Trane RT-SVX10C-EN specifications Digit 3 Unit Airflow

Page 5

Sample Model No.:

S X H G - D 1 1 4 0 A

H

7

C G 8 D 1 0 0 1 AT,etc

Digit No.: 1 2 3 4 5 6 7 8 9 10

11

12

13 14 15 16 17 18 19 20 21+

Digit 1 - Unit Type

S = Self-Contained

Digit 2 - Unit Function(s) E = DX Cooling, Electric Heat

F = DX Cooling, Natural Gas Heat L = DX Cooling, Hot Water Heat S = DX Cooling, Steam Heat

X = DX Cooling, Extended Casings

Digit 3 - Unit Airflow

H = Single-Zone

Digit 4 - Development Sequence

G= Seventh

Digits 5, 6, 7 - Nominal Capacity

C90 = 90 Tons

D11 = 105 Tons

D12 = 115 Tons

D13 = 130 Tons

Digit 8 Power Supply

4 = 460/60/3 XL

5 = 575/60/3 XL E = 200/60/3 XL F = 230/60/3 XL

Digit 9 - Heating Capacity

0 = No Heat

H = High Heat - 2 Stage

J = Limited Modulating High Heat P = Full Modulating High Heat

Note: When the second digit calls for "E" (electric heat), the following values apply in the ninth digit: W=190 kw

Note: When the second digit calls for "L" or "S", one of the following valve size values must be in Digit 9:

High Heat Coil: 3 = 1.0", 4 = 1.25", 5 = 1.50", 6 = 2.0", 7 = 2.5"

Low Heat Coil: C = 1.0", D = 1.25", E = 1.50", F = 2.0", G = 2.5"

Digit 10 - Design Sequence

W = Disconnect Redesign

Note: Sequence may be any letter A thru Z, or any digit 1 thru 9.

Digit 11 - Exhaust Option

O = None

7 = 100%, 15 HP w/ Statitrac

8 = 100%, 20 HP w/ Statitrac

9 = 100%, 25 HP w/ Statitrac F = 50%, 15 HP

H = 100%, 30 HP w/ Statitrac J = 100%, 40 HP w/ Statitrac

K = 100%, 15 HP w/o Statitrac (CV Only) L = 100%, 20 HP w/o Statitrac (CV Only) M = 100%, 25 HP w/o Statitrac (CV Only) N = 100%, 30 HP w/o Statitrac (CV Only) P = 100%, 40 HP w/o Statitrac (CV Only)

Digit 12 - Exhaust Air Fan Drive

Digit 18 - Accessory Panel

0

= None

0 = None

5

= 500 RPM

A = BAYSENS008*

6

= 600 RPM

B = BAYSENS010*

7

= 700 RPM

C = BAYSENS013*

8

= 800 RPM

D = BAYSENS014*

 

 

E = BAYSENS019*

Digit 13 - Filter

F = BAYSENS020*

A = Throwaway

G = BAYSENS021*

C = High-Efficiency Throwaway

 

 

D = Bag with Prefilter

Digit 19 - Ambient Control

E = Cartridge with Prefilter

0 = Standard

F = Throwaway Filter Rack Less Filter

 

 

 

Media

Digit 20 - Agency Approval

G = Bag Filter Rack Less Filter Media

0 = None (UL Gas Heater See Note 1)

 

 

1 = UL

Digit 14 - Supply Air Fan HP

2 = CSA

C = 30 HP (2-15 HP)

Note: Includes UL classified gas

D = 40 HP (2-20 HP)

heating section only when second

E = 50 HP (2-25 HP)

digit of Model No. is a "F".

F = 60 HP (2-30 HP)

 

 

G = 80 HP (2-40 HP)

Digits 21 - 36 - Miscellaneous

 

 

21

A = Unit Disconnect Switch

Digit 15 - Supply Air Fan Drive

22

B = Hot Gas Bypass

A = 1000 RPM

23

C = Economizer Control

B = 1100 RPM

 

with Comparative Enthalpy

C = 1200 RPM

23

Z = Economizer Control

D = 1300 RPM

 

with Reference Enthalpy

E = 1400 RPM

23

W = Economizer Control w/Dry Bulb

F = 1500 RPM

23

0 = None W/O Economizer

G = 1600 RPM

24

E = Low-Leak Fresh Air Dampers

 

 

25

F = High Duct Temperature Thermostat

 

 

26

G = High Capacity Evaporator

Digit 16 - Fresh Air

 

Coil (90 - 105 Only)

D = 0-100% Economizer (Std.)

27

K = Generic BAS Module

 

 

28

L = High Efficiency Motors

Digit 17 - System Control

 

(Supply and Exhaust)

1

= Constand Volume Control

29

M = Remote Human Interface

2

= VAV Supply Air Temperature

30

N = Ventilation Override Module

 

Control without Inlet Guide Vanes

31

R = Extended Grease Lines

3

= VAV - Supply Air Temperature

32

T = Access Doors

 

Control with Inlet Guide Vanes

33

V = Inter-processor Communication

4

= Space Pressure Control with

 

Bridge

 

Exhaust VFD w/o Bypass

34

0 = No communication module

5

= Space Pressure Control with

34

Y = Trane Communication Interface Module

 

Exhaust and Bypass

34

7 = LonTalk® Communication Interface Module

6

= VAV Supply Air Temperature Control

35

0 = None

 

with VFD without Bypass

36

6 = Factory-Powered 15A GFI

7

= VAV Supply Air Temperature Control

 

Convenience Outlet

 

with VFD and Bypass

 

 

8

= Supply and Exhaust Fan with

 

 

 

VFD and without Bypass

 

 

9

= Supply and Exhaust Fan with

 

 

 

VFD and Bypass

 

 

Echelon, LON, LONWORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, Neuron, 3120, 3150, the Echelon logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, LonMaker, and LonPoint are trademarks of Echelon Corporation.

