Trane RT-SVX10C-EN specifications Compressor Operational Sounds, Refrigerant Charging, At Shutdown

Page 85

change any two leads to check the internal motor phas- ing. If the compressor runs backward for an extended period (15 to 30 minutes), the motor winding can over heat and cause the motor winding thermostats to open. This will cause a “compressor trip” diagnostic and stop the compressor.

11.Press the STOP key at the Human Interface Module in the unit control panel to stop the compressor operation.

12.Repeat steps 5 through 11 for each compressor stage and the appropriate condenser fans.

Refrigerant Charging

1.Attach a set of service gauges onto the suction and dis- charge gauge ports for each circuit. Refer to Figure 4-6 for the various compressor locations.

2.Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the SAHF-PTG-1B for CV applications or SAHF-PTG- 2B for VAV applications for the SERVICE TEST screens and programming instructions.

3.Use Table 4-1 to program the following system compo- nents for the number 1 refrigeration circuit by scrolling through the displays;

Supply Fan (On)

Inlet Guide Vanes/VFD (100%, if applicable) OCC/UNOCC Relay (Unoccupied for VAV units) All Compressors for each circuit (On) Condenser Fans for each circuit (On)

4.Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay desig- nated in this step has elapsed. Press the ENTER key to confirm this choice.

Unit Start-Up (Continued)

Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all Federal, State and local laws. Refer to general service bulletin MSCU-SB-1 (latest edition).

7.Verify that the oil level in each compressor is correct. The oil level may be down to the bottom of the sightglass but should never be above the sightglass.

8.Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.

9.Repeat steps 1 through 8 for the number 2 refrigeration circuit.

10.After shutting the system off, check the compressor's oil’s appearance. Discoloration of the oil indicates that an abnormal condition has occurred. If the oil is dark and smells burnt, it has overheated because of: compressor is operating at extremely high condensing temperatures; high superheat; a compressor mechanical failure; or, oc- currence of a motor burnout.

If the oil is black and contains metal flakes, a mechanical failure has occurred. This symptom is often accompanied by a high compressor amperage draw.

If a motor burnout is suspected, use an acid test kit to check the condition of the oil. Test results will indicate an acid level exceeding 0.05 mg KOH/g if a burnout oc- curred.

The scroll compressor uses Trane OIL-42 without substi- tution. The appropriate oil charge for a 9 and 10 Ton scroll compressor is 8.5 pints. For a 14 and 15 Ton scroll compressor, use 13.8 pints.

Compressor Crankcase Heaters

9and 10 ton scroll compressors have a 100-watt heater in- stalled. 14 and 15 ton scroll compressors have two 80-watt heaters installed per compressor.

WARNING

Rotating Components!

Disconnect all electric power, including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvert- ently energized. Failure to disconnect power before ser- vicing could result in death or serious injury.

5.Press the TEST START key to start the test. Remember that the delay designated in step 4 must elapse before the system will begin to operate.

6.After all of the compressors and condenser fans for the number 1 circuit have been operating for approximately 30 minutes, observe the operating pressures. Use the appropriate pressure curve in Tables 4-6 to determine the proper operating pressures. For superheat and sub- cooling guidelines, refer to "Thermostatic Expansion Valves and Charging by Subcooling" at the end of this section.

Compressor Operational Sounds

Because of the scroll compressor design, it emits a higher frequency tone (sound) than a reciprocating compressor. It is designed to accommodate liquids, both oil and refriger- ant, without causing compressor damage. The following dis- cussion describes some of the operational sounds that dif- ferentiate it from those typically associated with a recipro- cating compressor. These sounds do not affect the opera- tion or reliability of the compressor.

At Shutdown

When a Scroll compressor shuts down, the gas within the scroll expands and causes momentary reverse rotation until the discharge check valve closes. This results in a “flutter” type sound.

