Trane RT-SVX10C-EN specifications Constant Volume CV Units

Page 10

Low Ambient Compressor Lockout

Utilizes an analog input device for CV & VAV applications. When the system is configured for low ambient compressor lockout, the compressors are not allowed to operate if the temperature of the outside air falls below the lockout set- point. When the temperature rises 5 F above the lockout setpoint, the compressors are allowed to operate. The set- point for units without the low ambient option is 50 F. For units with the low ambient option, the setpoint is 0 F. The setpoints are adjustable at the Human Interface inside the unit control panel.

Space Pressure Transducer (3U62)

Is an analog input device used on CV & VAV applications with the Statitrac option. It modulates the exhaust dampers to keep the space pressure within the building to a cus- tomer designated controlband. It is mounted in the filter section just above the exhaust damper actuator and is con- nected to the ECEM (1U52). Field supplied pneumatic tub- ing must be connected between the space being controlled and the transducer assembly.

Transducer Voltage Output vs Pressure Input

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

 

 

 

 

 

 

 

 

 

 

Volts

2.5

 

 

 

 

 

 

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

-0.5

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

 

 

 

 

 

Pressure (inches w.c.)

 

 

 

Morning Warm-Up - Zone Heat

When a system changes from an unoccupied to an occu- pied mode, or switches from STOPPED to AUTO, or power is applied to a unit with the MWU option, the heater in the unit or external heat will be brought on if the space tem- perature is below the MWU setpoint. The heat will remain on until the temperature reaches the MWU setpoint. If the unit is VAV, then the VAV box/unocc relay will continue to stay in the unoccupied position and the VFD/IGV output will stay at 100% during the MWU mode. When the MWU setpoint is reached and the heat mode is terminated, then the VAV box/unocc relay will switch to the occupied mode and the VFD/IGV output will be controlled by the duct static pressure. During Full Capacity MWU the economizer damper is held closed for as long as it takes to reach setpoint. During Cycling Capacity MWU the economizer damper is allowed to go to minimum position after one hour of operation if setpoint has not been reached.

Compressor Motor Winding Thermostats (2B7S1, 2B17S2, 2B27S5, 2B8S3, 2B18S4 & 2B28S6)

A thermostat is embedded in the motor windings of each Scroll compressor. Each thermostat is designed to open if the motor windings exceeds approximately 221 F. The ther- mostat will reset automatically when the winding tempera- ture decreases to approximately 181 F. Rapid cycling, loss of charge, abnormally high suction temperatures, or the compressor running backwards could cause the thermostat to open. During a request for compressor operation, if the Compressor Module (SCM) detects a problem outside of it's normal parameters, it turns any operating

General Information (Continued)

compressor(s) on that circuit "Off", locks out all compressor operation for that circuit, and initiates a manual reset diag- nostic.

Supply Air Temperature Low Limit

Uses the supply air temperature sensor input to modulate the economizer damper to minimum position in the event the supply air temperature falls below the occupied heating setpoint temperature.

Freezestat (4S12)

Is a binary input device used on CV & VAV units with Hy- dronic Heat. It is mounted in the heat section and con- nected to the Heat Module (1U50). If the temperature of the air entering the heating coil falls to 40 F, the normally open contacts on the freezestat closes signalling the Heat Mod- ule (1U50) and the Rooftop Module (RTM) to:

a. drive the Hydronic Heat Actuator (4U15) to the full open position.

b. turn the supply fan "Off".

c. closes the outside air damper;

d. turns "On" the SERVICE light at the Remote Panel. e. initiates a "Freezestat" diagnostic to the Human

Interface.

High Duct Temp Thermostats (Optional 3S16, 3S17) Are binary input devices used on CV & VAV applications with a Trane Communication Interface Module (TCI). They provide "high limit" shutdown of the unit and requires a manual reset. They are factory set to open if the supply air temperature reaches 240 F, or the return air temperature reaches 135 F. Once tripped, the thermostat can be reset by pressing the button located on the sensor once the air temperature has decreased approximately 25 F below the cutout point.

Compressor Circuit Breakers (1CB8, 1CB9, 1CB10, 1CB11 & 1CB14, 1CB15, 1CB16, 1CB17)

The Scroll Compressors are protected by circuit breakers which interrupt the power supply to the compressors if the current exceeds the breakers “must trip” value. During a re- quest for compressor operation, if the Compressor Module (SCM) detects a problem outside of it's normal parameters, it turns any operating compressor(s) on that circuit "Off", locks out all compressor operation for that circuit, and ini- tiates a manual reset diagnostic.

