Trane RT-SVX10C-EN specifications General Information, Supply AIR

Page 7

Rooftop Module (RTM - 1U48 Standard on all units) The Rooftop Module (RTM) responds to cooling, heating, and ventilation requests by energizing the proper unit com- ponents based on information received from other unit mod- ules, sensors, remote panels, and customer supplied bi- nary inputs. It initiates supply fan, exhaust fan, exhaust damper, inlet guide vane positioning or variable frequency drive output, and economizer operation based on that in- formation.

RTM Resistance Input vs Setpoint Temperatures

RTM cooling or

RTM cooling

 

 

heating

setpoint input

 

 

setpoint input

used as the

Resistance

used as the

source for

(Ohms) Max.

source for a

SUPPLY AIR

Tolerance 5%

ZONE temp

temp setpoint

 

 

setpoint (oF)

cooling (oF)

 

 

40

40

1084

 

45

45

992

 

50

50

899

 

55

55

796

 

60

60

695

 

65

65

597

 

70

70

500

 

75

75

403

 

80

80

305

 

n/a

85

208

 

n/a

90

111

 

RTM Resistance Value vs System Operating Mode

Resistance

 

 

 

applied to RTM

 

 

 

MODE input

Constant Volume Units

 

Terminals (Ohms)

 

 

 

Max. Tolerance

Fan

System

 

5%

Mode

Mode

 

2320

Auto

Off

 

4870

Auto

Cool

 

7680

Auto

Auto

 

10770

On

Off

 

13320

On

Cool

 

16130

On

Auto

 

19480

Auto

Heat

 

27930

On

Heat

 

Compressor Module (SCM & MCM - 1U49 standard on all units)

The Compressor module, (Single Circuit & Multiple Circuit), upon receiving a request for mechanical cooling, energizes the appropriate compressors and condenser fans. It moni- tors the compressor operation through feedback information it receives from various protection devices.

Human Interface Module (HI - 1U65 standard on all units)

The Human Interface module enables the operator to adjust the operating parameters for the unit using it's 16 key key- pad. The 2 line, 40 character LCD screen provides status information for the various unit functions as well as menus for the operator to set or modify the operating parameters.

Heat Module (1U50 used on heating units)

The Heat module, upon receiving a request for Heating, en- ergizes the appropriate heating stages or strokes the Modu- lating Heating valve as required.

General Information (Continued)

Ventilation Override Module (VOM - Optional 1U51) The Ventilation Override module initiates specified func- tions such as; space pressurization, exhaust, purge, purge with duct pressure control, and unit off when any one of the five (5) binary inputs to the module are activated. The com- pressors and condenser fans are disabled during the ven- tilation operation. If more than one ventilation sequence is activated, the one with the highest priority is initiated.

Interprocessor Communications Board (IPCB - Optional 1U55 used with the Optional Remote Human Interface)

The Interprocessor Communication Board expands commu- nications from the rooftop unit UCM network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for this application should be; Switches 1 and 2 "Off", Switch 3 "On".

Trane Communications Interface Module (TCI - Optional 1U54 used on units with Trane ICSTM )

The Trane Communication Interface module expands com- munications from the unit UCM network to a Trane Tracer 100TM or a Tracer SummitTM system and allows external setpoint adjustment and monitoring of status and diagnos- tics. DIP Switch settings on the TCI

module for these applications should be:

Tracer 100 (Comm3): Switches 1, 2, and 3 are "Off";

Tracer Summit (Comm4): Switch 1 is "On", switches 2, and 3 are "Off"

Lontalk Communication Interface Module (LCI - Optional 1U54 - used on units with Trane ICSTM or 3rd party Build- ing AutomationSystems)

The LonTalk Communication Interface module expands communications from the unit UCM network to a Trane Tracer SummitTM or a 3rd party building automation system, utilizing LonTalk, and allows external setpoint and configu- ration adjustment and monitoring of status and diagnostics.

Exhaust/Comparative Enthalpy Module (ECEM - Optional 1U52 used on units with Statitrac and/or comparative enthalpy options)

The Exhaust/Comparative Enthalpy module receives infor- mation from the return air humidity sensor, the outside air humidity sensor, and the return air temperature sensor to utilize the lowest possible humidity level when considering economizer operation. In addition, it receives space pres- sure information which is used to maintain the space pres- sure to within the setpoint controlband. Refer to the table below for the Humidity vs Voltage input values.

