Lead/Lag Operation
When Lead/Lag is enabled, each time the system cycles af- ter having stages 1 and 2 "On", "Stage 2" (K11 on SCM or K3 on MCM) and the corresponding condenser fan output "2A" will start first. The compressor module cycles the compressors "On" and "Off" to keep the zone temperature within the cooling setpoint deadband. The condenser fans are cycled "On" and "Off" to maintain the saturated refriger- ant temperature within the specified controlband.
Units equipped with 100% modulating exhaust
The exhaust dampers are controlled through an Exhaust/ Comparative Enthalpy Module (ECEM). The ECE module receives input form a space transducer and modulates the exhaust dampers to maintain the space pressure to within the specified setpoint controlband.
Gas Heating Sequence of Operation
Standard Two Stage Gas Furnace
The control system for the rooftop units are wired to ensure that the heating and cooling do not occur simultaneously. Refer to the wiring diagram that shipped with the unit while reviewing the following sequence of operation.
Fenwal Ignition System
(235 & 350 MBH Natural Gas)
When a heating requirement exists, the Rooftop Module (RTM) starts the supply fan and sends a request for heat to the Heat Module. The Heat Module closes K11 contacts and starts the combustion blower motor (4B11). The com- bustion blower motor starts on low speed through the nor- mally closed combustion fan relay (4K33) contacts. The heat module also closes K12 contacts. Power is then sup- plied through the supply air flow switch (4S38), the com- bustion air flow switch (4S25), the high limit cutout (4S26), and finally through the normally closed sequencing time delay (4DL6) contacts to the
The ignition electrode (4E1) will spark continuously for 4.7 seconds in an attempt to establish a flame. The flame is proven by the flame rod (4U19). The system will operate in the low heat mode until there is an additional call for heat established by closing the K1 contacts on the Heat Mod- ule.
The 60 second sequencing time delay relay (4DL6) will energize the combustion blower relay (4K33) which switches the combustion blower motor to high speed and energizes the 2nd stage solenoid on the gas valve (4L15).
Unit Start-Up (Continued)
If the flame rod (4U19) does not detect a flame at the time of an initial call for heat or detects a loss of flame during operation, it will
(4U18) will lockout automatically. If a flame failure occurs prior to the sequencing time delay relay (4DL6) opening its contacts which
Once the heating demand has been satisfied, the combus- tion blower motor and the ignition control board is
Propane Gas
Units that operate on propane gas have one additional con- trol that affects the combustion blower motor operation when a heating demand has been initiated or satisfied. The post purge time delay relay (4DL4) is installed which delays the starting of the combustion blower by approxi- mately 60 seconds. Once it has timed out, the combustion blower motor will start, closing the combustion air flow switch (4S25). The ignition sequence will follow the same sequence from the combustion airflow switch (4S25) to the subsequent controls as a natural gas system.
Once the heating demand has been satisfied, the Fenwal ignition control board (4U18) and the post purge time delay relay (4DL4) is
Honeywell Ignition System
(500 & 850 MBH Natural Gas)
When a heating requirement exists, the Rooftop Module (RTM) starts the supply fan and sends a request for heat to the Heat Module. The Heat Module closes K1 contacts and starts the combustion blower motor (4B11). The combustion blower motor starts on low speed through the normally closed combustion blower relay (4K33) contacts.
The supply airflow switch (4S38) and the combustion air switch (4S25) closes. Power is applied through the high limit cutout (4S26) to the Honeywell ignition control board (4U18). The ignition control board (4U18) starts a
56