Trane RT-SVX10C-EN specifications Variable Air Volume System Controls

Page 47

The occupied cooling setpoint ranges between 40 and 80 Fahrenheit. The warm-up setpoint ranges between 50 and 90 degrees Fahrenheit with a 2 degrees deadband. The Un- occupied cooling setpoint ranges between 45 and 98 degrees Fahrenheit. The heating setpoint ranges between 43 and 96 degrees Fahrenheit.

Two liquid crystal displays (LCD) display zone temperature, temperature setpoints, week day, time, and operational mode symbols.

The DIP switches on the subbase are used to enable or dis- able applicable functions, i.e.; Morning Warm-up, Econo- mizer minimum CFM override during unoccupied status, Fahrenheit or Centigrade, Supply air tempering, Remote zone temperature sensor, 12/24 hour time display, Smart fan, and Computed recovery.

During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of single pole double throw contacts is activated. See Table 3-10 for the Tempera- ture vs Resistance coefficient.

Constant Volume Zone Panel (5U68) - BAYSENS008B This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or automatic changeover control with dual setpoint capability.

Variable Air Volume System Controls

Remote Panel w/ NSB (5U58) - BAYSENS020B

This 7 day programmable sensor features four periods for Occupied\Unoccupied programming per day. Either one or all four periods can be programmed. If the power is inter- rupted, the program is retained in permanent memory. If power is off longer than 2 hours, only the clock and day may have to be reset.

The front panel allows selection of Occupied/Unoccupied periods with two temperature inputs (Cooling Supply Air Temperature and Heating Warm-up temperature) per occu- pied period. The occupied cooling setpoint ranges between

40and 80 Fahrenheit. The warm-up setpoint ranges be- tween 50 and 90 degrees Fahrenheit with a 2 degrees deadband. The Unoccupied cooling setpoint ranges be- tween 45 and 98 degrees Fahrenheit. The heating setpoint ranges between 43 and 96 degrees Fahrenheit.

The liquid crystal display (LCD) displays zone temperature, temperature setpoints, week day, time, and operational mode symbols.

The DIP switches on the subbase are used to enable or dis- able applicable functions, i.e.; Morning warm-up, econo- mizer minimum position override during unoccupied status, heat installed, remote zone temperature sensor, 12/24 hour time display, and daytime warm-up. Refer to

Table 3-10 for the Temperature vs Resistance coefficient.

During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of single pole double throw contacts is activated.

Remote Panel w/o NSB (5U59) - BAYSENS021A

The remote panel w/o Night setback has a system switch as well as a S/A temperature setpoint indicator, a local sensor, and four LED's. These features allow the operator to control

Installation (Continued)

system operation, and monitor unit operating status from a remote location. Use the installation instructions that shipped with the panel to install it, and the unit's field wiring diagram to connect it to the unit.

VAV Changeover Contacts (5K87)

These contacts are connected to the RTM when daytime heating on VAV units with internal or external hydronic heat is required. Daytime (occupied) heating switches the system to a CV type mode of operation. Refer to the unit wiring dia- gram for the field connection terminals in the unit control panel. The switch must be rated at 12 ma @ 24 VDC mini- mum.

Constant Volume or Variable Air Volume System Controls

Remote Human Interface Module (5U66)

The remote Human Interface module enables the operator to set of modify the operating parameters of the unit using it's 16 key keypad and view the operating status of the unit on the 2 line, 40 character LCD screen without leaving the building. However, the Remote Human Interface module can not be used to perform any service functions.

One remote panel is designed to monitor and control up to four units providing each of the units are equipped with an IPCB module. Use the installation instructions that shipped with the module to install it, and the appropriate illustrations in Figure 3-16 or 3-17 to connect it to the unit.

Remote Zone Sensor (BAYSENS013C)

This electronic analog sensor features remote zone sensing and timed override with override cancellation. It is used when the RTM has been programmed as the source for zone temperature control. Refer to Table 3-10 for the Tem- perature vs Resistance coefficient.

Remote Zone Sensor (BAYSENS014C)

This electronic analog sensor features single setpoint capa- bility and timed override with override cancellation. It is used with a Trane Integrated ComfortTM system. Refer to Table 3- 10 for the Temperature vs Resistance coefficient.

Remote Zone Sensor (5RT16, 5U57, and 5U69) (BAYSENS016A)

This bullet type analog Temperature sensor can be used for; outside air (ambient) sensing, return air temperature sens- ing, supply air temperature sensing, remote temperature sensing (uncovered), morning warm-up temperature sens- ing, and for VAV zone reset. Wiring procedures vary accord- ing to the particular application and equipment involved. When this sensor is wired to a BAYSENS019* or BAYSENS020* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to Table 3-10 for the Temperature vs Resistance coefficient.

Remote Zone Sensor (5RT16, 5U57, and 5U69) (BAYSENS017B)

This electronic analog sensor can be used with BAYSENS019*, 020*, or 021A Remote Panels. When this sensor is wired to a BAYSENS019* or BAYSENS020* Re- mote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.

46

Image 47
Contents With 3-DTMScroll Compressors ModelsLater Design Sequence Overview of Manual Literature Change HistoryTable of Contents Model Number Description General InformationDigit 3 Unit Airflow Unit Description Fiberglass WoolHazard Identification General Information Commonly Used AcronymsSupply AIR General InformationCFM Ventilation Control Module VCM Design special option onlyLead-Lag Constant Volume CV Units Unit Component Layout and Shipwith Locations Variable Air Volume VAV UnitsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents Storage Unit Dimensions & Weight InformationNo Step Surface Unit Inspection As soon as the unit arrives at the job sitePage Sahf Cooling-Only Units 20 thru 75 Ton Electrical Entrance Data Unit Dimensions InstallationUnit Dimensional Data Dimensions Size Unit Base Dimensional Data DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Size Furnace Dimensions Note Size/MBH Length Height Unit Base Dimensional Data Dimensions SizeUnit Dimensions Size Electrical Entrance Data Unit Dimensions SizeSHG Cooling & Heating Units 90 through 130 Ton Sshf SahfSehf SlhfSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Roof Curb and DuctworkSE,SL Pitch Pocket Location Installation Unit Rigging & PlacementIf a Trane Curb Accessory Kit is not used Heavy ObjectsTypical Unit Rigging Unit Base & Roof Curb Section Requirements for Electric Heat Units Main Electrical Power RequirementsInstallation Field Installed Control Wiring General Unit RequirementsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Units with StatitracTM Installation Sensor & Tubing InstallationGas Heat Units SFH Connecting the Gas Supply Line to the Furnace Gas TrainHazardous Gases and Flammable Vapors 350 MBH 850 MBH Hot Water Heat Units SLH Flue Assembly InstallationFlue Assembly 1000 MBH Modulating 500 MBH 1000 MBHSSHG-90 Steam Heat Units SSHThrough 130 Ton units Page Use Copper Conductors Only Hazardous VoltageLive Electrical Components Typical Field Power Wiring 20 thru 75 Ton Page FLA Supply Fan Motor FLA ea HorsepowerCondenser Fans Total FLA Exhaust Fan MotorUnit Tonnage No. of Compressors Tonnage Type Designation CombustionBlower Motor Sfhf Only On the Next Single Source Power 380V, 415V, 460V,Load Definitions Load = Current of the Largest Motor Compressor or FAN MotorMCA = 1.25 x Load MOP = 1.25 x Load Power Wire Sizing and Protection Device EquationsDisconnect Switch Sizing DSS Dual Source Power units 200VConstant Volume System Controls Controls using 24 VACInstallation Controls using DC Analog Input/Outputs Constant Volume or Variable Air Volume System Controls Variable Air Volume System ControlsDepressurize PressurizeFire Purge16A Refer to Wiring Notes on16B Page 17A 17B Input Voltage VAV SetpointTable of Contents Sequence of Operation Cooling Sequence of OperationPropane Gas Gas Heating Sequence of OperationFenwal Ignition System Unit Start-UpFull and Limited Modulating Gas Furnace Modulating Gas Sequence of OperationFlame Failure Freeze Protection Electric Heat Sequence of OperationUnit Start-Up Wet Heat Sequence of Operation Electrical Phasing Unit PowerCompressor Damage Voltage Imbalance Voltage Supply and Voltage ImbalanceVoltage Supply IGV Service Test Guide for Component OperationSupply FAN If all of the fans are rotating backwards System Airflow Measurements Constant Volume SystemsRotating Components Verifying Proper Fan RotationCondenser Fan Location with Human Interface Designator Variable Air Volume Systems Optional with all units equipped with an economizer Exhaust Airflow MeasurementTraqTM Sensor Airflow Measurement Optional with all UnitsTon Supply Fan Performance without Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop Ton Supply Fan Performance with Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM AIR Through 75 Ton Component Static Pressure Drops Inches W.CCFM RPM BHP STDAIR HF-C30 000 HF-C20 000HF-C25 000 10,000AIR RPM BHP RPM BHP BHP RPM BHP RPM BHPFresh Air & Return Air Damper Operation Economizer Damper AdjustmentTo Adjust the Fresh Air Damper Travel Exhaust Air DampersTon Units Damper Travel Adjustment PositionConnecting Rod Crank Arm Hole Configuration70 & 105 Ton Fresh Air & Return Air Linkage AdjustmentCompressor Start-Up All SystemsAt Low Ambient Start-Up Compressor Operational SoundsRefrigerant Charging At ShutdownCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Low Ambient Dampers Thermostatic Expansion ValvesCharging by Subcooling Gas Furnace Start-Up Electric, Steam and Hot Water Start-UpTwo Stage Gas Furnace High-Fire AdjustmentCombustion Air Adjustment O2 Low-Fire Adjustment 500 MBH, 850 & 1,000 MBH onlyCO2 Pressure MBHFiring Manifold Unit control Full Modulating Gas FurnaceHeat Exchanger Modulating Gas Regulator Legend Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Typical Gas Furnace Unit Start-Up Final Unit CheckoutService & Maintenance Unit Internal Fuse Replacement Data & VFD Factory Settings Service & MaintenanceModel Type Unit Model Box-type Note QtyQty Size of each Wet Heat Coil Fin Data Total Coil FinsService & Maintenance Fan Belt Adjustment Gripbelts Gripnotch Cross Small P.D Section Range Min Max Scroll Compressor ReplacementSuction Line Filter/Drier Installation Supply and Exhaust Fan VFD Programming Parameters Hazardous Voltage! w/CapacitorsVFD Programming Parameters Cooling Season Service & Maintenance Monthly MaintenanceFilters Heating Season Coil CleaningSteam or Hot Water Coils Coil CleanersContains Refrigerant Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Equipment Damage From Ultraviolet UV Lights Warranty and Liability Clause115 116