Honeywell VISTA-40 Enable OPEN/CLOSE Report for, OPEN/CLOSE Report for Keyswitch, Dial Tone Pause

Page 6

*39

ENABLE OPEN/CLOSE REPORT FOR

[0]

 

 

 

 

 

 

 

INSTALLER CODE 1=enable; 0=disable

 

 

 

 

 

*40

OPEN/CLOSE REPORT FOR KEYSWITCH

[0]

 

 

 

 

 

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

 

*41

NORMALLY CLOSED or EOLR (Zones 2-8)

[0]

 

 

 

 

 

 

 

1=N.C.loops; 0=EOLR supervision.

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

*42

DIAL TONE PAUSE

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

0=5 seconds; 1=11 seconds; 2=30 seconds.

 

 

 

 

 

 

Must be "0" UL Installations.

 

 

 

 

 

 

 

 

*43

DIAL TONE DETECTION

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

1=wait for true dial tone; 0=pause, then dial

 

 

 

 

 

 

 

 

 

 

 

 

 

*44

RING DETECTION COUNT

[00]

 

 

 

01-14; 15=answering machine; 00=no detection.

 

 

 

 

 

 

Must be "00" for UL Burglary.

 

 

 

 

 

 

 

 

*45

PRIMARY FORMAT

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;

 

3= ADEMCO Express

 

 

 

 

 

 

 

 

*46

LOW SPEED FORMAT (Primary)

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

0= ADEMCO Low Speed; 1=Sescoa/Radionics

 

 

 

 

 

*47

SECONDARY FORMAT

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;

 

3= ADEMCO Express

 

 

 

 

 

 

 

 

*48

LOW SPEED FORMAT (Sec.)

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

0= ADEMCO Low Speed; 1=Sescoa/Radionics

 

 

 

 

 

*49

CHECKSUM VERIFICATION

[0] [0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=yes; 0=no

Prim

 

 

 

Sec

*50

SESCOA/RADIONICS SELECT

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

1=Sescoa; 0=Radionics

 

 

 

 

 

 

 

 

*51

DUAL REPORTING

 

 

 

[0]

 

 

 

 

 

 

 

 

 

1=yes; 0=no If used with Spilt Reporting "1" option (1*34), alarms and alarm restores go to both primary & secondary numbers, while all other reports go to secondary only. If used with Split Reporting "2" option, alarms and alarm restores go to both, open/close and test messages go to secondary only, while all other reports go to primary.

*52 STANDARD/EXPANDED REPORT FOR PRIMARY

[0 0 0 0 0 0]

Alarm Rstr Byp Trbl O/C LoBat

0=standard; 1=expanded;

Note: Expanded overrides 4+2 format.

*53 STANDARD/EXPANDED REPORT FOR SECONDARY

[0 0 0 0 0 0]

Alarm Rstr Byp Trbl O/C LoBat

0=standard; 1=expanded;

Note: Expanded overrides 4+2 format.

*54 *57 ALARM REPORT CODES & ID DIGITS FOR ZONES 01-16.

Skip these fields. Use #93 Menu Mode, Zone

Programming to program the report codes.

*58 SUPERVISORY AND RESTORE CODES FOR ZONES 01-16.Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*59 *62 ALARM REPORT CODES & ID DIGITS FOR ZONES 17-32.

Skip these fields. Use #93 Menu Mode, Zone

Programming to program the report codes.

*63 SUPERVISORY AND RESTORE CODES FOR ZONES 17-32.Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*64 *67 ALARM REPORT CODES & ID DIGITS FOR ZONES 33-48.

Skip these fields. Use #93 Menu Mode, Zone

Programming to program the report codes.

*68 SUPERVISORY AND RESTORE CODES FOR ZONES 33-48.Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*69 *72 ALARM REPORT CODES & ID DIGITS FOR ZONES 49-64.

Skip these fields. Use #93 Menu Mode, Zone

Programming to program the report codes.

*73 SUPERVISORY AND RESTORE CODES FOR ZONES 49-64.Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*74 *77 ALARM REPORT CODES & ID DIGITS FOR ZONES 87-99.

Skip these fields. Use #93 Menu Mode, Zone

Programming to program the report codes.

*78 SUPERVISORY AND RESTORE CODES FOR ZONES 87-99.Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

Byp Rst

ZONE TYPE RESTORE ENABLES

 

 

 

 

 

 

 

 

 

 

 

*79 FOR ZONE TYPES 1-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

 

 

5

 

 

 

6

 

 

7

8

 

 

 

 

 

 

 

 

1=enable; [0=disable]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*80 FOR TYPES 9, 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

10

1=enable; [0=disable]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 6 –

Image 6
Contents $0&29,67$ N7001PRV5 5/04 Rev aTable of Contents Recommended Programming Procedure Program Field Index Field GroupField Group VISTA-40 Programming Form 54 *57 Alarm Report Codes & ID Digits for Zones Enable OPEN/CLOSE Report forOPEN/CLOSE Report for Keyswitch 59 *62 Alarm Report Codes & ID Digits for ZonesFields 1*28 1*31 are not applicable for UL installations 2nd Page Programming Fields press *943rd Page Programming Fields press *94 1st Page Fields Partition-Specific FieldsPartition # Program Fields 2nd Page FieldsProgramming With #93 Menu Mode Enter Zone no = Quit Zone ProgrammingSET to CONFIRM? = YES Zone Type PERIMETER03Input Type Input S/N AXXX-XXXXInput S/N Series Transmitters Loop Designations Xmit to Confirm Press to SkipEnter Zone no Expert Mode Zone ProgrammingProgram field 200 Number of Partitions SET to CONFIRM?Input S/N XXX-XXXX From TemplateTemplate Loop Function Wireless Key Default Templates 58045804BD Zone Type Template Loop FunctionAlpha Descriptors Programming Zone DESCRIP? Default SCREEN? Custom WORD? Part DESCRIP?Zone Descriptors Select Zone Descriptor mode Exit Edit MODE?Accept the word Select Default Screen modeSelect Custom Word Mode Select the next wordEnter the custom word number 01-20 you want to create Type the word using one of two methods as followsFollow the same procedure as for custom words Save the word by pressingCharacter Ascii Chart Alpha Descriptor VocabularyRF Expander Device ProgrammingAlpha Keypad VIP ModuleRelay Programming AlarmFault TroubleEnter Relay # Relay Output Devices ProgrammingChoices for Start/Stop Zone Types and System Operations Relay Action No Response Start Event Not UsedRelay Type Plex ECP Address Module RELAY# House Code Zone List ProgrammingStart Partn ANY Partition Unit CodeRelay Voice Descriptors Custom Word Substitutes for VIP Module Annunciation Custom Word no =QUIT Enter Index #System Layout Worksheets Descriptor Prim Partition # Char max Sub. #Access Codes & User Definitions for Partitions 1 DefaultsZone Definition for Zones Zone Definition for Zones Zone Definition for Zones Zone Types Zone Definitions for Keypad Panic Zones 95, 96Zone Definitions for System Zones 70, 88 89, 90, 91 Input TypesRelay Outputs Worksheets Choices for System Operation arePage Ademco VISTA-40 Summary of Connections GroundEileen Way, Syosset, New York