Honeywell 2-Partitioned Security System, VISTA-40 manual Relay Outputs Worksheets

Page 33

Relay Outputs Worksheets

Applicable only if relays (4204) or X-10 devices are used.

￿Programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Notes: 1. For 4204 the Device Programming section must be programmed for the device address. Set the DIP switches on the device for that address.

RELAY DEV #

2.

A

For X-10 devices, use the 1361X10 transformer in place of the transformer that comes in the box with the control panel.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=4204

 

Dev Add 4204

 

Relay # for 4204

 

 

 

S

T A R T

 

S

 

T O P

 

Restrict

 

 

or House Code

 

or

 

 

 

 

 

 

 

2=X-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for X-10

 

Unit Code for X-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EV/ZL

 

 

ZT / P

 

ZL

 

ZT / P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

2.

3.

4.

5.

6.

7.

8.

A =

DEVICE ACTION

0

= No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off

EV =

EVENT

0

= Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore

ZL =

ZONE LIST

1-4, 0 = Not Used

 

 

 

 

NOTES: "START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device action starts.

 

"STOP" ZONE LIST:

Upon restore of ALL zones in this list, device action stops. It need not be same list as used for START.

ZT = ZONE TYPE/SYSTEM OPERATION

 

 

 

 

 

 

Choices for Zone Types are:

 

 

 

 

 

 

 

 

 

 

 

 

 

00=zone not used

 

05=day/night burglary

10=interior (delay)

 

 

 

01=entry/exit 1

 

 

06=24-hour silent

20=arm stay

 

 

 

02=entry/exit 2

 

 

07=24-hour audible

21=arm away

 

 

 

03=perimeter

 

 

08=24-hour auxiliary

22=disarm

 

 

 

04=interior (follower)

 

09=supervised fire

23=no alarm response

 

 

 

 

NOTE:

Any zone in "ZT" for Start, going into alarm, fault, or trouble will activate the relay.

 

 

 

Any zone in "ZT" for Stop, that restores will stop the relay action.

Choices for System Operation are:

00

= No Response (Not Used)

 

23

= No Alarm Response

01

= Entry/Exit #1

 

31

= End of Exit Time

02

= Entry/exit #2

 

32

= Start of Entry Time

03

= Perimeter

 

33

= Any Burglary Alarm

04

= Interior Follower

 

34

= Code + [#] + 71 Key Entry

05

= Trouble Day/Alarm Night

 

35

= Code + [#] + 72 Key Entry

06

= 24-Hr. Silent

 

36

= At Bell Timeout **

07

= 24-Hr. Audible

 

37

= 2 Times Bell Timeout **

08

= 24-Hr. Auxiliary

 

38

= Chime

09

= Fire Alarm or Trouble

 

39

= Fire Alarm

10

= Interior W/Delay

 

40

= Bypassing

20

= Arming-STAY

 

31

= End of Exit Time

21

= Arming-AWAY

 

41

= AC Power Fail

22

= Disarming (Code + Off)

 

42

= System Battery Low

*

Stop condition only **

Or at disarming, whichever occurs earlier

43 = Communication failure

44 = RF Low Battery

45 = Polling Loop Failure

51 = RF Receiver Failure

52 = Kissoff

54 = Fire Zone Reset

55 = Disarm + 1 Minute

56 = XX Minutes (enter XX in field 1*74) * 57 = YY Seconds (enter YY in field 1*75) * 58 = Duress

60 = Audio Alarm Verification (must be selected for both START and STOP operation)

P = PARTITION No. 1-2, 0 = Any

– 33 –

Image 33
Contents N7001PRV5 5/04 Rev a $0&29,67$Table of Contents Recommended Programming Procedure Program Field Index Field GroupField Group VISTA-40 Programming Form OPEN/CLOSE Report for Keyswitch Enable OPEN/CLOSE Report for54 *57 Alarm Report Codes & ID Digits for Zones 59 *62 Alarm Report Codes & ID Digits for Zones2nd Page Programming Fields press *94 Fields 1*28 1*31 are not applicable for UL installations3rd Page Programming Fields press *94 Partition # Program Fields Partition-Specific Fields1st Page Fields 2nd Page FieldsProgramming With #93 Menu Mode SET to CONFIRM? = YES Zone ProgrammingEnter Zone no = Quit Zone Type PERIMETER03Input Type Input S/N AXXX-XXXXInput S/N Xmit to Confirm Press to Skip Series Transmitters Loop DesignationsProgram field 200 Number of Partitions Expert Mode Zone ProgrammingEnter Zone no SET to CONFIRM?From Template Input S/N XXX-XXXX5804BD Wireless Key Default Templates 5804Template Loop Function Zone Type Template Loop FunctionZone Descriptors Select Zone Descriptor mode Zone DESCRIP? Default SCREEN? Custom WORD? Part DESCRIP?Alpha Descriptors Programming Exit Edit MODE?Select Custom Word Mode Select Default Screen modeAccept the word Select the next wordFollow the same procedure as for custom words Type the word using one of two methods as followsEnter the custom word number 01-20 you want to create Save the word by pressingAlpha Descriptor Vocabulary Character Ascii ChartAlpha Keypad Device ProgrammingRF Expander VIP ModuleFault AlarmRelay Programming TroubleChoices for Start/Stop Zone Types and System Operations Relay Output Devices ProgrammingEnter Relay # Relay Action No Response Start Event Not UsedStart Partn ANY Partition Zone List ProgrammingRelay Type Plex ECP Address Module RELAY# House Code Unit CodeRelay Voice Descriptors Custom Word no =QUIT Enter Index # Custom Word Substitutes for VIP Module AnnunciationDescriptor Prim Partition # Char max Sub. # System Layout WorksheetsDefaults Access Codes & User Definitions for Partitions 1Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Zone Definitions for System Zones 70, 88 89, 90, 91 Zone Definitions for Keypad Panic Zones 95, 96Zone Types Input TypesChoices for System Operation are Relay Outputs WorksheetsPage Ground Ademco VISTA-40 Summary of ConnectionsEileen Way, Syosset, New York