5

Image 5
Contents With 3-DTMScroll Compressors ModelsLater Design Sequence Overview of Manual Literature Change HistoryTable of Contents Model Number Description General InformationDigit 3 Unit Airflow Hazard Identification Fiberglass WoolGeneral Information Commonly Used Acronyms Unit DescriptionSupply AIR General InformationCFM Ventilation Control Module VCM Design special option onlyLead-Lag Constant Volume CV Units Unit Component Layout and Shipwith Locations Variable Air Volume VAV UnitsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents No Step Surface Unit Dimensions & Weight InformationUnit Inspection As soon as the unit arrives at the job site StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Dimensional Data Dimensions Size InstallationUnit Base Dimensional Data Dimensions Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeElectrical Entrance Data Unit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Sehf SahfSlhf SshfSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Roof Curb and DuctworkSE,SL If a Trane Curb Accessory Kit is not used Installation Unit Rigging & PlacementHeavy Objects Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section Installation Field Installed Control Wiring Main Electrical Power RequirementsGeneral Unit Requirements Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Units with StatitracTM Installation Sensor & Tubing InstallationGas Heat Units SFH Connecting the Gas Supply Line to the Furnace Gas TrainHazardous Gases and Flammable Vapors 350 MBH 850 MBH Flue Assembly Flue Assembly Installation1000 MBH Modulating 500 MBH 1000 MBH Hot Water Heat Units SLHSSHG-90 Steam Heat Units SSHThrough 130 Ton units Page Use Copper Conductors Only Hazardous VoltageLive Electrical Components Typical Field Power Wiring 20 thru 75 Ton Page Condenser Fans Total FLA Supply Fan Motor FLA ea HorsepowerExhaust Fan Motor FLAUnit Tonnage No. of Compressors Tonnage Type Designation CombustionBlower Motor Sfhf Only Load Definitions Load Single Source Power 380V, 415V, 460V,= Current of the Largest Motor Compressor or FAN Motor On the NextDisconnect Switch Sizing DSS Power Wire Sizing and Protection Device EquationsDual Source Power units 200V MCA = 1.25 x Load MOP = 1.25 x LoadConstant Volume System Controls Controls using 24 VACInstallation Controls using DC Analog Input/Outputs Constant Volume or Variable Air Volume System Controls Variable Air Volume System ControlsDepressurize PressurizeFire Purge16A Refer to Wiring Notes on16B Page 17A 17B Input Voltage VAV SetpointTable of Contents Sequence of Operation Cooling Sequence of OperationFenwal Ignition System Gas Heating Sequence of OperationUnit Start-Up Propane GasFull and Limited Modulating Gas Furnace Modulating Gas Sequence of OperationFlame Failure Freeze Protection Electric Heat Sequence of OperationUnit Start-Up Wet Heat Sequence of Operation Electrical Phasing Unit PowerCompressor Damage Voltage Imbalance Voltage Supply and Voltage ImbalanceVoltage Supply IGV Service Test Guide for Component OperationSupply FAN Rotating Components System Airflow Measurements Constant Volume SystemsVerifying Proper Fan Rotation If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems TraqTM Sensor Airflow Measurement Exhaust Airflow MeasurementOptional with all Units Optional with all units equipped with an economizerTon Supply Fan Performance without Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop Ton Supply Fan Performance with Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM AIR Through 75 Ton Component Static Pressure Drops Inches W.CCFM RPM BHP STDAIR HF-C25 000 HF-C20 00010,000 HF-C30 000AIR RPM BHP RPM BHP BHP RPM BHP RPM BHPTo Adjust the Fresh Air Damper Travel Economizer Damper AdjustmentExhaust Air Dampers Fresh Air & Return Air Damper OperationConnecting Rod Crank Arm Hole Damper Travel Adjustment PositionConfiguration Ton UnitsCompressor Start-Up Fresh Air & Return Air Linkage AdjustmentAll Systems 70 & 105 TonRefrigerant Charging Compressor Operational SoundsAt Shutdown At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Low Ambient Dampers Thermostatic Expansion ValvesCharging by Subcooling Gas Furnace Start-Up Electric, Steam and Hot Water Start-UpCombustion Air Adjustment O2 High-Fire AdjustmentLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only Two Stage Gas FurnaceCO2 Pressure MBHFiring Manifold Unit control Full Modulating Gas FurnaceHeat Exchanger Modulating Gas Regulator Legend Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Typical Gas Furnace Unit Start-Up Final Unit CheckoutService & Maintenance Unit Internal Fuse Replacement Data & VFD Factory Settings Service & MaintenanceQty Size of each Unit Model Box-type Note QtyWet Heat Coil Fin Data Total Coil Fins Model TypeService & Maintenance Fan Belt Adjustment Gripbelts Gripnotch Cross Small P.D Section Range Min Max Scroll Compressor ReplacementSuction Line Filter/Drier Installation Supply and Exhaust Fan VFD Programming Parameters Hazardous Voltage! w/CapacitorsVFD Programming Parameters Cooling Season Service & Maintenance Monthly MaintenanceFilters Heating Season Coil CleaningSteam or Hot Water Coils Coil CleanersContains Refrigerant Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Equipment Damage From Ultraviolet UV Lights Warranty and Liability Clause115 116