First Alert FA148CPSSIA manual UL Notices, SIA Quick Reference Guide

Page 35

UL NOTICES

1.Entry Delay No. 1 and No. 2 (fields 35, 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.

2.For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds.

3.The maximum number of reports per armed period (field 93) must be set to “0” (unlimited) for UL installations.

4.Periodic testing (see scheduling mode) must be at least every 24 hours.

5.Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.).

6.All partitions must be owned and managed by the same person(s).

7.All partitions must be part of one building at one street address.

8.If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.

9.For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The tamper switch installed to protect the control unit enclosure door is suitable for this purpose.

10.Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for UL installations.

11.Auto-disarming is not a UL Listed feature.

12.As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications, the following UL requirements per UL681 are provided:

The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:

a)60 seconds for a system with standard line security or encrypted line security,

b)120 seconds for a system without standard line security or encrypted line security, or

c)120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.

13.This control is not intended for bank safe and vault applications.

SIA QUICK REFERENCE GUIDE

1.31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports in armed period” set in field 93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).

2.34 Exit Delay: Minimum exit delay is 45 seconds.

3.35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.

4.37 Audible Exit Warning: Feature always enabled; field does not exist.

5.39 Power Up in Previous State: Must be “1,” power up in previous state.

6.40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91 must be set.

7.50 Burglary Dial Delay: Delay must be minimum of 30 seconds.

8.59 Exit Error Alarm Report Code: Always enabled.

968 Cancel Report Code: Default is “code enabled.”

10.69 Recent Closing Report Code: Always enabled.

11.91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be set to “1” (enabled).

12.93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.

13.Cross zone timer programming is set in field 85; cross zone pairs are assigned in zone list 4 using 81 Zone List mode.

14.Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code reporting by programming zone 92 using 56 Zone Programming mode.

15.Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.

– 35 –

Image 35
Contents K5305-5PRV5 11/08 Rev. B FA168CPS / FA168CPSSIA FA148CP / FA148CPSIATable of Contents RF transmitters Programming Mode CommandsInstaller code + # + 03 enable AVS operation Special MessagesData Field Programming Form ∗34 ∗31∗32 ∗33∗45 ∗46 ∗39∗40 ∗41 ∗42∗55 ∗50∗53 ∗54∗62 ∗59∗60 ∗61∗69 ∗66∗67 ∗68∗85 ∗77∗78 ∗84∗91 ∗88∗90 ∗95 ∗93∗167 ∗163∗164 ∗166∗181 ∗171∗177 ∗185 ∗184∗194 ∗191∗192 ∗193Field *182 Configurable Zone Types WorksheetsEntries for Fields *182 and *184 Entry Zone Type∗56 Zone Programming Menu Mode Input Device type Hardwire TypeReport Code RC Response Time RT∗58 Expert Zone Program Mode Wireless KEY Programming Templates Not Confirmed Wireless Key Transmitter5804BD 2-Way Wireless Key Transmitter ConfirmFA168CPS ∗57 Function KEY Programming Menu ModeFunction Key Partition NumberOutput Normally Low Programming Output DevicesOutput Identification Device Output Number∗80 Output Function Menu Mode Zone Type Menu Mode Output Function NoActivated By Zone ListOutput Number ∗81 Zone List Menu ModeMenu Mode Zone List Number Output Action∗82 Alpha Descriptor Menu Mode ZN 01 Back Door Descriptor ExampleZN 01 Back D OOR Example Back DoorCharacter Ascii Chart For Adding Custom Words Setting Schedules Repeat Option Setting the REAL-TIME ClockQuick Program Command Results Pre-Programmed #03 Command #04 CommandProgramming ∗29 IP/GSM Program ModeEnable IP/GSM? Diagnostics SelectZone Type Definitions SIA Quick Reference Guide UL NoticesReserved Zones Worksheet for ∗56 Zone ProgrammingOption Function Comments Worksheet for ∗57 Function KEY ProgrammingWorksheet for ∗81 Zone List Programming List No Used For… Contains These Zones…FA168CPS Worksheet for ∗80 Output Function ProgrammingDays Reports as†† Enabled By…Worksheet for Schedules Table of Device Addresses5800CO 5800Micra 5800SS1 5800WAVE 5801 5802 MN Series Transmitter Input Loop Identification

FA148CPSSIA specifications

First Alert FA148CPSSIA is a premium smoke and carbon monoxide detector that stands out for its advanced features and technologies, designed to enhance home safety. This innovative device provides dual protection against two of the most dangerous threats faced in homes: smoke from potential fires and carbon monoxide, a silent killer that is odorless and colorless.

One of the main features of the FA148CPSSIA is its voice alert system. This device does not just sound an alarm; it provides an intelligible voice alert that appraises homeowners on the specific type of danger. This feature allows users to quickly identify whether they are facing a smoke or carbon monoxide event, enabling them to respond more effectively.

Furthermore, the FA148CPSSIA is equipped with a 10-year lithium battery, which means that homeowners do not have to worry about battery replacements for over a decade. This feature not only makes the device more convenient but also ensures continual protection without frequent maintenance. The unit is designed with a low battery chirp alert, reminding users when it is time to replace or recharge the entire unit.

Another remarkable aspect of the FA148CPSSIA is its SmartHome compatibility. The unit can connect with various smart home systems, allowing users to monitor the device and receive alerts on their mobile devices. This integration makes for a holistic approach to home safety, as homeowners can receive real-time notifications whether they are at home or away.

The First Alert FA148CPSSIA features a sleek and modern design that allows it to blend seamlessly into any home décor. Its compact form factor allows for easy installation in various places around the house, including bedrooms, hallways, and kitchens.

In terms of technology, the FA148CPSSIA employs photoelectric smoke sensing technology, which is effective in detecting smoldering fires while reducing the likelihood of false alarms. This advanced sensing capability ensures that users are alerted to real dangers without unnecessary interruptions.

Overall, the First Alert FA148CPSSIA is a feature-rich, reliable, and user-friendly smoke and carbon monoxide detector. Its combination of voice alerts, long-lasting battery, smart connectivity, and advanced sensing technology makes it an ideal choice for enhancing home safety and ensuring peace of mind for families.