Top Vent - Vertical Termination
Venting with 3 elbows
| V1 Minimum | H1 + H2 Maximum | V2 | V1 + V2 Minimum | ||
| 90° Elbow | 1 ft. | 305 mm | * | * | |
1 ft. |
| 305 mm | 2 ft. | 610 mm | * | * |
2 ft. |
| 610 mm | 4 ft. | 1.2 m | * | * |
3 ft. |
| 914 mm | 6 ft. | 1.8 m | * | * |
4 ft. |
| 1.2 m | 14 ft. | 4.3 m | * | * |
H MAX. =14 ft. (4.3 m)
V1 + V2 + H1 + H2 MAX. = 40 ft. (12.2 m)
* No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 cannot exceed 40 ft. (12.2 m)
V2
Note: Use SLP Series components only.
Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).
H1
H2
V1
INSTALLED
HORIZONTALLY
Figure 7.12
Heat & Glo • | 31 |