7

Image 7
Contents Later Design Sequence ModelsWith 3-DTMScroll Compressors Overview of Manual Literature Change HistoryTable of Contents Model Number Description General InformationDigit 3 Unit Airflow Unit Description Fiberglass WoolHazard Identification General Information Commonly Used AcronymsSupply AIR General InformationCFM Ventilation Control Module VCM Design special option onlyLead-Lag Constant Volume CV Units Unit Component Layout and Shipwith Locations Variable Air Volume VAV UnitsGeneral Information Space Temperature Averaging Control Module Locations for SHF 40, 60, 70 & 75 Ton Units Table of Contents Storage Unit Dimensions & Weight InformationNo Step Surface Unit Inspection As soon as the unit arrives at the job sitePage Sahf Cooling-Only Units 20 thru 75 Ton Electrical Entrance Data Unit Dimensions InstallationUnit Dimensional Data Dimensions Size Unit Base Dimensional Data DimensionsSEHF, SFHF, SLHF, SSHF, Sxhf Units 20 thru 75 Ton Unit Size Furnace Dimensions Note Size/MBH Length Height Unit Base Dimensional Data Dimensions SizeUnit Dimensions Size Electrical Entrance Data Unit Dimensions SizeSHG Cooling & Heating Units 90 through 130 Ton Sshf SahfSehf SlhfSE,SL Roof Curb and DuctworkSahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G Pitch Pocket Location Installation Unit Rigging & PlacementIf a Trane Curb Accessory Kit is not used Heavy ObjectsTypical Unit Rigging Unit Base & Roof Curb Section Requirements for Electric Heat Units Main Electrical Power RequirementsInstallation Field Installed Control Wiring General Unit RequirementsInstallation Condensate Drain Connections Page Removing Supply and Exhaust Fan Shipping Channels Motors 5Hp Page Units with StatitracTM Installation Sensor & Tubing InstallationHazardous Gases and Flammable Vapors Connecting the Gas Supply Line to the Furnace Gas TrainGas Heat Units SFH 350 MBH 850 MBH Hot Water Heat Units SLH Flue Assembly InstallationFlue Assembly 1000 MBH Modulating 500 MBH 1000 MBHSSHG-90 Steam Heat Units SSHThrough 130 Ton units Page Live Electrical Components Hazardous VoltageUse Copper Conductors Only Typical Field Power Wiring 20 thru 75 Ton Page FLA Supply Fan Motor FLA ea HorsepowerCondenser Fans Total FLA Exhaust Fan MotorBlower Motor Sfhf Only CombustionUnit Tonnage No. of Compressors Tonnage Type Designation On the Next Single Source Power 380V, 415V, 460V,Load Definitions Load = Current of the Largest Motor Compressor or FAN MotorMCA = 1.25 x Load MOP = 1.25 x Load Power Wire Sizing and Protection Device EquationsDisconnect Switch Sizing DSS Dual Source Power units 200VInstallation Controls using DC Analog Input/Outputs Controls using 24 VACConstant Volume System Controls Constant Volume or Variable Air Volume System Controls Variable Air Volume System ControlsDepressurize PressurizeFire Purge16A Refer to Wiring Notes on16B Page 17A 17B Input Voltage VAV SetpointTable of Contents Sequence of Operation Cooling Sequence of OperationPropane Gas Gas Heating Sequence of OperationFenwal Ignition System Unit Start-UpFlame Failure Modulating Gas Sequence of OperationFull and Limited Modulating Gas Furnace Unit Start-Up Wet Heat Sequence of Operation Electric Heat Sequence of OperationFreeze Protection Compressor Damage Unit PowerElectrical Phasing Voltage Supply Voltage Supply and Voltage ImbalanceVoltage Imbalance IGV Service Test Guide for Component OperationSupply FAN If all of the fans are rotating backwards System Airflow Measurements Constant Volume SystemsRotating Components Verifying Proper Fan RotationCondenser Fan Location with Human Interface Designator Variable Air Volume Systems Optional with all units equipped with an economizer Exhaust Airflow MeasurementTraqTM Sensor Airflow Measurement Optional with all UnitsTon Supply Fan Performance without Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance without Inlet Guide VanesWocfm 1200 RPM 40 HP 40% 300 RP Standard Evaporator Coil 20000 30000 40000 50000 60000 Drop Ton Supply Fan Performance with Inlet Guide Vanes 20 & 25 Ton Supply Fan Performance with Inlet Guide Vanes15 HP 900 RPM 80% 10 HP RPM AIR Through 75 Ton Component Static Pressure Drops Inches W.CAIR STDCFM RPM BHP HF-C30 000 HF-C20 000HF-C25 000 10,000AIR RPM BHP RPM BHP BHP RPM BHP RPM BHPFresh Air & Return Air Damper Operation Economizer Damper AdjustmentTo Adjust the Fresh Air Damper Travel Exhaust Air DampersTon Units Damper Travel Adjustment PositionConnecting Rod Crank Arm Hole Configuration70 & 105 Ton Fresh Air & Return Air Linkage AdjustmentCompressor Start-Up All SystemsAt Low Ambient Start-Up Compressor Operational SoundsRefrigerant Charging At ShutdownCompressor Locations Cooling Cycle Pressure Curve 340 320 Full Load 380 360 340 OD Ambient Full Load 380 360 340 OD Ambient 320 240 220 380 360 OD Ambient Charging by Subcooling Thermostatic Expansion ValvesLow Ambient Dampers Gas Furnace Start-Up Electric, Steam and Hot Water Start-UpTwo Stage Gas Furnace High-Fire AdjustmentCombustion Air Adjustment O2 Low-Fire Adjustment 500 MBH, 850 & 1,000 MBH onlyFiring Manifold MBHCO2 Pressure Heat Exchanger Full Modulating Gas FurnaceUnit control Modulating Gas Regulator Limited Modulating Gas Furnace Unit Start-UpModulating Gas Regulator Legend Typical Gas Furnace Unit Start-Up Final Unit CheckoutService & Maintenance Unit Internal Fuse Replacement Data & VFD Factory Settings Service & MaintenanceModel Type Unit Model Box-type Note QtyQty Size of each Wet Heat Coil Fin Data Total Coil FinsService & Maintenance Fan Belt Adjustment Suction Line Filter/Drier Installation Scroll Compressor ReplacementGripbelts Gripnotch Cross Small P.D Section Range Min Max VFD Programming Parameters Hazardous Voltage! w/CapacitorsSupply and Exhaust Fan VFD Programming Parameters Filters Service & Maintenance Monthly MaintenanceCooling Season Heating Season Coil CleaningContains Refrigerant Coil CleanersSteam or Hot Water Coils Final Process Index See Figure Gate type valve 36-37 See -12 Figure See VOM Contacts -16 Figure Equipment Damage From Ultraviolet UV Lights Warranty and Liability Clause115 116