Honeywell 2-Partitioned Security System manual VISTA-40 Programming Form

Page 5

VISTA-40 Programming Form

Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets.

*00

INSTALLER CODE

 

 

 

Enter 4 digits, 0-9 [4140]

 

 

 

 

*02

 

*05 RESPONSE TYPES FOR ZONES

 

 

 

 

 

 

 

 

 

 

 

Skip these fields. Use #93 Menu Mode, Zone

 

 

 

 

Programming to program the response types.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*09

ENTRY DELAY #1

[02]

 

 

 

 

 

 

 

 

 

 

 

00, 02-15 times 15 seconds

 

 

 

 

 

Maximum "03" for UL.

 

 

 

 

 

 

 

 

 

 

*10

EXIT DELAY #1

[03]

 

 

 

00, 03-15 times 15 seconds

 

 

 

 

 

Maximum "04" for UL installations.

 

 

 

 

 

 

 

 

 

 

*11

ENTRY DELAY #2

[06]

 

 

 

00, 02-15 times 15 seconds (must be longer than Entry Delay

 

#1). Maximum "03" for UL installations.

 

 

 

 

 

 

 

 

 

 

*12

EXIT DELAY #2

[08]

 

 

 

00, 03-15 times 15 seconds (must be longer than Exit Delay

 

#1). Maximum "04" for UL installations.

 

 

 

 

 

 

 

 

 

 

*13

ALARM SOUNDER DURATION

[04]

 

 

 

01-15 times 2 minutes. Must be minimum 16 minutes for UL

 

installations.

 

 

 

 

*14

ZONE 9 RESPONSE TIME

[0]

 

 

 

 

*25

BURG.TRIGGER FOR RESPONSE TYPE 8

[1]

 

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

 

 

 

 

*26

INTELLIGENT TEST REPORTING

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

1=yes (no report sent if any other report was recently sent);

 

 

0=no (send report at programmed interval, field *27)

 

 

 

 

 

Must be 0 for UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*27

TEST REPORT INTERVAL

 

 

 

[024]

 

 

 

Enter interval in hours, 001-199; 000=no report;

 

 

 

 

 

 

Max. 024 for UL installations.

 

 

 

 

 

 

 

 

 

 

 

*28

POWER UP IN PREVIOUS STATE

 

 

 

 

[1]

 

 

 

 

 

 

 

 

 

1=yes; 0=no; "1" for UL installations.

 

 

 

 

 

 

 

 

*29

QUICK ARM

 

 

 

 

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

 

 

1=yes; 0=no

 

 

 

 

 

 

 

 

 

 

 

*30

TOUCHTONE OR ROTARY DIAL

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

1=TouchTone; 0=rotary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*31

PABX ACCESS CODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00-09; B-F (11-15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*32

PRIM. SUBS. ACCT #

 

 

 

 

 

 

Enter 00-09; B-F (11-15) [15 15 15 15]

*33 PRIMARY PHONE NUMBER

Enter 1 for fast response time 10ms Enter 0 for normal response time 350ms. Must be 0 for UL installations.

*15

KEYSWITCH ASSIGNMENT

[0]

 

 

 

Enter partition in which keyswitch used,

 

 

 

 

1-2; 0=disable

 

 

 

*16

CONFIRMATION OF ARMING DING

[0]

 

 

 

 

 

1=enable; 0=disable.

 

 

 

 

Must be "1" for UL Installations.

 

 

 

*17

AC LOSS KEYPAD SOUNDING

[0]

 

 

 

 

 

1=yes; 0=no

 

 

 

*19

RANDOMIZE AC LOSS REPORT

[0]

 

 

 

 

1=10-40 min; 0=normal report (about 2 min. after AC loss).

Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause

*34 SECONDARY PHONE NUMBER

Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause

*35 DOWNLOAD PHONE NO.

*20 VIP MODULE PHONE CODE

 

Enter 01 - 09 for the first digit; enter

[00],

[11]

11 for “*” or 12 for “#” for the second digit.

 

 

 

Must be set to "0" for UL installations.

 

 

 

*21

PREVENT FIRE TIMEOUT

 

 

[0]

 

 

 

1=No timeout; 0=Timeout.

 

 

 

 

 

 

 

*22

KEYPAD PANIC ENABLES

[001]

 

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable

995

996 999

 

*23

MULTIPLE ALARMS

 

 

[1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=yes; 0=no

 

 

 

 

 

 

 

*24

IGNORE EXPANSION ZONE TAMPER

[0]

 

 

 

 

1=Ignore; 0=Enable tamper for RF and RPMs.

Must be "0" for UL installations if using these devices.

Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause

*36 DOWNLOAD ID NO.

 

 

 

 

 

 

 

Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]

*37 DOWNLOAD COMMAND ENABLES

0

Dlr ShtdwnSys ShtdwnNot UsedRmt BypRmt DisarmRmt ArmUpld PgmDwnld Pgm

See field 1*53 for Callback disable option; [1=enable]; 0=disable. For UL installations, all entries must be "0."

*38 PREVENT ZONE XX BYPASS

[00]

01-64; 00 if all zones can be bypassed

– 5 –

Image 5
Contents N7001PRV5 5/04 Rev a $0&29,67$Table of Contents Recommended Programming Procedure Field Group Program Field IndexField Group VISTA-40 Programming Form OPEN/CLOSE Report for Keyswitch Enable OPEN/CLOSE Report for54 *57 Alarm Report Codes & ID Digits for Zones 59 *62 Alarm Report Codes & ID Digits for Zones2nd Page Programming Fields press *94 Fields 1*28 1*31 are not applicable for UL installations3rd Page Programming Fields press *94 Partition # Program Fields Partition-Specific Fields1st Page Fields 2nd Page FieldsProgramming With #93 Menu Mode SET to CONFIRM? = YES Zone ProgrammingEnter Zone no = Quit Zone Type PERIMETER03Input S/N Input TypeInput S/N AXXX-XXXX Xmit to Confirm Press to Skip Series Transmitters Loop DesignationsProgram field 200 Number of Partitions Expert Mode Zone ProgrammingEnter Zone no SET to CONFIRM?From Template Input S/N XXX-XXXX5804BD Wireless Key Default Templates 5804Template Loop Function Zone Type Template Loop FunctionZone Descriptors Select Zone Descriptor mode Zone DESCRIP? Default SCREEN? Custom WORD? Part DESCRIP?Alpha Descriptors Programming Exit Edit MODE?Select Custom Word Mode Select Default Screen modeAccept the word Select the next wordFollow the same procedure as for custom words Type the word using one of two methods as followsEnter the custom word number 01-20 you want to create Save the word by pressingAlpha Descriptor Vocabulary Character Ascii ChartAlpha Keypad Device ProgrammingRF Expander VIP ModuleFault AlarmRelay Programming TroubleChoices for Start/Stop Zone Types and System Operations Relay Output Devices ProgrammingEnter Relay # Relay Action No Response Start Event Not UsedStart Partn ANY Partition Zone List ProgrammingRelay Type Plex ECP Address Module RELAY# House Code Unit CodeRelay Voice Descriptors Custom Word no =QUIT Enter Index # Custom Word Substitutes for VIP Module AnnunciationDescriptor Prim Partition # Char max Sub. # System Layout WorksheetsDefaults Access Codes & User Definitions for Partitions 1Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Zone Definitions for System Zones 70, 88 89, 90, 91 Zone Definitions for Keypad Panic Zones 95, 96Zone Types Input TypesChoices for System Operation are Relay Outputs WorksheetsPage Ground Ademco VISTA-40 Summary of ConnectionsEileen Way, Syosset, New York