Trane RT-SVX10C-EN specifications Compressor Damage, Electrical Phasing, Unit Power

Page 61

Use the checklist provided below in conjunction with the “General Unit Requirement" checklist” to ensure that the unit is properly installed and ready for operation. Be sure to complete all of the procedures described in this section be- fore starting the unit for the first time.

[ ] Turn the field supplied disconnect switch, located up- stream of the rooftop unit, to the "Off" position.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvert- ently energized. Failure to disconnect power before ser- vicing could result in death or serious injury.

[ ] Turn the 115 volt control circuit switch 1S1 to the "Off" position. It is located in the secondary of the 1T1 trans- former.

[ ] Turn the 24 volt control circuit switch 1S70 to the "Off" position. It is located in the secondary of the 1T2 & 1T3 transformers.

[ ] Turn the "System" selection switch (at the Remote Panel) to the "Off" position and the "Fan" selection switch (if Applicable) to the "Auto" or "Off" position.

[ ] Check all electrical connections for tightness and "point of termination" accuracy.

[ ] Verify that the condenser airflow will be unobstructed.

[ ] Check the compressor crankcase oil level. Oil should be visible in the compressor oil sight glass. The oil level should be 1/2 to 3/4 high in the sight glass with the com- pressor "Off".

[ ] Verify that the compressor discharge service valve and the liquid line service valve is back seated on each cir- cuit.

CAUTION

Compressor Damage!

Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines may result in compressor damage.

Compressor service valves must be fully opened before start-up (suction, discharge, liquid line, and oil line).

Do not start the unit in the cooling mode if the ambient tem- perature is below the following minimum recommended op- erating temperatures:

Standard unit with or without HGBP - +55 F for 20 & 40 Ton

+50 F for 25 & 30 Ton

+45 F for 70 thru 130 Ton

+40 F for 55 Ton

+35 F for 50 Ton

+30 F for 60 Ton

Unit Start-Up (Continued)

Units with Low Ambient option without HGBP - 0 F

Units with Low Ambient option with HGBP - +10 F

Note: To prevent compressor damage due to no refrigerant flow, do not pump the system down with the compressor(s) below 7 PSIG under any circumstance.

[ ] Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the Service/Maintenance section of this manual for in- structions.

[ ] Inspect the interior of the unit for tools and debris. Install all panels in preparation for starting the unit.

Electrical Phasing

Unlike traditional reciprocating compressors, scroll com- pressors are phase sensitive. Proper phasing of the electri- cal supply to the unit is critical for proper operation and reli- ability.

The compressor motor is internally connected for clockwise rotation with the incoming power supply phased as

A, B, C.

Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instru- ment such as an Associated Research Model 45 Phase Se- quence Indicator and following the steps below:

[ ] Turn the field supplied disconnect switch that provides power to terminal block 1TB1 or to the unit mounted dis- connect switch 1S14 to the "Off" position.

[ ] Connect the phase sequence indicator leads to the ter- minal block or unit mounted disconnect switch as fol- lows;

Phase Sequence

Unit Power

Leads

Terminal

Black (phase A)

L1

Red (phase B)

L2

Yellow (Phase C)

L3

[ ] Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote discon- nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvert- ently energized. Failure to disconnect power before ser- vicing could result in death or serious injury.

HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT SWITCH 1S14.

59

Image 61
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Overview of Manual Literature Change HistoryTable of Contents Model Number Description General InformationDigit 3 Unit Airflow Hazard Identification Fiberglass WoolGeneral Information Commonly Used Acronyms Unit DescriptionSupply AIR General InformationCFM Ventilation Control Module VCM Design special option onlyLead-Lag Constant Volume CV Units Unit Component Layout and Shipwith Locations Variable Air Volume VAV UnitsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents No Step Surface Unit Dimensions & Weight InformationUnit Inspection As soon as the unit arrives at the job site StoragePage Sahf Cooling-Only Units 20 thru 75 Ton Unit Dimensional Data Dimensions Size InstallationUnit Base Dimensional Data Dimensions Electrical Entrance Data Unit DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Dimensions Size Unit Base Dimensional Data Dimensions SizeElectrical Entrance Data Unit Dimensions Size Unit Size Furnace Dimensions Note Size/MBH Length HeightSHG Cooling & Heating Units 90 through 130 Ton Sehf SahfSlhf SshfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G If a Trane Curb Accessory Kit is not used Installation Unit Rigging & PlacementHeavy Objects Pitch Pocket LocationTypical Unit Rigging Unit Base & Roof Curb Section Installation Field Installed Control Wiring Main Electrical Power RequirementsGeneral Unit Requirements Requirements for Electric Heat UnitsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Units with StatitracTM Installation Sensor & Tubing InstallationHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH Flue Assembly Flue Assembly Installation1000 MBH Modulating 500 MBH 1000 MBH Hot Water Heat Units SLHSSHG-90 Steam Heat Units SSHThrough 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page Condenser Fans Total FLA Supply Fan Motor FLA ea HorsepowerExhaust Fan Motor FLABlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation Load Definitions Load Single Source Power 380V, 415V, 460V,= Current of the Largest Motor Compressor or FAN Motor On the NextDisconnect Switch Sizing DSS Power Wire Sizing and Protection Device EquationsDual Source Power units 200V MCA = 1.25 x Load MOP = 1.25 x LoadInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Constant Volume or Variable Air Volume System Controls Variable Air Volume System ControlsDepressurize PressurizeFire Purge16A Refer to Wiring Notes on16B Page 17A 17B Input Voltage VAV SetpointTable of Contents Sequence of Operation Cooling Sequence of OperationFenwal Ignition System Gas Heating Sequence of OperationUnit Start-Up Propane GasFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance IGV Service Test Guide for Component OperationSupply FAN Rotating Components System Airflow Measurements Constant Volume SystemsVerifying Proper Fan Rotation If all of the fans are rotating backwardsCondenser Fan Location with Human Interface Designator Variable Air Volume Systems TraqTM Sensor Airflow Measurement Exhaust Airflow MeasurementOptional with all Units Optional with all units equipped with an economizerTon Supply Fan Performance without Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop Ton Supply Fan Performance with Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM AIR Through 75 Ton Component Static Pressure Drops Inches W.CAIR STDCFM RPM BHP HF-C25 000 HF-C20 00010,000 HF-C30 000AIR RPM BHP RPM BHP BHP RPM BHP RPM BHPTo Adjust the Fresh Air Damper Travel Economizer Damper AdjustmentExhaust Air Dampers Fresh Air & Return Air Damper OperationConnecting Rod Crank Arm Hole Damper Travel Adjustment PositionConfiguration Ton UnitsCompressor Start-Up Fresh Air & Return Air Linkage AdjustmentAll Systems 70 & 105 TonRefrigerant Charging Compressor Operational SoundsAt Shutdown At Low Ambient Start-UpCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Gas Furnace Start-Up Electric, Steam and Hot Water Start-UpCombustion Air Adjustment O2 High-Fire AdjustmentLow-Fire Adjustment 500 MBH, 850 & 1,000 MBH only Two Stage Gas FurnaceFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Typical Gas Furnace Unit Start-Up Final Unit CheckoutService & Maintenance Unit Internal Fuse Replacement Data & VFD Factory Settings Service & MaintenanceQty Size of each Unit Model Box-type Note QtyWet Heat Coil Fin Data Total Coil Fins Model TypeService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Heating Season Coil CleaningContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Equipment Damage From Ultraviolet UV Lights Warranty and Liability Clause115 116