Trane RT-SVX10C-EN specifications Steam Heat Units SSH, SSHG-90

Page 36

4.Install a "Gate" type valve in the supply branch line as close as possible to the hot water main and upstream of any other device or takeoff.

5.Install a "Gate" type valve in the return branch line as close as possible to the return main and down stream of any other device.

6.Install a strainer in the hot water supply branch as shown in Figure 3-12.

7.Install the 3-way valve in an upright position, piped for valve seating against the flow. Ensure that the valve's lo- cation lends itself to serviceability.

8.The Type "W" hot water coil used in SLHF units is self- venting only when the tube water velocity exceeds 1.5 feet per second (fps). If the tube velocity is less than 1.5 feet per second, either:

a. install an automatic air vent at the top of the return header, using the tapped pipe connection;

or,

b. vent the coil from the top of the return header down to the return piping. At the vent connection, size the return piping to provide sufficient water velocity.

9.Install a "Globe" type valve in the Bypass line as shown in Figure 3-12.

Table 3-5

Connection Sizes for Hot Water & Steam Coil (See Note 1)

 

Heat

Coil Connections

 

Section

(diameter in inches)

Unit Model

Capacity

 

 

and Size

(Note 2)

Supply

Return

SLH*-20

High or

2-1/2"

2-1/2"

to 130

Low Heat

 

 

SSHF-20

High or

 

 

to 30

Low Heat

3"

1-1/4"

SSHF-40

High Heat

3"

1-1/2"

to 75

 

 

 

(Note 3)

Low Heat

1-1/2"

1"

SSHG-90

Low Heat

 

 

to 130

(Note 3)

 

 

Notes:

1.Type W coils—with center offset headers—are used in SLH_ units; Type NS coils are used in SSH_ units.

2.See Digit 9 of the unit model number to determine the heating capacity.

3.SSH_ - 40 to 130 Ton units have multiple headers.

Steam Heat Units (SSH_)

Steam heating coils are factory installed inside the heater section of the unit. The coils are pitched, within the units, to provide the proper condensate flow from the coil. To main- tain the designed degree of pitch for the coil, the unit must be level.

Once the unit is set into place, the steam piping and the factory provided two way modulating valve must be in- stalled. The valve can be installed inside the heater section or near the unit. If the valve is installed in a remote location,

Installation (Continued)

use field supplied wiring to extend the control wires from the heater section to the valve. Two access holes are pro- vided in the unit base as illustrated in Figure 3-2.

Following the guidelines listed below will enhance both the installation and operation of the "wet heat" system.

Figure 3-13 illustrates the recommended piping configura- tions for the steam coil. Table 3-5 list the coil connection sizes.

Note: The valve actuators are not waterproof. Failure to protect the valve from moisture may result in the loss of heating control.

1.Support all field-installed piping independently from the heating coil.

2.Use swing joints or flexible connectors adjacent to the heating coil. (These devices will absorb the strains of ex- pansion and contraction.)

3.Install the 2-way valve in an upright position. Ensure that the valve's location lends itself to serviceability.

4.Pitch the supply and return steam piping downward 1" per 10' of run in the direction of flow.

5.All return lines and fittings must be equal to the diameter of the "outlet" connection on the steam coil(s). If the steam trap connection is smaller that the coil "outlet" di- ameter, reduce the pipe size between the strainer and the steam trap connections only.

6.Install a 1/2" 15 degree swing-check vacuum breaker at the top of the return coil header using the tapped pipe connection. Position the vacuum breaker as close to the coil as possible.

Note: Vacuum breakers should have extended lines from the vent ports to the atmosphere or connect each vent line to the return pipe on the discharge side of the steam traps.

7.Install a "Gate" type valve in the supply branch line as close as possible to the steam main and upstream of any other device.

8.Install a "Gate" type valve in the return branch line as close as possible to the condensate return main and downstream of any other device.

9.Install a strainer as close as possible to the inlet of the control valve and steam trap(s).

10.Steam trap selection should be based on the maximum possible condensate flow and the recommended load factors.

11.Install a Float-and-Thermostatic (FT) type trap to main- tain proper flow. They provide gravity drains and continu- ous discharge operation. FT type traps are required if the system includes either;

a.an atmospheric pressure/gravity condensate return; or,

b.a potentially low pressure steam supply.

