Trane RT-SVX10C-EN specifications Hazardous Voltage, Fan Belt Adjustment

Page 106

Fan Belt Adjustment

The supply fan belts and optional exhaust fan belts must be inspected periodically to assure proper unit operation.

Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length.

When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt ten- sion adjustment bolts on the motor mounting base.

Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated below; ad- just the belt tension as follows;

Service & Maintenance (Continued)

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvert- ently energized. Failure to disconnect power before ser- vicing could result in death or serious injury.

1.To determine the appropriate belt deflection;

a.Measure the center-to-center shaft distance (in inches) between the fan and motor sheaves.

b.Divide the distance measured in Step 1a by 64; the resulting value represents the amount of belt deflection that corresponds to the proper belt tension.

2.Set the large O-ring on the belt tension gauge at the de- flection value determined in Step 1b.

3.Set the small O-ring at zero on the force scale of the gauge plunger.

4.Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O- ring is even with the top of the next belt—-or even with a

straightedge placed across the fan and motor sheaves. Refer to Figure 5-1

.

5.Remove the belt tension gauge. The small O-ring now in- dicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) re- quired to give the needed deflection.

6.Compare the "force" scale reading (Step 5) with the ap- propriate “force” value listed in Figure 5-1. If the "force" reading is outside the range, readjust the belt tension.

Note: Actual belt deflection "force" must not exceed the maximum “force” value shown in Figure 5-1.

7.Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension will decrease rapidly until the new belts are “run in”.

104

Image 106
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Literature Change History Overview of ManualTable of Contents General Information Model Number DescriptionDigit 3 Unit Airflow General Information Commonly Used Acronyms Fiberglass WoolHazard Identification Unit DescriptionGeneral Information Supply AIRVentilation Control Module VCM Design special option only CFMLead-Lag Constant Volume CV Units Variable Air Volume VAV Units Unit Component Layout and Shipwith LocationsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents Unit Inspection As soon as the unit arrives at the job site Unit Dimensions & Weight InformationNo Step Surface StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Base Dimensional Data Dimensions InstallationUnit Dimensional Data Dimensions Size Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Electrical Entrance Data Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeUnit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Slhf SahfSehf SshfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Heavy Objects Installation Unit Rigging & PlacementIf a Trane Curb Accessory Kit is not used Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section General Unit Requirements Main Electrical Power RequirementsInstallation Field Installed Control Wiring Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Installation Sensor & Tubing Installation Units with StatitracTMHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH 1000 MBH Modulating 500 MBH 1000 MBH Flue Assembly InstallationFlue Assembly Hot Water Heat Units SLHSteam Heat Units SSH SSHG-90Through 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Exhaust Fan Motor Supply Fan Motor FLA ea HorsepowerCondenser Fans Total FLA FLABlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation = Current of the Largest Motor Compressor or FAN Motor Single Source Power 380V, 415V, 460V,Load Definitions Load On the NextDual Source Power units 200V Power Wire Sizing and Protection Device EquationsDisconnect Switch Sizing DSS MCA = 1.25 x Load MOP = 1.25 x LoadInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Variable Air Volume System Controls Constant Volume or Variable Air Volume System ControlsPressurize DepressurizePurge FireRefer to Wiring Notes on 16A16B Page 17A 17B VAV Setpoint Input VoltageTable of Contents Cooling Sequence of Operation Sequence of OperationUnit Start-Up Gas Heating Sequence of OperationFenwal Ignition System Propane GasFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance Service Test Guide for Component Operation IGVSupply FAN Verifying Proper Fan Rotation System Airflow Measurements Constant Volume SystemsRotating Components If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems Optional with all Units Exhaust Airflow MeasurementTraqTM Sensor Airflow Measurement Optional with all units equipped with an economizer20 & 25 Ton Supply Fan Performance without Inlet Guide Vanes Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM Through 75 Ton Component Static Pressure Drops Inches W.C AIRAIR STDCFM RPM BHP 10,000 HF-C20 000HF-C25 000 HF-C30 000RPM BHP BHP RPM BHP RPM BHP AIR RPM BHPExhaust Air Dampers Economizer Damper AdjustmentTo Adjust the Fresh Air Damper Travel Fresh Air & Return Air Damper OperationConfiguration Damper Travel Adjustment PositionConnecting Rod Crank Arm Hole Ton UnitsAll Systems Fresh Air & Return Air Linkage AdjustmentCompressor Start-Up 70 & 105 TonAt Shutdown Compressor Operational SoundsRefrigerant Charging At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Electric, Steam and Hot Water Start-Up Gas Furnace Start-UpLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only High-Fire AdjustmentCombustion Air Adjustment O2 Two Stage Gas FurnaceFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Unit Start-Up Final Unit Checkout Typical Gas FurnaceService & Maintenance Service & Maintenance Unit Internal Fuse Replacement Data & VFD Factory SettingsWet Heat Coil Fin Data Total Coil Fins Unit Model Box-type Note QtyQty Size of each Model TypeService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Coil Cleaning Heating SeasonContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Warranty and Liability Clause Equipment Damage From Ultraviolet UV Lights115 116