Trane RT-SVX10C-EN specifications Purge, Fire

Page 49

PURGE

Supply Fan - On

Inlet Vanes - Open (if equipped) Exhaust Fan - On (if equipped) Exhaust Dampers - Open (if equipped) OA Dampers - Open

Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - Energized

VO Relay - Energized (with VOM module installed) OA Preheater State - Off (with VCM module installed)

SHUTDOWN Supply Fan - Off

Inlet Vanes - Closed (if equipped) Exhaust Fan - Off (if equipped)

Exhaust Dampers - Closed (if equipped) OA Dampers - Closed

Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - De-energized

VO Relay - Energized (with VOM module installed) OA Preheater State - Off (with VCM module installed)

FIRE

Supply Fan - Off

Inlet Vanes - Closed (if equipped) Exhaust Fan - Off (if equipped)

Exhaust Dampers - Closed (if equipped) OA Dampers - Closed

Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - De-energized

VO Relay - Energized (with VOM module installed) OA Preheater State - Off (with VCM module installed)

Table 3-10 - Temperature vs. Resistance Coefficient

The UCM network relies on various sensors located throughout the system to provide temperature information in the form of an analog input. All of the sensors used have the same temperature vs. resistance co-efficient and are made from Keystone Carbon D97 material with a 1 degree Centigrade tolerance.

Emergency Stop Switch (5S71)

A normally closed (N.C.) switch (5S71) wired to the RTM may be used during emergency situations to shut down all unit operations. When opened, an immediate shutdown oc- curs. An emergency stop diagnostic is entered into the Hu- man Interface and the unit must be manually reset. Refer to the appropriate illustrations in Figure 3-16 or 3-17 for the proper connection terminals in the unit control panel. The switch must be rated for 12 ma @ 24 VDC minimum.

Occupied/Unoccupied Contacts (5K86)

To provide Night Setback control if a remote panel with NSB (5U58) was not ordered, a field supplied contact (5K86) must be installed. This binary input provides the Occupied/ Unoccupied status information of the building to the RTM. It can be initiated by a time clock, or a Building Automation System control output. The relay’s contacts must be rated for 12 ma @ 24 VDC minimum. Refer to the appropriate il- lustrations in Figure 3-16 or 3-17 for the proper connection terminals in the unit control panel.

Demand Limit Relay (5K89)

If the unit is equipped with a Generic BAS Module (1U51), (i.e. unit model number digit 21+ is a “K”), a normally open (N.O.) switch may be used to limit the electrical power us- age during peak periods. When demand limit is initiated, the mechanical cooling and heating operation is limited to either 50% or 100%. Demand limit can be initiated by a toggle switch closure, a time clock, or an ICSTM control output. These contacts must be rated for 12 ma @ 24 VDC mini- mum.

Outside Air Sensor (3RT3) - BAYSENS016A

This device senses the outdoor air temperature and sends this information in the form of an analog input to the RTM. It's factory installed on units with an economizer, but can be field provided/installed and used for informational purposes on units without an economizer. Refer to the appropriate il- lustrations in Figure 3-16 or 3-17 for the proper connection terminals in the unit control panel. Refer to Table 3-10 for Temperature vs Resistance coefficient.

Generic Building Automation System (1U51)

Temperature (F)

Resistance

Temperature (F)

Resistance

The Generic Building Automation System (GBAS) module

(in. 1000 Ohms)

(in. 1000 Ohms)

allows a non-Trane building control system to communicate

-40

346.1

71

11.6

with the rooftop unit and accepts external setpoints in form

-30

241.7

72

11.31

-20

170.1

73

11.03

of analog inputs for cooling, heating, demand limiting, and

-10

121.4

74

10.76

supply air pressure parameters. Refer to Figure 3-18 for the

-5

103

75

10.5

input wiring to the GBAS module and the various desired

0

87.56

76

10.25

setpoints with the corresponding DC voltage inputs for both

5

74.65

77

10

VAV and CV applications.

10

63.8

78

9.76

 

15

54.66

79

9.53

For complete application details of the module, refer to

20

46.94

80

9.3

25

40.4

85

8.25

Engineering Bulletin UN-PRB001-EN.

30

34.85

90

7.33

 

35

30.18

100

5.82

 

40

26.22

105

5.21

 

45

22.85

110

4.66

 

50

19.96

120

3.76

 

55

17.47

130

3.05

 

60

15.33

140

2.5

 

65

13.49

150

2.05

 

66

13.15

160

1.69

 

67

12.82

170

1.4

 

68

12.5

180

1.17

 

69

12.19

190

0.985

 

70

11.89

200

0.83

 

48

Image 49
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Overview of Manual Literature Change HistoryTable of Contents Model Number Description General InformationDigit 3 Unit Airflow Hazard Identification Fiberglass WoolGeneral Information Commonly Used Acronyms Unit DescriptionSupply AIR General InformationCFM Ventilation Control Module VCM Design special option onlyLead-Lag Constant Volume CV Units Unit Component Layout and Shipwith Locations Variable Air Volume VAV UnitsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents No Step Surface Unit Dimensions & Weight InformationUnit Inspection As soon as the unit arrives at the job site StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Dimensional Data Dimensions Size InstallationUnit Base Dimensional Data Dimensions Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeElectrical Entrance Data Unit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Sehf SahfSlhf SshfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G If a Trane Curb Accessory Kit is not used Installation Unit Rigging & PlacementHeavy Objects Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section Installation Field Installed Control Wiring Main Electrical Power RequirementsGeneral Unit Requirements Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Units with StatitracTM Installation Sensor & Tubing InstallationHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH Flue Assembly Flue Assembly Installation1000 MBH Modulating 500 MBH 1000 MBH Hot Water Heat Units SLHSSHG-90 Steam Heat Units SSHThrough 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Condenser Fans Total FLA Supply Fan Motor FLA ea HorsepowerExhaust Fan Motor FLABlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation Load Definitions Load Single Source Power 380V, 415V, 460V,= Current of the Largest Motor Compressor or FAN Motor On the NextDisconnect Switch Sizing DSS Power Wire Sizing and Protection Device EquationsDual Source Power units 200V MCA = 1.25 x Load MOP = 1.25 x LoadInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Constant Volume or Variable Air Volume System Controls Variable Air Volume System ControlsDepressurize PressurizeFire Purge16A Refer to Wiring Notes on16B Page 17A 17B Input Voltage VAV SetpointTable of Contents Sequence of Operation Cooling Sequence of OperationFenwal Ignition System Gas Heating Sequence of OperationUnit Start-Up Propane GasFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance IGV Service Test Guide for Component OperationSupply FAN Rotating Components System Airflow Measurements Constant Volume SystemsVerifying Proper Fan Rotation If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems TraqTM Sensor Airflow Measurement Exhaust Airflow MeasurementOptional with all Units Optional with all units equipped with an economizerTon Supply Fan Performance without Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop Ton Supply Fan Performance with Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM AIR Through 75 Ton Component Static Pressure Drops Inches W.CAIR STDCFM RPM BHP HF-C25 000 HF-C20 00010,000 HF-C30 000AIR RPM BHP RPM BHP BHP RPM BHP RPM BHPTo Adjust the Fresh Air Damper Travel Economizer Damper AdjustmentExhaust Air Dampers Fresh Air & Return Air Damper OperationConnecting Rod Crank Arm Hole Damper Travel Adjustment PositionConfiguration Ton UnitsCompressor Start-Up Fresh Air & Return Air Linkage AdjustmentAll Systems 70 & 105 TonRefrigerant Charging Compressor Operational SoundsAt Shutdown At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Gas Furnace Start-Up Electric, Steam and Hot Water Start-UpCombustion Air Adjustment O2 High-Fire AdjustmentLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only Two Stage Gas FurnaceFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Typical Gas Furnace Unit Start-Up Final Unit CheckoutService & Maintenance Unit Internal Fuse Replacement Data & VFD Factory Settings Service & MaintenanceQty Size of each Unit Model Box-type Note QtyWet Heat Coil Fin Data Total Coil Fins Model TypeService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Heating Season Coil CleaningContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Equipment Damage From Ultraviolet UV Lights Warranty and Liability Clause115 116