First Alert FA148CPSSIA manual ∗171, ∗177, ∗181

Page 14

 

171

Pager 4 Report Options

 

[0,0,0]

 

 

 

 

 

 

See field *162 for reporting options.

P1

P2 comm

 

 

 

 

Select for each partition (use zone list 12 for options 12 or 13).

 

 

 

172 Pager Delay Option For Alarms

0 = none

1 = 1 minute

2 = 2 minutes

3 = 3 minutes

[3]

This field determines the delay of alarm reports to the pager. This gives the Central Station enough time to verify the alarm report it received before the dialer attempts to dial the pager.

This delay is for ALL pagers in the system.

MISCELLANEOUS SYSTEM FIELDS (*174-*181)

174 Clean Me Reporting Options

0 = disable

1 = Clean Me signal reports

[0] For ESL smoke detectors

This is a maintenance feature for ESL 2-wire smoke detectors on Zone

1.If used, this option limits the number of smoke detectors to a

maximum of 10, rather than 16. To enable the “clean me” feature, a time response setting of “3” (1.2 seconds) must be entered in 56 Zone

Programming for zone 1.

NOTE: If Clean Me is enabled, you must enter “3” in field 56 programming for zone 1 response time.

177

Device Duration 1, 2

 

 

0

= 15 secs

6

= 2-1/2 min

#+11 = 7 min

 

1

= 30 secs

7

= 3 min

#+12 = 8 min

 

2

= 45 secs

8

= 4 min

#+13 = 10 min

 

3

= 60 secs

9

= 5 min

#+14 = 12 min

 

4

= 90 secs

#+10 = 6 min

#+15 = 15 min

 

5

= 2 min

 

 

 

[0] [0]

1 2

(used in *80 Menu mode-Device Actions 5/6)

These entries set the duration for output action options 5 (duration 1) and 6 (duration 2) programmed in 80 Output Function Programming.

181

50/60 Hertz AC Operation

 

 

 

[0]

 

0 = 60 Hz; 1 = 50 Hz

 

 

 

Select the type of AC power applied to the control (option is used for

 

 

 

 

Real-Time Clock synchronization)

CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)

(see Configurable Zone Type Worksheet)

The system allows you to define custom zone types (FA168CPS supports 4 [types 90-93]; FA148CP supports 2 [types 90, 91]), based on the options described at right.

All configurable zone types can be programmed via the downloader. Zone types 90-91 can also be programmed from a keypad using data fields *182-*185.

IMPORTANT: Be careful when selecting combinations of options for configurable zone types. Contradictory options can cause unpredictable results.

Configurable Zone Type Options

Auto Restore (entry 2): Faults on zones set for this option are cleared; restore messages sent upon restoral of faults.

Vent Zone (entry 2): Zones set for this option are ignored if faulted when arming the system, but are protected if the zone is later restored (e.g., an open window can be ignored when arming, but if the window is later closed, it will be protected; opening the window again causes an alarm.)

Bypass Disarmed (entry 4): Zones set for this option can be bypassed only while the system is disarmed.

Bypass Armed (entry 4): Zones set for this option can be bypassed when the system is armed.

Dial Delay (entry 6): Alarms on zones set for this option participate in dial delay central station reporting, if system dial delay enabled in field *50.

Fault Delay (entry 6): Faults on zones set for this option are delayed by the time set in field *87. Do not use this option if using entry/exit delay for this zone type.

Faults Display (entry 7): Selects how faults on zones set for this zone type are displayed.

Power Reset/Verification(entry 7): Selects whether the system resets power (when user enters code + OFF), and whether the system performs alarm verification (see description for zone type 16 in Zone Type Definitions section) when a fault occurs on these zones.

Use Entry Delay (entry 8): Selects whether to use the system’s entry delay times.

Use Exit Delay (entry 8): Selects whether to use the system’s exit delay time.

Interior Type (entry 8): Zones set for this option are treated same as standard zone type 4 (bypasses when armed STAY, faults displayed).

Alarm Sounds (entry 9): Selects the type of alarms sound for zones set for this zone type.

Bell Timeout (entry 9): Alarm sounding on zones set for this option remain for the duration set in fields *32 / *33.

Fire Zone (entry 9): Zones set for this option respond in the same manner as if programmed for zone type 9. Do not set fire zones to respond as a “fault” in entries 1-6.

Trouble Sounds (entry 10): Selects the type of trouble sounds for zones set for this zone type (periodic beeps = once every 30 seconds; trouble beeps = rapid beeping).

Chime Enable (entry 10): Zones set for this option cause a chime when Chime mode is on.

– 14 –

Image 14
Contents FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA K5305-5PRV5 11/08 Rev. BTable of Contents Special Messages Programming Mode CommandsInstaller code + # + 03 enable AVS operation RF transmittersData Field Programming Form ∗33 ∗31∗32 ∗34∗41 ∗42 ∗39∗40 ∗45 ∗46∗54 ∗50∗53 ∗55∗61 ∗59∗60 ∗62∗68 ∗66∗67 ∗69∗84 ∗77∗78 ∗85∗91 ∗88∗90 ∗93 ∗95∗166 ∗163∗164 ∗167∗181 ∗171∗177 ∗184 ∗185∗193 ∗191∗192 ∗194Entry Zone Type Configurable Zone Types WorksheetsEntries for Fields *182 and *184 Field *182∗56 Zone Programming Menu Mode Response Time RT Hardwire TypeReport Code RC Input Device type∗58 Expert Zone Program Mode Wireless KEY Programming Templates Confirm Wireless Key Transmitter5804BD 2-Way Wireless Key Transmitter Not ConfirmedPartition Number ∗57 Function KEY Programming Menu ModeFunction Key FA168CPSDevice Output Number Programming Output DevicesOutput Identification Output Normally Low∗80 Output Function Menu Mode Zone List Menu Mode Output Function NoActivated By Zone TypeOutput Action ∗81 Zone List Menu ModeMenu Mode Zone List Number Output Number∗82 Alpha Descriptor Menu Mode Example Back Door Descriptor ExampleZN 01 Back D OOR ZN 01 Back DoorCharacter Ascii Chart For Adding Custom Words Setting Schedules Pre-Programmed #03 Command #04 Command Setting the REAL-TIME ClockQuick Program Command Results Repeat OptionDiagnostics Select ∗29 IP/GSM Program ModeEnable IP/GSM? ProgrammingZone Type Definitions UL Notices SIA Quick Reference GuideWorksheet for ∗56 Zone Programming Reserved ZonesList No Used For… Contains These Zones… Worksheet for ∗57 Function KEY ProgrammingWorksheet for ∗81 Zone List Programming Option Function CommentsWorksheet for ∗80 Output Function Programming FA168CPSTable of Device Addresses Reports as†† Enabled By…Worksheet for Schedules DaysSeries Transmitter Input Loop Identification 5800CO 5800Micra 5800SS1 5800WAVE 5801 5802 MN

FA148CPSSIA specifications

First Alert FA148CPSSIA is a premium smoke and carbon monoxide detector that stands out for its advanced features and technologies, designed to enhance home safety. This innovative device provides dual protection against two of the most dangerous threats faced in homes: smoke from potential fires and carbon monoxide, a silent killer that is odorless and colorless.

One of the main features of the FA148CPSSIA is its voice alert system. This device does not just sound an alarm; it provides an intelligible voice alert that appraises homeowners on the specific type of danger. This feature allows users to quickly identify whether they are facing a smoke or carbon monoxide event, enabling them to respond more effectively.

Furthermore, the FA148CPSSIA is equipped with a 10-year lithium battery, which means that homeowners do not have to worry about battery replacements for over a decade. This feature not only makes the device more convenient but also ensures continual protection without frequent maintenance. The unit is designed with a low battery chirp alert, reminding users when it is time to replace or recharge the entire unit.

Another remarkable aspect of the FA148CPSSIA is its SmartHome compatibility. The unit can connect with various smart home systems, allowing users to monitor the device and receive alerts on their mobile devices. This integration makes for a holistic approach to home safety, as homeowners can receive real-time notifications whether they are at home or away.

The First Alert FA148CPSSIA features a sleek and modern design that allows it to blend seamlessly into any home décor. Its compact form factor allows for easy installation in various places around the house, including bedrooms, hallways, and kitchens.

In terms of technology, the FA148CPSSIA employs photoelectric smoke sensing technology, which is effective in detecting smoldering fires while reducing the likelihood of false alarms. This advanced sensing capability ensures that users are alerted to real dangers without unnecessary interruptions.

Overall, the First Alert FA148CPSSIA is a feature-rich, reliable, and user-friendly smoke and carbon monoxide detector. Its combination of voice alerts, long-lasting battery, smart connectivity, and advanced sensing technology makes it an ideal choice for enhancing home safety and ensuring peace of mind for families.