7. Electric heat lock out switch installed

External Insulating Requirements Insulate and vapor seal surfaces colder than surrounding air dew-point a to prevent unplanned condensation. Trane recommends field-insulation of the following areas to prevent potential condensate problems:

1.Supply and return water piping connections

2.Condensate drain lines and connections

3.Fresh air intake duct connections

4.Discharge duct connections

5.Wall boxes

32

UNT-SVX07A-EN

Image 32
Contents Installation, Operation, and Maintenance Models FC & FF ZO and later design sequenceGeneral information Common Hvac AcronymsContents General Model NumberGeneral Model Number DescriptionDigit 28 auxiliary control valve 0 = none Digit 29 piping packages 0 = noneDigit 30 control type 0 = none Digit 31 control optionTable I-GI-1. Fan-coil component data Table I-GI-2. Low vertical fan-coil component dataAvailable Models Model E horizontal recessedModel K low vertical cabinet Model M inverted vertical cabinetFactory-Installed Piping Packages Dimensions Installation WeightsVertical Concealed Unit Dimensions & weights, in-lbs Vertical Concealed, Model aVertical Cabinet Unit Dimensions, in-lbs Vertical Cabinet, Model BHorizontal Concealed Unit Dimensions, in-lbs Horizontal Concealed, Model CHorizontal Cabinet Unit Dimensions, in-lbs Horizontal Cabinet, Model DHorizontal Recessed, Model E Installation Dimensions WeightsHorizontal Recessed Unit Dimensions, in-lbs Vertical wall hung cabinet unit dimensions & weights, in-lbs Vertical Wall Hung Cabinet, Model FVertical Recessed Unit Dimensions, in-lbs Vertical Recessed, Model HVertical Slope Top Unit Dimensions, in-lbs Vertical Slope Top, Model JLow Vertical Concealed Unit Dimensions, in-lbs Low Vertical Concealed, Model KLow Vertical Cabinet Unit Dimensions, in-lbs Low Vertical Cabinet, Model LInverted vertical cabinet unit dimensions & weights, in-lbs Inverted Vertical Cabinet, Model MInverted vertical recessed unit dimensions & weights, in-lbs Inverted Vertical Recessed, Model NFan-Coil Coil Connections Vertical Units Horizontal Units Force Flo Coil Connections Vertical Units Horizontal Units Inverted UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Dimensions Wall BoxProjection Panel Dimensions Projection PanelPre-installation Installation considerations Installation PreparationReceiving and Handling Jobsite StorageService Access Pre-Installation ChecklistConnecting field piping to coil MechanicalDuct Connections Piping ConsiderationsCondensate Drain Venting the Hydronic Coil Figure I-MR-4. Close-up view of the changeover sensorBalancing The Manual Circuit Setter Valve Figure I-MR-8. Manual circuit setter valveMechanical Code of System Components in Piping Diagram Steam PipingUnit Wiring Diagrams Supply Power WiringWall Mounted Control Interconnection Wiring ElectricalTable I-ER-2. Low vertical free discharge motors, 115 volt Table I-ER-3. Decimal to fractional HP kW conversionTable I-ER-8. Fan-coil electric heat kW Table I-ER-9. Electric heat kWTable I-ER-10. Force Flo single-stage, max kW electric heat Table I-ER-11. Force Flo single stage, low kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installation Installing the UnitUnit Leveling Figure I-IP-3. Zone sensor with on/cancel Comm jack Figure I-IP-5. Zone sensor onlyInstalling Wall Mounted Controls Wiring InstructionsFan Mode Switch Installation Zone Sensor InstallationInstallation Checklist Unit LevelingCommunication Wiring Recommended Communication Wiring PracticesPre-startup Device AddressingPre-Startup Checklist Installation startup Tracer ZN510 & ZN520 Unit StartupManual Fan Mode Switch General Operation informationGeneral Information Relay BoardFan Mode Switch Operation SequenceTracer ZN010 & ZN510 Operation Tracer ZN520 OperationBinary Inputs Binary OutputsFan Mode Switch Analog InputsZone Sensors Supply Fan OperationTracer ZN520 Sequence of Operation Discharge Air Tempering Cooling OperationHeating Operation Fan Mode Operation Continuous Fan OperationFan Start on High Speed Electric Heat OperationManual Fresh Air Damper Economizer Damper OptionTable O-SO-12. Binary input configurations Table O-SO-13. Binary output configurationData Sharing Binary OutputsTable O-SO-14. Analog inputs Table O-SO-15. Analog inputsFan Switch On/Cancel ButtonsTable O-SO-16. Zone sensor wiring connections Zone SensorMaintenance diagnostics Table M-D-1. Tracer ZN520 DiagnosticsTranslating Multiple Diagnostics Resetting DiagnosticsDiagnostic Reset Cycling the Fan SwitchTable M-D-5. Valves Stay Open Table M-D-3. Fan outputs do not energizeTable M-D-4. Valves Stay Closed Table M-D-8. Fresh Air Damper Stays Closed Table M-D-6. Electric Heat Not OperatingTable M-D-7. Fresh Air Damper Stays Open Maintenance troubleshooting Troubleshooting the Relay BoardSwitch SW1 Controller Type Switch SW2 Electric HeatTroubleshooting Tracer ZN010, ZN510 & ZN520 Red Service LEDGreen Status LED Yellow Comm LEDTable M-T-1. Test sequence for 1-heat/1-cool configurations BOP5 BOP6Main Drain Pan MaintenanceMaintenance Procedures Winterizing the Coil Coil MaintenanceSteam and Hydronic Coil Cleaning Procedure Control Device Replacement Replacing the MotorPeriodic Maintenance Checklists Monthly ChecklistMonthly Maintenance Annual MaintenanceTypical wiring Csti Fan Speed SwitchCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN