Maintenance diagnostics
Diagnostics
Table M-D-1. Tracer ZN520 Diagnostics
Diagnostic | Fan | Other Outputs (Note 1) |
Condensate overflow | Off | Valves Closed, Fresh air damper Closed, electric heat Off, |
|
| Baseboard heat Off |
Low temperature detection | Off | Valves Open, Fresh air damper Closed, electric heat Off, |
|
| Baseboard heat Off |
Low air flow - fan failure | Off | Valves Closed, Fresh air damper Closed, electric heat Off, |
|
| Baseboard heat Off |
Space temperature failure | Off | Valves Closed, Fresh air damper Closed, electric heat Off, |
|
| Baseboard heat Off |
Entering water temp failure | On | Valves Enabled (Note 2), Fresh air damper Enabled (Note 2), |
|
| electric heat Enabled (Note 2), Baseboard heat Off |
Discharge air temp low limit | Off | Valves Open, Fresh air damper Closed, electric heat Off, |
|
| Baseboard heat Off |
Discharge air temp failure | Off | Valves Closed, Fresh air damper Closed, electric heat Off, |
|
| Baseboard heat Off, |
Fresh air temp failure | On | Valves Enabled, Fresh air damper Minimum position3, electric |
|
| heat Enabled, Baseboard heat Enabled |
Relative humidity failure | On | Valves Enabled, Fresh air damper Enabled, electric heat |
|
| Enabled, Baseboard heat Enabled |
Generic | On | Valves Enabled, Fresh air damper Enabled, electric heat |
|
| Enabled, Baseboard heat Enabled |
CO2 Input failure | On | Valves Enabled, Fresh air damper Enabled, electric heat |
|
| Enabled, Baseboard heat Enabled |
Maintenance required | On | Valves Enabled, Fresh air damper Enabled, electric heat |
|
| Enabled, Baseboard heat Enabled |
Local fan mode failure | On | Valves Enabled, Fresh air damper Enabled, Electric Heat |
|
| Enabled, Baseboard heat Enabled |
Local setpoint failure | On | Valves Enabled, Fresh air damper Enabled, electric heat |
|
| Enabled, Baseboard heat Enabled |
Invalid unit configuration | Off | Valves Disabled, Fresh air damper Disabled, electric heat |
|
| Disabled, Baseboard heat Disabled |
Normal – power up | On | Valves Enabled, Fresh air damper Enabled, Electric heat Enabled |
Note 1: The generic binary output
Note 2: When the entering water temperature is required but not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid entering water temperature value is present
Note 3: When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid outdoor air temperature value is present
60 |