Trane UniTrane Fan-Coil & Force Flo Air Conditioners Table M-D-6. Electric Heat Not Operating

Page 63

Maintenance diagnostics

Table M-D-6. Electric Heat Not Operating

Probable Cause

Explanation

Normal operation

The controller cycles electric heat on and off to meet the unit capacity requirements.

Requested mode: off

It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the controller,

 

the units shuts off the electric heat.

Communicated disable

Numerous communicated requests may disable electric heat, including an auxiliary heat enable input and the heat/cool mode input.

 

Depending on the state of the communicated request, the unit may disable electric heat.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and associated output

 

wiring. However, based on the current step in the test sequence, the electric heat may not be on. Refer to the “Manual Output Test”

 

section.

Diagnostic present

A specific list of diagnostics affects electric heat operation. For more information, see the “Diagnostics” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does

 

not match the actual end device, the electric heat may not work properly.

No power to the controller

If the controller does not have power, electric heat does not operate. For the controller to operate normally, a

 

24VAC input voltage must be applied. Whenthe green LED is off continuously, the controller does not have sufficient power or has

 

failed.

Unit Wiring

The wiring between the controller outputs and the electric heat contacts must be present and correct for normal electric heat

 

operation. Refer to the typicalunit wiring diagrams in the Appendix of this manual.

Table M-D-7. Fresh Air Damper Stays Open

Probable Cause

Explanation

Normal operation

The controller opens and closes the fresh air damper based on the controller’s occupancy mode and fan status. Normally, the

 

fresh air damper is open during moccupied mode when the fan is running and closed during unoccupied mode.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and associated output

 

wiring. However, based on thecurrent step in the test sequence, the fresh air damper may not be open. Refer to

 

the “Manual Output Test” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit

 

configuration does not match the actualend device, the damper may not work correctly.

Unit wiring

The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer

 

to the typical unit wiringdiagrams in the Appendix of this manual.

Table M-D-8. Fresh Air Damper Stays Closed

Probable Cause

Explanation

Normal operation

The controller opens and closes the fresh air damper based on the controller’s occupancy mode and fan status. Normally, the

 

fresh air damper is open during moccupied mode when the fan is running and closed during unoccupied mode.

Warmup and cooldown

The controller includes both a warmup and cooldown sequence to keep the fresh air damper closed during the transition from

 

unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible.

Requested mode: off

It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the

 

controller, the unit closes the fresh air damper.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and associated output

 

wiring. However, based on thecurrent step in the test sequence, the fresh air damper may not be open. Refer to

 

the “Manual Output Test” section.

Diagnostic present

A specific list of diagnostics effects fresh air damper operation. For more information, see the “Diagnostics” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit

 

configuration does not match the actualend device, the damper may not work correctly.

No power to the controller

If the controller does not have power, the fresh air damper does not operate. For the controller to operate normally, a

 

24 VAC input voltage must be applied.When the green LED is off continuously, the controller does not have sufficient power or has

 

failed.

Unit wiring

The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer

 

to the typical unit wiringdiagrams in the Appendix of this manual.