35

Image 36
Contents Models Later Design SequenceWith 3-DTMScroll Compressors Literature Change History Overview of ManualTable of Contents General Information Model Number DescriptionDigit 3 Unit Airflow Fiberglass Wool Hazard IdentificationGeneral Information Commonly Used Acronyms Unit DescriptionGeneral Information Supply AIRVentilation Control Module VCM Design special option only CFMLead-Lag Constant Volume CV Units Variable Air Volume VAV Units Unit Component Layout and Shipwith LocationsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents Unit Dimensions & Weight Information No Step SurfaceUnit Inspection As soon as the unit arrives at the job site StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Installation Unit Dimensional Data Dimensions SizeUnit Base Dimensional Data Dimensions Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Base Dimensional Data Dimensions Size Unit Dimensions SizeElectrical Entrance Data Unit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Sahf SehfSlhf SshfRoof Curb and Ductwork SE,SLSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Installation Unit Rigging & Placement If a Trane Curb Accessory Kit is not usedHeavy Objects Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section Main Electrical Power Requirements Installation Field Installed Control WiringGeneral Unit Requirements Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Installation Sensor & Tubing Installation Units with StatitracTMConnecting the Gas Supply Line to the Furnace Gas Train Hazardous Gases and Flammable VaporsGas Heat Units SFH 350 MBH 850 MBH Flue Assembly Installation Flue Assembly1000 MBH Modulating 500 MBH 1000 MBH Hot Water Heat Units SLHSteam Heat Units SSH SSHG-90Through 130 Ton units Page Hazardous Voltage Live Electrical ComponentsUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Supply Fan Motor FLA ea Horsepower Condenser Fans Total FLAExhaust Fan Motor FLACombustion Blower Motor Sfhf OnlyUnit Tonnage No. of Compressors Tonnage Type Designation Single Source Power 380V, 415V, 460V, Load Definitions Load= Current of the Largest Motor Compressor or FAN Motor On the NextPower Wire Sizing and Protection Device Equations Disconnect Switch Sizing DSSDual Source Power units 200V MCA = 1.25 x Load MOP = 1.25 x LoadControls using 24 VAC Installation Controls using DC Analog Input/OutputsConstant Volume System Controls Variable Air Volume System Controls Constant Volume or Variable Air Volume System ControlsPressurize DepressurizePurge FireRefer to Wiring Notes on 16A16B Page 17A 17B VAV Setpoint Input VoltageTable of Contents Cooling Sequence of Operation Sequence of OperationGas Heating Sequence of Operation Fenwal Ignition SystemUnit Start-Up Propane GasModulating Gas Sequence of Operation Flame FailureFull and Limited Modulating Gas Furnace Electric Heat Sequence of Operation Unit Start-Up Wet Heat Sequence of OperationFreeze Protection Unit Power Compressor DamageElectrical Phasing Voltage Supply and Voltage Imbalance Voltage SupplyVoltage Imbalance Service Test Guide for Component Operation IGVSupply FAN System Airflow Measurements Constant Volume Systems Rotating ComponentsVerifying Proper Fan Rotation If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems Exhaust Airflow Measurement TraqTM Sensor Airflow MeasurementOptional with all Units Optional with all units equipped with an economizer20 & 25 Ton Supply Fan Performance without Inlet Guide Vanes Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM Through 75 Ton Component Static Pressure Drops Inches W.C AIRSTD AIRCFM RPM BHP HF-C20 000 HF-C25 00010,000 HF-C30 000RPM BHP BHP RPM BHP RPM BHP AIR RPM BHPEconomizer Damper Adjustment To Adjust the Fresh Air Damper TravelExhaust Air Dampers Fresh Air & Return Air Damper OperationDamper Travel Adjustment Position Connecting Rod Crank Arm HoleConfiguration Ton UnitsFresh Air & Return Air Linkage Adjustment Compressor Start-UpAll Systems 70 & 105 TonCompressor Operational Sounds Refrigerant ChargingAt Shutdown At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Thermostatic Expansion Valves Charging by SubcoolingLow Ambient Dampers Electric, Steam and Hot Water Start-Up Gas Furnace Start-UpHigh-Fire Adjustment Combustion Air Adjustment O2Low-Fire Adjustment 500 MBH, 850 & 1,000 MBH only Two Stage Gas FurnaceMBH Firing ManifoldCO2 Pressure Full Modulating Gas Furnace Heat ExchangerUnit control Limited Modulating Gas Furnace Unit Start-Up Modulating Gas RegulatorModulating Gas Regulator Legend Unit Start-Up Final Unit Checkout Typical Gas FurnaceService & Maintenance Service & Maintenance Unit Internal Fuse Replacement Data & VFD Factory SettingsUnit Model Box-type Note Qty Qty Size of eachWet Heat Coil Fin Data Total Coil Fins Model TypeService & Maintenance Fan Belt Adjustment Scroll Compressor Replacement Suction Line Filter/Drier InstallationGripbelts Gripnotch Cross Small P.D Section Range Min Max Hazardous Voltage! w/Capacitors VFD Programming ParametersSupply and Exhaust Fan VFD Programming Parameters Service & Maintenance Monthly Maintenance FiltersCooling Season Coil Cleaning Heating SeasonCoil Cleaners Contains RefrigerantSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Warranty and Liability Clause Equipment Damage From Ultraviolet UV Lights115 116