Trane RT-SVX10C-EN Economizer Damper Adjustment, To Adjust the Fresh Air Damper Travel

Page 82

Economizer Damper Adjustment

Exhaust Air Dampers

Verify that the exhaust dampers (if equipped) close tightly when the unit is off. Adjust the damper linkage as necessary to ensure proper closure. An access panel is provided un- der each damper assembly.

Fresh Air & Return Air Damper Operation

The fresh air and return air damper linkage is accessible from the filter section of the unit. The damper linkage con- necting the fresh air dampers to the return air dampers is preset from the factory in the number 1 position. Refer to Table 4-5 for the appropriate linkage position for the unit and operating airflow (CFM).

WARNING

No Step Surface!

Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to col- lapse. Failure of the drain pan could result in death or serious injury.

Note: Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.

Arbitrarily adjusting the fresh air dampers to open fully when the return air dampers are closed or; failing to main- tain the return air pressure drop with the fresh air dampers when the return air dampers are closed, can overload the supply fan motor and cause building pressurization control problems due to improper CFM being delivered to the space.

The fresh air/return air damper linkage is connected to a crank arm with a series of holes that allows the installer or operator to modify the amount of fresh air damper travel in order to match the return static pressure. Refer to

Table 4-5 for the equivalent return air duct losses that corre- spond to each of the holes illustrated in Figure 4-5.

To Adjust the Fresh Air Damper Travel:

1.Drill a 1/4" hole through the unit casing up stream of the return air dampers. Use a location that will produce an accurate reading with the least amount of turbulence.

Several locations may be necessary, and average the reading.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvert- ently energized. Failure to disconnect power before ser- vicing could result in death or serious injury.

HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT SWITCH 1S14.

Unit Start-Up (Continued)

2.Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.

3.Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the "On" position.

4.Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the applicable SAHF-PTG manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.

5.Use Table 4-1 to program the following system components for operation by scrolling through the displays;

Supply Fan (On)

Inlet Guide Vanes (100% Open, if applicable) Variable Frequency Drive (100% Output, if applicable) RTM Occ/Unocc Output (Unoccupied)

Fresh Air Dampers (Closed)

6.Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay desig- nated in this step has elapsed. Press the ENTER key to confirm this choice.

WARNING

Rotating Components!

Disconnect all electric power, including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvert- ently energized. Failure to disconnect power before ser- vicing could result in death or serious injury.

7.Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fan will begin to operate.

8.With the fresh air dampers fully closed and the supply fan operating at 100% airflow requirements, measure the return static pressure at the location determined in step 1.

9.Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.

10.Open the field supplied main power disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the "Open" position while working on the dampers.

11.Compare the static pressure reading to the static pres- sure ranges and linkage positions in Table 4-5 for the unit size and operating CFM.

80

Image 82
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Literature Change History Overview of ManualTable of Contents General Information Model Number DescriptionDigit 3 Unit Airflow General Information Commonly Used Acronyms Fiberglass WoolHazard Identification Unit DescriptionGeneral Information Supply AIRVentilation Control Module VCM Design special option only CFMLead-Lag Constant Volume CV Units Variable Air Volume VAV Units Unit Component Layout and Shipwith LocationsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents Unit Inspection As soon as the unit arrives at the job site Unit Dimensions & Weight InformationNo Step Surface StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Base Dimensional Data Dimensions InstallationUnit Dimensional Data Dimensions Size Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Electrical Entrance Data Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeUnit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Slhf SahfSehf SshfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Heavy Objects Installation Unit Rigging & PlacementIf a Trane Curb Accessory Kit is not used Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section General Unit Requirements Main Electrical Power RequirementsInstallation Field Installed Control Wiring Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Installation Sensor & Tubing Installation Units with StatitracTMHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH 1000 MBH Modulating 500 MBH 1000 MBH Flue Assembly InstallationFlue Assembly Hot Water Heat Units SLHSteam Heat Units SSH SSHG-90Through 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Exhaust Fan Motor Supply Fan Motor FLA ea HorsepowerCondenser Fans Total FLA FLABlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation = Current of the Largest Motor Compressor or FAN Motor Single Source Power 380V, 415V, 460V,Load Definitions Load On the NextDual Source Power units 200V Power Wire Sizing and Protection Device EquationsDisconnect Switch Sizing DSS MCA = 1.25 x Load MOP = 1.25 x LoadInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Variable Air Volume System Controls Constant Volume or Variable Air Volume System ControlsPressurize DepressurizePurge FireRefer to Wiring Notes on 16A16B Page 17A 17B VAV Setpoint Input VoltageTable of Contents Cooling Sequence of Operation Sequence of OperationUnit Start-Up Gas Heating Sequence of OperationFenwal Ignition System Propane GasFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance Service Test Guide for Component Operation IGVSupply FAN Verifying Proper Fan Rotation System Airflow Measurements Constant Volume SystemsRotating Components If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems Optional with all Units Exhaust Airflow MeasurementTraqTM Sensor Airflow Measurement Optional with all units equipped with an economizer20 & 25 Ton Supply Fan Performance without Inlet Guide Vanes Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM Through 75 Ton Component Static Pressure Drops Inches W.C AIRAIR STDCFM RPM BHP 10,000 HF-C20 000HF-C25 000 HF-C30 000RPM BHP BHP RPM BHP RPM BHP AIR RPM BHPExhaust Air Dampers Economizer Damper AdjustmentTo Adjust the Fresh Air Damper Travel Fresh Air & Return Air Damper OperationConfiguration Damper Travel Adjustment PositionConnecting Rod Crank Arm Hole Ton UnitsAll Systems Fresh Air & Return Air Linkage AdjustmentCompressor Start-Up 70 & 105 TonAt Shutdown Compressor Operational SoundsRefrigerant Charging At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Electric, Steam and Hot Water Start-Up Gas Furnace Start-UpLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only High-Fire AdjustmentCombustion Air Adjustment O2 Two Stage Gas FurnaceFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Unit Start-Up Final Unit Checkout Typical Gas FurnaceService & Maintenance Service & Maintenance Unit Internal Fuse Replacement Data & VFD Factory SettingsWet Heat Coil Fin Data Total Coil Fins Unit Model Box-type Note QtyQty Size of each Model TypeService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Coil Cleaning Heating SeasonContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Warranty and Liability Clause Equipment Damage From Ultraviolet UV Lights115 116