Constant Volume (CV) Units

Zone Temperature - Cooling

Relies on input from a sensor located directly in the space, while a system is in the occupied "Cooling" mode. It modu- lates the economizer (if equipped) and/or stages the me- chanical cooling "On and Off" as required to maintain the zone temperature to within the cooling setpoint deadband.

Zone Temperature - Heating

Relies on input from a sensor located directly in the space, while a system is in the occupied "Heating" mode or an un- occupied period, to stage the heat "on and off" or to modu- late the heating valve (hydronic heat only) as required to maintain the zone temperature to within the heating setpoint deadband. The supply fan will be requested to operate any time there is a requested for heat. On gas heat units, the fan will continue to run for 60 seconds after the furnace is turned off.

Supply Air Tempering

On CV units equipped with staged heat, if the supply air temperature falls 10 F below the occupied heating setpoint temperature while the heater is "Off", the first stage of heat will be turned "On". The heater is turned "Off" when the sup- ply air temperature reaches 10 F above the occupied heat- ing setpoint temperature.

10

Image 10
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Literature Change History Overview of ManualTable of Contents General Information Model Number DescriptionDigit 3 Unit Airflow General Information Commonly Used Acronyms Fiberglass WoolHazard Identification Unit DescriptionGeneral Information Supply AIRVentilation Control Module VCM Design special option only CFMLead-Lag Constant Volume CV Units Variable Air Volume VAV Units Unit Component Layout and Shipwith LocationsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents Unit Inspection As soon as the unit arrives at the job site Unit Dimensions & Weight InformationNo Step Surface StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Base Dimensional Data Dimensions InstallationUnit Dimensional Data Dimensions Size Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Electrical Entrance Data Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeUnit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Slhf SahfSehf SshfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Heavy Objects Installation Unit Rigging & PlacementIf a Trane Curb Accessory Kit is not used Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section General Unit Requirements Main Electrical Power RequirementsInstallation Field Installed Control Wiring Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Installation Sensor & Tubing Installation Units with StatitracTMHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH 1000 MBH Modulating 500 MBH 1000 MBH Flue Assembly InstallationFlue Assembly Hot Water Heat Units SLHSteam Heat Units SSH SSHG-90Through 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Exhaust Fan Motor Supply Fan Motor FLA ea HorsepowerCondenser Fans Total FLA FLABlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation = Current of the Largest Motor Compressor or FAN Motor Single Source Power 380V, 415V, 460V,Load Definitions Load On the NextDual Source Power units 200V Power Wire Sizing and Protection Device EquationsDisconnect Switch Sizing DSS MCA = 1.25 x Load MOP = 1.25 x LoadInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Variable Air Volume System Controls Constant Volume or Variable Air Volume System ControlsPressurize DepressurizePurge FireRefer to Wiring Notes on 16A16B Page 17A 17B VAV Setpoint Input VoltageTable of Contents Cooling Sequence of Operation Sequence of OperationUnit Start-Up Gas Heating Sequence of OperationFenwal Ignition System Propane GasFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance Service Test Guide for Component Operation IGVSupply FAN Verifying Proper Fan Rotation System Airflow Measurements Constant Volume SystemsRotating Components If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems Optional with all Units Exhaust Airflow MeasurementTraqTM Sensor Airflow Measurement Optional with all units equipped with an economizer20 & 25 Ton Supply Fan Performance without Inlet Guide Vanes Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM Through 75 Ton Component Static Pressure Drops Inches W.C AIRAIR STDCFM RPM BHP 10,000 HF-C20 000HF-C25 000 HF-C30 000RPM BHP BHP RPM BHP RPM BHP AIR RPM BHPExhaust Air Dampers Economizer Damper AdjustmentTo Adjust the Fresh Air Damper Travel Fresh Air & Return Air Damper OperationConfiguration Damper Travel Adjustment PositionConnecting Rod Crank Arm Hole Ton UnitsAll Systems Fresh Air & Return Air Linkage AdjustmentCompressor Start-Up 70 & 105 TonAt Shutdown Compressor Operational SoundsRefrigerant Charging At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Electric, Steam and Hot Water Start-Up Gas Furnace Start-UpLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only High-Fire AdjustmentCombustion Air Adjustment O2 Two Stage Gas FurnaceFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Unit Start-Up Final Unit Checkout Typical Gas FurnaceService & Maintenance Service & Maintenance Unit Internal Fuse Replacement Data & VFD Factory SettingsWet Heat Coil Fin Data Total Coil Fins Unit Model Box-type Note QtyQty Size of each Model TypeService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Coil Cleaning Heating SeasonContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Warranty and Liability Clause Equipment Damage From Ultraviolet UV Lights115 116