UNT-SVX07A-EN

63

Image 63
Contents Models FC & FF ZO and later design sequence Installation, Operation, and MaintenanceCommon Hvac Acronyms General informationContents Model Number GeneralModel Number Description GeneralDigit 31 control option Digit 28 auxiliary control valve 0 = noneDigit 29 piping packages 0 = none Digit 30 control type 0 = noneTable I-GI-2. Low vertical fan-coil component data Table I-GI-1. Fan-coil component dataModel M inverted vertical cabinet Available ModelsModel E horizontal recessed Model K low vertical cabinetFactory-Installed Piping Packages Vertical Concealed, Model a DimensionsInstallation Weights Vertical Concealed Unit Dimensions & weights, in-lbsVertical Cabinet, Model B Vertical Cabinet Unit Dimensions, in-lbsHorizontal Concealed, Model C Horizontal Concealed Unit Dimensions, in-lbsHorizontal Cabinet, Model D Horizontal Cabinet Unit Dimensions, in-lbsInstallation Dimensions Weights Horizontal Recessed Unit Dimensions, in-lbsHorizontal Recessed, Model E Vertical Wall Hung Cabinet, Model F Vertical wall hung cabinet unit dimensions & weights, in-lbsVertical Recessed, Model H Vertical Recessed Unit Dimensions, in-lbsVertical Slope Top, Model J Vertical Slope Top Unit Dimensions, in-lbsLow Vertical Concealed, Model K Low Vertical Concealed Unit Dimensions, in-lbsLow Vertical Cabinet, Model L Low Vertical Cabinet Unit Dimensions, in-lbsInverted Vertical Cabinet, Model M Inverted vertical cabinet unit dimensions & weights, in-lbsInverted Vertical Recessed, Model N Inverted vertical recessed unit dimensions & weights, in-lbsFan-Coil Coil Connections Vertical Units Horizontal Units Horizontal Units Inverted Units Force Flo Coil Connections Vertical UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Wall Box DimensionsProjection Panel Projection Panel DimensionsJobsite Storage Pre-installation Installation considerationsInstallation Preparation Receiving and HandlingPre-Installation Checklist Service AccessPiping Considerations Connecting field piping to coilMechanical Duct ConnectionsCondensate Drain Figure I-MR-4. Close-up view of the changeover sensor Venting the Hydronic CoilFigure I-MR-8. Manual circuit setter valve Balancing The Manual Circuit Setter ValveMechanical Steam Piping Code of System Components in Piping DiagramElectrical Unit Wiring DiagramsSupply Power Wiring Wall Mounted Control Interconnection WiringTable I-ER-3. Decimal to fractional HP kW conversion Table I-ER-2. Low vertical free discharge motors, 115 voltTable I-ER-9. Electric heat kW Table I-ER-8. Fan-coil electric heat kWTable I-ER-11. Force Flo single stage, low kW electric heat Table I-ER-10. Force Flo single-stage, max kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installing the Unit InstallationUnit Leveling Figure I-IP-5. Zone sensor only Figure I-IP-3. Zone sensor with on/cancel Comm jackZone Sensor Installation Installing Wall Mounted ControlsWiring Instructions Fan Mode Switch InstallationUnit Leveling Installation ChecklistDevice Addressing Communication WiringRecommended Communication Wiring Practices Pre-startupPre-Startup Checklist Tracer ZN510 & ZN520 Unit Startup Installation startupRelay Board Manual Fan Mode SwitchGeneral Operation information General InformationTracer ZN520 Operation Fan Mode Switch OperationSequence Tracer ZN010 & ZN510 OperationBinary Outputs Binary InputsSupply Fan Operation Fan Mode SwitchAnalog Inputs Zone SensorsTracer ZN520 Sequence of Operation Cooling Operation Heating OperationDischarge Air Tempering Continuous Fan Operation Fan Mode OperationEconomizer Damper Option Fan Start on High SpeedElectric Heat Operation Manual Fresh Air DamperBinary Outputs Table O-SO-12. Binary input configurationsTable O-SO-13. Binary output configuration Data SharingTable O-SO-15. Analog inputs Table O-SO-14. Analog inputsZone Sensor Fan SwitchOn/Cancel Buttons Table O-SO-16. Zone sensor wiring connectionsTable M-D-1. Tracer ZN520 Diagnostics Maintenance diagnosticsCycling the Fan Switch Translating Multiple DiagnosticsResetting Diagnostics Diagnostic ResetTable M-D-3. Fan outputs do not energize Table M-D-4. Valves Stay ClosedTable M-D-5. Valves Stay Open Table M-D-6. Electric Heat Not Operating Table M-D-7. Fresh Air Damper Stays OpenTable M-D-8. Fresh Air Damper Stays Closed Switch SW2 Electric Heat Maintenance troubleshootingTroubleshooting the Relay Board Switch SW1 Controller TypeYellow Comm LED Troubleshooting Tracer ZN010, ZN510 & ZN520Red Service LED Green Status LEDBOP5 BOP6 Table M-T-1. Test sequence for 1-heat/1-cool configurationsMaintenance Maintenance ProceduresMain Drain Pan Coil Maintenance Steam and Hydronic Coil Cleaning ProcedureWinterizing the Coil Replacing the Motor Control Device ReplacementAnnual Maintenance Periodic Maintenance ChecklistsMonthly Checklist Monthly MaintenanceCsti Fan Speed Switch Typical wiringCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN