Trane UNT-SVX07A-EN Table M-D-3. Fan outputs do not energize, Table M-D-4. Valves Stay Closed

Page 62

Maintenance diagnostics

Table M-D-3. Fan outputs do not energize

Probable Cause

Explanation

 

Random start

After power-up, the controller always observes a random start that varies observedbetween 0 and 25 seconds. The controller

 

remains off until the random start time expires.

 

Power-up control wait

When power-up control wait is enabled (non-zero time), the controller remains off until one of two conditions occurs:

 

1. The controller exits power-up control wait once it receives communicated information.

 

 

2. The controller exits power-up control wait once the power-up control wait time expires.

 

Cycling fan operation

When the fan mode switch is in the auto postion, the unit fan cycles off when there is no call for heating or cooling. The heating/

 

cooling sources cycle on oroff periodically with the unit fan to match the capacity according to pulse-width-modulation (PWM) logic.

Unoccupied operation

The fan cycles with capacity when the unit is in unoccupied mode. This occurs even if the unit is in continuous fan operation. While

 

unoccupied, the fan cycleson or off with heating/cooling to provide varying amounts of heating or cooling to the space. to match the

 

capacity according to pulse-width-modulation (PWM) logic.

 

Fan mode off

When using the local fan mode switch to determine the fan operation, the off position controls the unit fan to off.

Requested mode: off

It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When “off” is communicated to the

 

controller, the unitcontrols the fan to off. The unit is not capable of heating or cooling when the controller is in this mode.

Diagnostic present

A specific list of diagnostics effects fan operation. For more information, see the “Diagnostics” section.

No power to the

If the controller does not have power, the unit fan will not operate. For the controller

controller to operate

controller

normally, it must have an input voltage of 24 VAC. Whenthe green LED is off continuously, the controller does not have sufficient

 

power or the controller has failed.

 

Manual output test

The controller includes a manual output test sequence to verify binary output operation and the associated wiring. However, based

 

on the current step in the test sequence, the unit fan may not be powered on. Refer to the “Manual Output Test” section.

Unit wiring

The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan operation.

 

Refer to the typical unit wiringdiagrams in the Appendix of this manual.

 

Table M-D-4. Valves Stay Closed

Probable Cause

Explanation

Normal operation

The controller opens and closes the valves to meet the unit capacity requirements.

Requested mode: off

It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When off is communicated to the

 

controller, the unitcontrols the fan to off. The unit is not capable of heating or cooling when the controller is in this mode.

Valve override

The controller can communicate a valve override request. This request effects the valve operation.

Manual output test

The controller includes a manual output test sequence to verify analog and binary output operation and the associated wiring.

 

However, based on thecurrent step in the test sequence, the valves may not be open. Refer to the “Manual Output Test” section.

Diagnostic present

A specific list of diagnostics affects valve operation. For more information, see the “Diagnostics” section.

Sampling logic

The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe changeover. It

 

determines whenthe entering water temperature is either too cool or too hot for the desired heating or cooling mode. Refer to the

 

“Entering Water section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit configuration

 

does not match the actualend device, the valves may not work correctly.

No power to the

If the controller does not have power, the valves do not operate. For the controller controller to operate normally,

 

it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have sufficient power,or the

 

controller has failed.

Unit wiring

The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation. Refer to the

 

typical unit wiring diagrams in the Appendix of this manual.

Table M-D-5. Valves Stay Open

Probable Cause

Explanation

Normal operation

The controller opens and closes the valves to meet the unit capacity requirements.

Valve override

The controller can communicate a valve override request to affect the valve operation.

Manual output test

The controller includes a manual output test sequence that verifies analog and binary output operation and the associated wiring.

 

However, based on thecurrent step in the test sequence, the valves may be open. Refer to the “Manual Output Test” section.

Diagnostic present

A specific list of diagnostics affects valve operation. For more information, see the “Diagnostics” section.

Sampling logic

The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe

 

changeover to determine if the entering water temperature is correct for the unit operating mode. Refer to the “Entering Water

 

Temperature Sampling” section.

Unit configuration

The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does

 

not match the actual end device, the valves may not work correctly.

Unit wiring

The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation. Refer to the

 

typical unit wiring diagrams inthe Appendix of this manual.

62

UNT-SVX07A-EN

Image 62
Contents Installation, Operation, and Maintenance Models FC & FF ZO and later design sequenceGeneral information Common Hvac AcronymsContents General Model NumberGeneral Model Number DescriptionDigit 30 control type 0 = none Digit 28 auxiliary control valve 0 = noneDigit 29 piping packages 0 = none Digit 31 control optionTable I-GI-1. Fan-coil component data Table I-GI-2. Low vertical fan-coil component dataModel K low vertical cabinet Available ModelsModel E horizontal recessed Model M inverted vertical cabinetFactory-Installed Piping Packages Vertical Concealed Unit Dimensions & weights, in-lbs DimensionsInstallation Weights Vertical Concealed, Model aVertical Cabinet Unit Dimensions, in-lbs Vertical Cabinet, Model BHorizontal Concealed Unit Dimensions, in-lbs Horizontal Concealed, Model CHorizontal Cabinet Unit Dimensions, in-lbs Horizontal Cabinet, Model DHorizontal Recessed, Model E Installation Dimensions WeightsHorizontal Recessed Unit Dimensions, in-lbs Vertical wall hung cabinet unit dimensions & weights, in-lbs Vertical Wall Hung Cabinet, Model FVertical Recessed Unit Dimensions, in-lbs Vertical Recessed, Model HVertical Slope Top Unit Dimensions, in-lbs Vertical Slope Top, Model JLow Vertical Concealed Unit Dimensions, in-lbs Low Vertical Concealed, Model KLow Vertical Cabinet Unit Dimensions, in-lbs Low Vertical Cabinet, Model LInverted vertical cabinet unit dimensions & weights, in-lbs Inverted Vertical Cabinet, Model MInverted vertical recessed unit dimensions & weights, in-lbs Inverted Vertical Recessed, Model NFan-Coil Coil Connections Vertical Units Horizontal Units Force Flo Coil Connections Vertical Units Horizontal Units Inverted UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Dimensions Wall BoxProjection Panel Dimensions Projection PanelReceiving and Handling Pre-installation Installation considerationsInstallation Preparation Jobsite StorageService Access Pre-Installation ChecklistDuct Connections Connecting field piping to coilMechanical Piping ConsiderationsCondensate Drain Venting the Hydronic Coil Figure I-MR-4. Close-up view of the changeover sensorBalancing The Manual Circuit Setter Valve Figure I-MR-8. Manual circuit setter valveMechanical Code of System Components in Piping Diagram Steam PipingWall Mounted Control Interconnection Wiring Unit Wiring DiagramsSupply Power Wiring ElectricalTable I-ER-2. Low vertical free discharge motors, 115 volt Table I-ER-3. Decimal to fractional HP kW conversionTable I-ER-8. Fan-coil electric heat kW Table I-ER-9. Electric heat kWTable I-ER-10. Force Flo single-stage, max kW electric heat Table I-ER-11. Force Flo single stage, low kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installation Installing the UnitUnit Leveling Figure I-IP-3. Zone sensor with on/cancel Comm jack Figure I-IP-5. Zone sensor onlyFan Mode Switch Installation Installing Wall Mounted ControlsWiring Instructions Zone Sensor InstallationInstallation Checklist Unit LevelingPre-startup Communication WiringRecommended Communication Wiring Practices Device AddressingPre-Startup Checklist Installation startup Tracer ZN510 & ZN520 Unit StartupGeneral Information Manual Fan Mode SwitchGeneral Operation information Relay BoardTracer ZN010 & ZN510 Operation Fan Mode Switch OperationSequence Tracer ZN520 OperationBinary Inputs Binary OutputsZone Sensors Fan Mode SwitchAnalog Inputs Supply Fan OperationTracer ZN520 Sequence of Operation Discharge Air Tempering Cooling OperationHeating Operation Fan Mode Operation Continuous Fan OperationManual Fresh Air Damper Fan Start on High SpeedElectric Heat Operation Economizer Damper OptionData Sharing Table O-SO-12. Binary input configurationsTable O-SO-13. Binary output configuration Binary OutputsTable O-SO-14. Analog inputs Table O-SO-15. Analog inputsTable O-SO-16. Zone sensor wiring connections Fan SwitchOn/Cancel Buttons Zone SensorMaintenance diagnostics Table M-D-1. Tracer ZN520 DiagnosticsDiagnostic Reset Translating Multiple DiagnosticsResetting Diagnostics Cycling the Fan SwitchTable M-D-5. Valves Stay Open Table M-D-3. Fan outputs do not energizeTable M-D-4. Valves Stay Closed Table M-D-8. Fresh Air Damper Stays Closed Table M-D-6. Electric Heat Not OperatingTable M-D-7. Fresh Air Damper Stays Open Switch SW1 Controller Type Maintenance troubleshootingTroubleshooting the Relay Board Switch SW2 Electric HeatGreen Status LED Troubleshooting Tracer ZN010, ZN510 & ZN520Red Service LED Yellow Comm LEDTable M-T-1. Test sequence for 1-heat/1-cool configurations BOP5 BOP6Main Drain Pan MaintenanceMaintenance Procedures Winterizing the Coil Coil MaintenanceSteam and Hydronic Coil Cleaning Procedure Control Device Replacement Replacing the MotorMonthly Maintenance Periodic Maintenance ChecklistsMonthly Checklist Annual MaintenanceTypical wiring Csti Fan Speed SwitchCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN