Trane UNT-SVX07A-EN manual Analog Inputs, Zone Sensors, Fan Mode Switch, Supply Fan Operation

Page 52

sequence of

Operation operation

Analog Inputs

Both Tracer ZN010 and ZN510 accept a maximum of five analog inputs. Reference Table O-SO-4.

Zone Sensors

The zone sensors available with the Tracer ZN010 and ZN510 provide up to three different inputs

1.Space temperature measurement (10KΩ thermistor)

2.Local setpoint

3.Fan mode switch

Wall mounted zone sensors include a thermistor as a component of the internal printed circuit board. Unit mounted zone sensors use a sensor placed in the unit’s return air stream.

Each zone sensor is equipped with a thumbwheel for setpoint adjustment.

Fan Mode Switch

The zone sensor may be equipped with a fan mode switch. The fan mode switch offers selections of off, low, medium, high, or auto.

Supply Fan Operation

Reference Table O-SO-5 for fan mode operation. Reference Table O-SO-5 for fan mode operation. Tracer ZN010 and ZN510 will operate in either continuous fan or fan cycling mode. The fan cycles when the fan mode switch is placed in auto. The fan runs continuous when placed in the high, medium, or low position. Use Rover, Trane’s installation and service tool, to change auto defaults.

Table O-SO-4. Analog inputs

analog input

description

application

zone

space temperature

space temperature detection

set

local setpoint

thumbwheel setpoint

fan

fan mode input

zone sensor fan switch

analog input 1 (AI1)

entering water temperature

entering water temperature detection

analog input 2 (AI2)

discharge air temperature

discharge air temperature detection

Notes:

1.The zone sensor, entering water temperature sensor, and the discharge air temperature sensor are 10KΩ thermistors. Figure 26 provides the resistance-temperature curve for these thermistors.

2.Zone sensor:

Wall mounted sensors include a thermistor soldered to the sensor’s circuit board Unit mounted sensors include a return air sensor in the unit’s return air stream.

3.Changeover units include an entering water temperature sensor.

Table O-SO-5. Fan mode operation

heating mode

 

cooling mode

 

 

 

fan mode

occupied

unoccupied

occupied

unoccupied

 

off

off

off

off

off

 

low

low

off/high (3)

low

off/high (3)

 

medium

medium

off/high (3)

medium

off/high (3)

 

high

high

off/high (3)

high

off/high (3)

 

auto

 

 

 

 

 

continuous

heat default

off/high (3)

cool default

off/high (3)

 

cycling off/heat default

off/high (3)

off/cool default

off/high (3)

 

Notes:

1.During the transition from off to any fan speed but high, Tracer ZN010 and ZN510 automatically starts the fan on high speed and runs for three seconds before transitioning to the selected speed (if it is other than high). This provides enough torque to start all fan motors from the off position.

2.When the heating output is controlled off, Tracer ZN010 and ZN510 automatically controls the fan on for an additional 30 seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.

3.Whenever two states are listed for the fan:

The first state (off) applies when there is not a call for heating or cooling. The second state (varies) applies when there is a call for heating or cooling.

The heat default is factory configured for low fan speed, and the cool default is medium.

Table O-SO-6. Valid operating range and factory default setpoints

setpoint/parameter

default setting

valid operating range

unoccupied cooling setpoint

85° F

40 to 115° F

occupied cooling setpoint

74° F

40 to 115° F

occupied heating setpoint

71° F

40 to 115° F

unoccupied heating setpoint

60° F

40 to 115° F

cooling setpoint high limit

110° F

40 to 115° F

cooling setpoint low limit

40° F

40 to 115° F

heating setpoint high limit

105° F

40 to 115° F

heating setpoint low limit

40° F

40 to 115° F

power-up control wait

0 sec

0 to 240 sec

52

UNT-SVX07A-EN

Image 52
Contents Installation, Operation, and Maintenance Models FC & FF ZO and later design sequenceGeneral information Common Hvac AcronymsContents General Model NumberGeneral Model Number DescriptionDigit 28 auxiliary control valve 0 = none Digit 29 piping packages 0 = noneDigit 30 control type 0 = none Digit 31 control optionTable I-GI-1. Fan-coil component data Table I-GI-2. Low vertical fan-coil component dataAvailable Models Model E horizontal recessedModel K low vertical cabinet Model M inverted vertical cabinetFactory-Installed Piping Packages Dimensions Installation WeightsVertical Concealed Unit Dimensions & weights, in-lbs Vertical Concealed, Model aVertical Cabinet Unit Dimensions, in-lbs Vertical Cabinet, Model BHorizontal Concealed Unit Dimensions, in-lbs Horizontal Concealed, Model CHorizontal Cabinet Unit Dimensions, in-lbs Horizontal Cabinet, Model DHorizontal Recessed Unit Dimensions, in-lbs Installation Dimensions WeightsHorizontal Recessed, Model E Vertical wall hung cabinet unit dimensions & weights, in-lbs Vertical Wall Hung Cabinet, Model FVertical Recessed Unit Dimensions, in-lbs Vertical Recessed, Model HVertical Slope Top Unit Dimensions, in-lbs Vertical Slope Top, Model JLow Vertical Concealed Unit Dimensions, in-lbs Low Vertical Concealed, Model KLow Vertical Cabinet Unit Dimensions, in-lbs Low Vertical Cabinet, Model LInverted vertical cabinet unit dimensions & weights, in-lbs Inverted Vertical Cabinet, Model MInverted vertical recessed unit dimensions & weights, in-lbs Inverted Vertical Recessed, Model NFan-Coil Coil Connections Vertical Units Horizontal Units Force Flo Coil Connections Vertical Units Horizontal Units Inverted UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Dimensions Wall BoxProjection Panel Dimensions Projection PanelPre-installation Installation considerations Installation PreparationReceiving and Handling Jobsite StorageService Access Pre-Installation ChecklistConnecting field piping to coil MechanicalDuct Connections Piping ConsiderationsCondensate Drain Venting the Hydronic Coil Figure I-MR-4. Close-up view of the changeover sensorBalancing The Manual Circuit Setter Valve Figure I-MR-8. Manual circuit setter valveMechanical Code of System Components in Piping Diagram Steam PipingUnit Wiring Diagrams Supply Power WiringWall Mounted Control Interconnection Wiring ElectricalTable I-ER-2. Low vertical free discharge motors, 115 volt Table I-ER-3. Decimal to fractional HP kW conversionTable I-ER-8. Fan-coil electric heat kW Table I-ER-9. Electric heat kWTable I-ER-10. Force Flo single-stage, max kW electric heat Table I-ER-11. Force Flo single stage, low kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installation Installing the UnitUnit Leveling Figure I-IP-3. Zone sensor with on/cancel Comm jack Figure I-IP-5. Zone sensor onlyInstalling Wall Mounted Controls Wiring InstructionsFan Mode Switch Installation Zone Sensor InstallationInstallation Checklist Unit LevelingCommunication Wiring Recommended Communication Wiring PracticesPre-startup Device AddressingPre-Startup Checklist Installation startup Tracer ZN510 & ZN520 Unit StartupManual Fan Mode Switch General Operation informationGeneral Information Relay BoardFan Mode Switch Operation SequenceTracer ZN010 & ZN510 Operation Tracer ZN520 OperationBinary Inputs Binary OutputsFan Mode Switch Analog InputsZone Sensors Supply Fan OperationTracer ZN520 Sequence of Operation Heating Operation Cooling OperationDischarge Air Tempering Fan Mode Operation Continuous Fan OperationFan Start on High Speed Electric Heat OperationManual Fresh Air Damper Economizer Damper OptionTable O-SO-12. Binary input configurations Table O-SO-13. Binary output configurationData Sharing Binary OutputsTable O-SO-14. Analog inputs Table O-SO-15. Analog inputsFan Switch On/Cancel ButtonsTable O-SO-16. Zone sensor wiring connections Zone SensorMaintenance diagnostics Table M-D-1. Tracer ZN520 DiagnosticsTranslating Multiple Diagnostics Resetting DiagnosticsDiagnostic Reset Cycling the Fan SwitchTable M-D-4. Valves Stay Closed Table M-D-3. Fan outputs do not energizeTable M-D-5. Valves Stay Open Table M-D-7. Fresh Air Damper Stays Open Table M-D-6. Electric Heat Not OperatingTable M-D-8. Fresh Air Damper Stays Closed Maintenance troubleshooting Troubleshooting the Relay BoardSwitch SW1 Controller Type Switch SW2 Electric HeatTroubleshooting Tracer ZN010, ZN510 & ZN520 Red Service LEDGreen Status LED Yellow Comm LEDTable M-T-1. Test sequence for 1-heat/1-cool configurations BOP5 BOP6Maintenance Procedures MaintenanceMain Drain Pan Steam and Hydronic Coil Cleaning Procedure Coil MaintenanceWinterizing the Coil Control Device Replacement Replacing the MotorPeriodic Maintenance Checklists Monthly ChecklistMonthly Maintenance Annual MaintenanceTypical wiring Csti Fan Speed SwitchCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN