First Alert FA148CPSSIA manual ∗171, ∗177, ∗181

Page 14

 

171

Pager 4 Report Options

 

[0,0,0]

 

 

 

 

 

 

See field *162 for reporting options.

P1

P2 comm

 

 

 

 

Select for each partition (use zone list 12 for options 12 or 13).

 

 

 

172 Pager Delay Option For Alarms

0 = none

1 = 1 minute

2 = 2 minutes

3 = 3 minutes

[3]

This field determines the delay of alarm reports to the pager. This gives the Central Station enough time to verify the alarm report it received before the dialer attempts to dial the pager.

This delay is for ALL pagers in the system.

MISCELLANEOUS SYSTEM FIELDS (*174-*181)

174 Clean Me Reporting Options

0 = disable

1 = Clean Me signal reports

[0] For ESL smoke detectors

This is a maintenance feature for ESL 2-wire smoke detectors on Zone

1.If used, this option limits the number of smoke detectors to a

maximum of 10, rather than 16. To enable the “clean me” feature, a time response setting of “3” (1.2 seconds) must be entered in 56 Zone

Programming for zone 1.

NOTE: If Clean Me is enabled, you must enter “3” in field 56 programming for zone 1 response time.

177

Device Duration 1, 2

 

 

0

= 15 secs

6

= 2-1/2 min

#+11 = 7 min

 

1

= 30 secs

7

= 3 min

#+12 = 8 min

 

2

= 45 secs

8

= 4 min

#+13 = 10 min

 

3

= 60 secs

9

= 5 min

#+14 = 12 min

 

4

= 90 secs

#+10 = 6 min

#+15 = 15 min

 

5

= 2 min

 

 

 

[0] [0]

1 2

(used in *80 Menu mode-Device Actions 5/6)

These entries set the duration for output action options 5 (duration 1) and 6 (duration 2) programmed in 80 Output Function Programming.

181

50/60 Hertz AC Operation

 

 

 

[0]

 

0 = 60 Hz; 1 = 50 Hz

 

 

 

Select the type of AC power applied to the control (option is used for

 

 

 

 

Real-Time Clock synchronization)

CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)

(see Configurable Zone Type Worksheet)

The system allows you to define custom zone types (FA168CPS supports 4 [types 90-93]; FA148CP supports 2 [types 90, 91]), based on the options described at right.

All configurable zone types can be programmed via the downloader. Zone types 90-91 can also be programmed from a keypad using data fields *182-*185.

IMPORTANT: Be careful when selecting combinations of options for configurable zone types. Contradictory options can cause unpredictable results.

Configurable Zone Type Options

Auto Restore (entry 2): Faults on zones set for this option are cleared; restore messages sent upon restoral of faults.

Vent Zone (entry 2): Zones set for this option are ignored if faulted when arming the system, but are protected if the zone is later restored (e.g., an open window can be ignored when arming, but if the window is later closed, it will be protected; opening the window again causes an alarm.)

Bypass Disarmed (entry 4): Zones set for this option can be bypassed only while the system is disarmed.

Bypass Armed (entry 4): Zones set for this option can be bypassed when the system is armed.

Dial Delay (entry 6): Alarms on zones set for this option participate in dial delay central station reporting, if system dial delay enabled in field *50.

Fault Delay (entry 6): Faults on zones set for this option are delayed by the time set in field *87. Do not use this option if using entry/exit delay for this zone type.

Faults Display (entry 7): Selects how faults on zones set for this zone type are displayed.

Power Reset/Verification(entry 7): Selects whether the system resets power (when user enters code + OFF), and whether the system performs alarm verification (see description for zone type 16 in Zone Type Definitions section) when a fault occurs on these zones.

Use Entry Delay (entry 8): Selects whether to use the system’s entry delay times.

Use Exit Delay (entry 8): Selects whether to use the system’s exit delay time.

Interior Type (entry 8): Zones set for this option are treated same as standard zone type 4 (bypasses when armed STAY, faults displayed).

Alarm Sounds (entry 9): Selects the type of alarms sound for zones set for this zone type.

Bell Timeout (entry 9): Alarm sounding on zones set for this option remain for the duration set in fields *32 / *33.

Fire Zone (entry 9): Zones set for this option respond in the same manner as if programmed for zone type 9. Do not set fire zones to respond as a “fault” in entries 1-6.

Trouble Sounds (entry 10): Selects the type of trouble sounds for zones set for this zone type (periodic beeps = once every 30 seconds; trouble beeps = rapid beeping).

Chime Enable (entry 10): Zones set for this option cause a chime when Chime mode is on.

– 14 –

Image 14
Contents FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA K5305-5PRV5 11/08 Rev. BTable of Contents Special Messages Programming Mode CommandsInstaller code + # + 03 enable AVS operation RF transmittersData Field Programming Form ∗33 ∗31∗32 ∗34∗41 ∗42 ∗39∗40 ∗45 ∗46∗54 ∗50∗53 ∗55∗61 ∗59∗60 ∗62∗68 ∗66∗67 ∗69∗84 ∗77∗78 ∗85 ∗91 ∗88 ∗90 ∗93 ∗95∗166 ∗163∗164 ∗167∗181 ∗171∗177 ∗184 ∗185∗193 ∗191∗192 ∗194Entry Zone Type Configurable Zone Types WorksheetsEntries for Fields *182 and *184 Field *182∗56 Zone Programming Menu Mode Response Time RT Hardwire TypeReport Code RC Input Device type∗58 Expert Zone Program Mode Wireless KEY Programming Templates Confirm Wireless Key Transmitter5804BD 2-Way Wireless Key Transmitter Not ConfirmedPartition Number ∗57 Function KEY Programming Menu ModeFunction Key FA168CPSDevice Output Number Programming Output DevicesOutput Identification Output Normally Low∗80 Output Function Menu Mode Zone List Menu Mode Output Function NoActivated By Zone TypeOutput Action ∗81 Zone List Menu ModeMenu Mode Zone List Number Output Number∗82 Alpha Descriptor Menu Mode Example Back Door Descriptor ExampleZN 01 Back D OOR ZN 01 Back DoorCharacter Ascii Chart For Adding Custom Words Setting Schedules Pre-Programmed #03 Command #04 Command Setting the REAL-TIME ClockQuick Program Command Results Repeat OptionDiagnostics Select ∗29 IP/GSM Program ModeEnable IP/GSM? ProgrammingZone Type Definitions UL Notices SIA Quick Reference GuideWorksheet for ∗56 Zone Programming Reserved ZonesList No Used For… Contains These Zones… Worksheet for ∗57 Function KEY ProgrammingWorksheet for ∗81 Zone List Programming Option Function CommentsWorksheet for ∗80 Output Function Programming FA168CPSTable of Device Addresses Reports as†† Enabled By…Worksheet for Schedules DaysSeries Transmitter Input Loop Identification 5800CO 5800Micra 5800SS1 5800WAVE 5801 5802 MN