At Low Ambient Start-Up

When the compressor starts up under low ambient condi- tions, the initial flow rate of the compressor is low due to the low condensing pressure. This causes a low differential across the thermal expansion valve that limits its capacity. Under these conditions, it is not unusual to hear the com- pressor rattle until the suction pressure climbs and the flow rate increases.

83

Image 85
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Overview of Manual Literature Change HistoryTable of Contents Model Number Description General InformationDigit 3 Unit Airflow Hazard Identification Fiberglass WoolGeneral Information Commonly Used Acronyms Unit DescriptionSupply AIR General InformationCFM Ventilation Control Module VCM Design special option onlyLead-Lag Constant Volume CV Units Unit Component Layout and Shipwith Locations Variable Air Volume VAV UnitsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents No Step Surface Unit Dimensions & Weight InformationUnit Inspection As soon as the unit arrives at the job site StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Dimensional Data Dimensions Size InstallationUnit Base Dimensional Data Dimensions Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeElectrical Entrance Data Unit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Sehf SahfSlhf SshfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G If a Trane Curb Accessory Kit is not used Installation Unit Rigging & PlacementHeavy Objects Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section Installation Field Installed Control Wiring Main Electrical Power RequirementsGeneral Unit Requirements Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Units with StatitracTM Installation Sensor & Tubing InstallationHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH Flue Assembly Flue Assembly Installation1000 MBH Modulating 500 MBH 1000 MBH Hot Water Heat Units SLHSSHG-90 Steam Heat Units SSHThrough 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Condenser Fans Total FLA Supply Fan Motor FLA ea HorsepowerExhaust Fan Motor FLABlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation Load Definitions Load Single Source Power 380V, 415V, 460V,= Current of the Largest Motor Compressor or FAN Motor On the NextDisconnect Switch Sizing DSS Power Wire Sizing and Protection Device EquationsDual Source Power units 200V MCA = 1.25 x Load MOP = 1.25 x LoadInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Constant Volume or Variable Air Volume System Controls Variable Air Volume System ControlsDepressurize PressurizeFire Purge16A Refer to Wiring Notes on16B Page 17A 17B Input Voltage VAV SetpointTable of Contents Sequence of Operation Cooling Sequence of OperationFenwal Ignition System Gas Heating Sequence of OperationUnit Start-Up Propane GasFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance IGV Service Test Guide for Component OperationSupply FAN Rotating Components System Airflow Measurements Constant Volume SystemsVerifying Proper Fan Rotation If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems TraqTM Sensor Airflow Measurement Exhaust Airflow MeasurementOptional with all Units Optional with all units equipped with an economizerTon Supply Fan Performance without Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop Ton Supply Fan Performance with Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM AIR Through 75 Ton Component Static Pressure Drops Inches W.CAIR STDCFM RPM BHP HF-C25 000 HF-C20 00010,000 HF-C30 000AIR RPM BHP RPM BHP BHP RPM BHP RPM BHPTo Adjust the Fresh Air Damper Travel Economizer Damper AdjustmentExhaust Air Dampers Fresh Air & Return Air Damper OperationConnecting Rod Crank Arm Hole Damper Travel Adjustment PositionConfiguration Ton UnitsCompressor Start-Up Fresh Air & Return Air Linkage AdjustmentAll Systems 70 & 105 TonRefrigerant Charging Compressor Operational SoundsAt Shutdown At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Gas Furnace Start-Up Electric, Steam and Hot Water Start-UpCombustion Air Adjustment O2 High-Fire AdjustmentLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only Two Stage Gas FurnaceFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Typical Gas Furnace Unit Start-Up Final Unit CheckoutService & Maintenance Unit Internal Fuse Replacement Data & VFD Factory Settings Service & MaintenanceQty Size of each Unit Model Box-type Note QtyWet Heat Coil Fin Data Total Coil Fins Model TypeService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Heating Season Coil CleaningContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Equipment Damage From Ultraviolet UV Lights Warranty and Liability Clause115 116