Honeywell 2-Partitioned Security System Zone Programming, SET to CONFIRM? = YES, Report Code

Page 11

Zone Programming

If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.

PROMPTEXPLANATION

ZONE PROG?

 

1 = YES 0 = NO

0

Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [] to display the next screen. Press # to display a previous screen.

SET TO CONFIRM?

 

1

= YES

0 = NO

0

 

 

 

 

 

 

 

ENTER ZONE NO.

 

 

00

= QUIT

 

 

10￿

 

 

 

 

 

Zone 10 entered

 

 

 

 

 

 

 

 

 

 

 

 

 

10 ZT

P

RC

In L

 

 

 

0 0

1

1 0

0 0

1

 

 

10 ZONE TYPE

PERIMETER03

Zone number 10 and Zone Type 03 entry shown

These are special zone types used with 5800 Series Wireless Pushbutton Units that result in arming the system in the STAY or AWAY mode, or disarming the system, depending on the selection made.

This prompt appears once upon entering Zone Programming Mode.

If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been entered later.

Enter the 2-digit zone number to be programmed, as follows:

Protection Zones = 01–64

System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97

Keypad Panic Zones = 95, 96, 99

Press [] to continue.

This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P = Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the sensor is connected.

Some devices can support more than one zone by means of individual loops (for example, 5801, 5804, 5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.

Press [] to continue.

Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. Refer to the Zone Type Definitions section in the ADEMCO VISTA-40 Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary). Available zone types are listed below.

00

= Assign for Unused Zones

08

= 24 Hr. Auxiliary

01

= Entry/Exit #1, Burglary

09

= Fire Without Verification

02

= Entry/Exit #2, Burglary

10

= Interior Delay, Burglary

03

= Perimeter, Burglary

20

= Arm–STAY†

04

= Interior Follower, Burglary

21

= Arm AWAY†

05

= Trouble Day/Alarm Night

22

= Disarm†

06

= 24

Hr. Silent Alarm

23

= No Alarm Response

07

= 24

Hr. Audible Alarm

 

(e.g., relay activation)

Press [] to continue.

10 Partition

1

Enter the partition number (1–2)you are assigning this zone to. Press [] to continue.

10 REPORT CODE

 

1st 03 2nd 12

3C

Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."

(Refer to the System Communication section in the Installation and Setup Guide for more information about report codes and reporting formats.)

Press [] to continue.

– 11 –

Image 11
Contents N7001PRV5 5/04 Rev a $0&29,67$Table of Contents Recommended Programming Procedure Field Group Program Field IndexField Group VISTA-40 Programming Form 59 *62 Alarm Report Codes & ID Digits for Zones Enable OPEN/CLOSE Report forOPEN/CLOSE Report for Keyswitch 54 *57 Alarm Report Codes & ID Digits for Zones2nd Page Programming Fields press *94 Fields 1*28 1*31 are not applicable for UL installations3rd Page Programming Fields press *94 2nd Page Fields Partition-Specific FieldsPartition # Program Fields 1st Page FieldsProgramming With #93 Menu Mode Zone Type PERIMETER03 Zone ProgrammingSET to CONFIRM? = YES Enter Zone no = QuitInput S/N Input TypeInput S/N AXXX-XXXX Xmit to Confirm Press to Skip Series Transmitters Loop DesignationsSET to CONFIRM? Expert Mode Zone ProgrammingProgram field 200 Number of Partitions Enter Zone noFrom Template Input S/N XXX-XXXXZone Type Template Loop Function Wireless Key Default Templates 58045804BD Template Loop FunctionExit Edit MODE? Zone DESCRIP? Default SCREEN? Custom WORD? Part DESCRIP?Zone Descriptors Select Zone Descriptor mode Alpha Descriptors ProgrammingSelect the next word Select Default Screen modeSelect Custom Word Mode Accept the wordSave the word by pressing Type the word using one of two methods as followsFollow the same procedure as for custom words Enter the custom word number 01-20 you want to createAlpha Descriptor Vocabulary Character Ascii ChartVIP Module Device ProgrammingAlpha Keypad RF ExpanderTrouble AlarmFault Relay ProgrammingRelay Action No Response Start Event Not Used Relay Output Devices ProgrammingChoices for Start/Stop Zone Types and System Operations Enter Relay #Unit Code Zone List ProgrammingStart Partn ANY Partition Relay Type Plex ECP Address Module RELAY# House CodeRelay Voice Descriptors Custom Word no =QUIT Enter Index # Custom Word Substitutes for VIP Module AnnunciationDescriptor Prim Partition # Char max Sub. # System Layout WorksheetsDefaults Access Codes & User Definitions for Partitions 1Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Input Types Zone Definitions for Keypad Panic Zones 95, 96Zone Definitions for System Zones 70, 88 89, 90, 91 Zone TypesChoices for System Operation are Relay Outputs WorksheetsPage Ground Ademco VISTA-40 Summary of ConnectionsEileen Way, Syosset, New York