Trane UniTrane Fan-Coil & Force Flo Air Conditioners manual Tracer ZN520 Sequence of Operation

Page 53

sequence of

Operation operation

Tracer ZN520 Sequence of Operation

The Tracer ZN520 operates the fan in the following modes:

1)occupied

2)unoccupied

3)occupied standby

4)occupied bypass

5)Tracer Summit with supply fan control

Occupied

When the controller is in the occupied mode, the unit attempts to maintain the space temperature at the active occupied heating or cooling setpoint, based on the measured space temperature, the discharge air temperature, the active setpoint, and the proportional/integral control algorithm. The modulating control algorithm used when occupied or in occupied standby is described in the following sections. Additional information related to the handling of the controller setpoints can be found in the previous Setpoint operation section.

Unoccupied Mode

When the controller is in the unoccupied mode, the controller attempts to maintain the space temperature at the stored unoccupied heating or cooling setpoint, based on the measured space temperature, the active setpoint and the control algorithm, regardless of the presence of a hardwired or communicated setpoint. Similar to other configuration properties of the controller, the locally stored unoccupied setpoints can be modified using Rover™ service tool.

In unoccupied mode, a simplified zone control algorithm is run. During the cooling mode, when the space tempera- ture is above the cool setpoint, the primary cooling capacity operates at 100%. If more capacity is needed, the supplementary cooling capacity turns on (or opens to 100%). During the heating mode, when the space temperature is below the heat setpoint, the primary heating capacity turns on. All capacity is turned off when the space temperature is between the unoccupied cooling and heating setpoints. Note that primary

heating or cooling capacity is defined by unit type and whether heating or cooling is enabled or disabled. For example, if the economizer is enabled and possible, it will be the primary cooling capacity. If hydronic heating is possible, it will be the primary heating capacity.

Occupied Standby Mode

The controller can be placed into the occupied standby mode when a communicated occupancy request is combined with the local (hardwired) occupancy binary input signal. When the communicated occupancy request is unoccupied, the occupancy binary input (if present) does not affect the controller’s occupancy. When the communicated occupancy request is occupied, the controller uses the local occupancy binary input to switch between the occupied and occupied standby modes.

During occupied standby mode, the controller’s economizer damper position goes to the economizer standby mini- mum position. The economizer standby minimum position can be changed using Rover service tool.

In the occupied standby mode, the controller uses the occupied standby cooling and heating setpoints. Because the occupied standby setpoints typically cover a wider range than the occupied setpoints, the TracerZN520 controller reduces the demand for heating and cooling the space. Also, the outdoor air economizer damper uses the econo- mizer standby minimum position to reduce the heating and cooling demands.

When no occupancy request is commu- nicated, the occupancy binary input switches the controller’s operating mode between occupied and unoccupied. When no communicated occupancy request exists, the unit cannot switch to occupied standby mode.

Occupied Bypass Mode

The controller can be placed in occupied bypass mode by either communicating an occupancy request of Bypass to the controller or by using the timed override On button on the Trane zone sensor.

When the controller is in unoccupied mode, you can press the On button on the zone sensor to place the controller into occupied bypass mode for the duration of the bypass time (typically 120 minutes).

Occupancy Sources

There are four ways to control the controller’s occupancy:

Communicated request (usually provided by the building automation system or peer device)

By pressing the zone sensor’s timed override On button

Occupancy binary input

Default operation of the controller (occupied mode)

A communicated request from a building automation system or another peer controller can change the controller’s occupancy. However, if communication is lost, the controller reverts to the default operating mode (occupied) after 15 minutes (configurable, specified by the “receive heartbeat time”), if no local hardwired occupancy signal exists.

A communicated request can be pro- vided to control the occupancy of the controller. Typically, the occupancy of the controller is determined by using time-of- day scheduling of the building automation system. The result of the time-of-day schedule can then be communicated to the unit controller.

Tracer Summit with Supply Fan Control If the unit is communicating with Tracer Summit and the supply fan control programming point is configured for Tracer (the factory configures as local), Tracer Summit will control the fan regardless of the fan mode switch position.

When the fan mode switch is set to Off or when power is restored to the unit, all Tracer ZN520 lockouts (latching diagnos- tics) are manually reset. The last diagnos- tic to occur is retained until the unit power is disconnected. Refer to Trane publica- tion, CNT-SVX04A-EN Tracer ZN520 Installation Operation and Programming Guide, for specific instructions regarding the procedure for running the Tracer ZN520.

UNT-SVX07A-EN

53

Image 53
Contents Models FC & FF ZO and later design sequence Installation, Operation, and MaintenanceCommon Hvac Acronyms General informationContents Model Number GeneralModel Number Description GeneralDigit 29 piping packages 0 = none Digit 28 auxiliary control valve 0 = noneDigit 30 control type 0 = none Digit 31 control optionTable I-GI-2. Low vertical fan-coil component data Table I-GI-1. Fan-coil component dataModel E horizontal recessed Available ModelsModel K low vertical cabinet Model M inverted vertical cabinetFactory-Installed Piping Packages Installation Weights DimensionsVertical Concealed Unit Dimensions & weights, in-lbs Vertical Concealed, Model aVertical Cabinet, Model B Vertical Cabinet Unit Dimensions, in-lbsHorizontal Concealed, Model C Horizontal Concealed Unit Dimensions, in-lbsHorizontal Cabinet, Model D Horizontal Cabinet Unit Dimensions, in-lbsHorizontal Recessed, Model E Installation Dimensions WeightsHorizontal Recessed Unit Dimensions, in-lbs Vertical Wall Hung Cabinet, Model F Vertical wall hung cabinet unit dimensions & weights, in-lbsVertical Recessed, Model H Vertical Recessed Unit Dimensions, in-lbsVertical Slope Top, Model J Vertical Slope Top Unit Dimensions, in-lbsLow Vertical Concealed, Model K Low Vertical Concealed Unit Dimensions, in-lbsLow Vertical Cabinet, Model L Low Vertical Cabinet Unit Dimensions, in-lbsInverted Vertical Cabinet, Model M Inverted vertical cabinet unit dimensions & weights, in-lbsInverted Vertical Recessed, Model N Inverted vertical recessed unit dimensions & weights, in-lbsFan-Coil Coil Connections Vertical Units Horizontal Units Horizontal Units Inverted Units Force Flo Coil Connections Vertical UnitsFresh Air Opening Dimensions, Horizontal Units Fresh Air Opening Dimensions, Vertical Units Wall Box Wall Box DimensionsProjection Panel Projection Panel DimensionsInstallation Preparation Pre-installation Installation considerationsReceiving and Handling Jobsite StoragePre-Installation Checklist Service AccessMechanical Connecting field piping to coilDuct Connections Piping ConsiderationsCondensate Drain Figure I-MR-4. Close-up view of the changeover sensor Venting the Hydronic CoilFigure I-MR-8. Manual circuit setter valve Balancing The Manual Circuit Setter ValveMechanical Steam Piping Code of System Components in Piping DiagramSupply Power Wiring Unit Wiring DiagramsWall Mounted Control Interconnection Wiring ElectricalTable I-ER-3. Decimal to fractional HP kW conversion Table I-ER-2. Low vertical free discharge motors, 115 voltTable I-ER-9. Electric heat kW Table I-ER-8. Fan-coil electric heat kWTable I-ER-11. Force Flo single stage, low kW electric heat Table I-ER-10. Force Flo single-stage, max kW electric heatTable I-ER-12. Force Flo 2-stage electric heat Installing the Unit InstallationUnit Leveling Figure I-IP-5. Zone sensor only Figure I-IP-3. Zone sensor with on/cancel Comm jackWiring Instructions Installing Wall Mounted ControlsFan Mode Switch Installation Zone Sensor InstallationUnit Leveling Installation ChecklistRecommended Communication Wiring Practices Communication WiringPre-startup Device AddressingPre-Startup Checklist Tracer ZN510 & ZN520 Unit Startup Installation startupGeneral Operation information Manual Fan Mode SwitchGeneral Information Relay BoardSequence Fan Mode Switch OperationTracer ZN010 & ZN510 Operation Tracer ZN520 OperationBinary Outputs Binary InputsAnalog Inputs Fan Mode SwitchZone Sensors Supply Fan OperationTracer ZN520 Sequence of Operation Discharge Air Tempering Cooling OperationHeating Operation Continuous Fan Operation Fan Mode OperationElectric Heat Operation Fan Start on High SpeedManual Fresh Air Damper Economizer Damper OptionTable O-SO-13. Binary output configuration Table O-SO-12. Binary input configurationsData Sharing Binary OutputsTable O-SO-15. Analog inputs Table O-SO-14. Analog inputsOn/Cancel Buttons Fan SwitchTable O-SO-16. Zone sensor wiring connections Zone SensorTable M-D-1. Tracer ZN520 Diagnostics Maintenance diagnosticsResetting Diagnostics Translating Multiple DiagnosticsDiagnostic Reset Cycling the Fan SwitchTable M-D-5. Valves Stay Open Table M-D-3. Fan outputs do not energizeTable M-D-4. Valves Stay Closed Table M-D-8. Fresh Air Damper Stays Closed Table M-D-6. Electric Heat Not OperatingTable M-D-7. Fresh Air Damper Stays Open Troubleshooting the Relay Board Maintenance troubleshootingSwitch SW1 Controller Type Switch SW2 Electric HeatRed Service LED Troubleshooting Tracer ZN010, ZN510 & ZN520Green Status LED Yellow Comm LEDBOP5 BOP6 Table M-T-1. Test sequence for 1-heat/1-cool configurationsMain Drain Pan MaintenanceMaintenance Procedures Winterizing the Coil Coil MaintenanceSteam and Hydronic Coil Cleaning Procedure Replacing the Motor Control Device ReplacementMonthly Checklist Periodic Maintenance ChecklistsMonthly Maintenance Annual MaintenanceCsti Fan Speed Switch Typical wiringCsti Non Fan Speed Switch Line voltage fan speed switch Tracer ZN010 with electric heat Tracer ZN510 with main and auxilliary valves ZN520 with 2-stage electric heat Page Page Page PL-TD-UNT-SVX07A-EN