Heat & Glo LifeStyle 6000GCF-IPI Vent Diagrams, Top Vent Horizontal Termination One Elbow

Page 13

D. Vent Diagrams

Note: The 6000 series fireplaces can adapt to SL series vent pipe, if desired.

When venting off the top of the unit, use a DVP-2SLadapter and a minimum 48 inch vertical section of SL series vent pipe.

After the 48 inch vertical section, the venting table rules must be followed. The first 48 inch vertical section is NOT counted as part of the vertical components in the table. It is still counted as part of the overall maximum run. All venting table rules for the vent run must still be followed.

Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal SL pipe 7 ft. min. vertical = 11 ft. max. horizontal

1.Top Vent - Horizontal Termination One Elbow

V1

H1

Figure 5.3

WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install wall shield and ceiling firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

WARNING

Fire Risk.

When using DVP-HRC-SS and DVP-HRC-ZC- SS termination caps on top vented fireplaces, a 6 inch minimum vertical vent section is required before installing first elbow.

V1 Minimum

H1

Maximum

6 inches

152 mm

3 ft

 

914 mm

1 ft

305 mm

3 ft

 

914 mm

 

 

 

 

 

2 ft

610 mm

6 ft

 

1.8 m

 

 

 

 

 

3 ft

914 mm

9 ft

 

2.7 m

4 ft

1.2 m

12 ft

 

3.7 m

V1 + H1 = 40 ft (12.2 m) Maximum

H1 = 20 ft (6.1 m) Maximum

V1 = 6 inches (152 mm) Minimum

Two Elbows

H2H1

V1

V1 Minimum

H1 + H2 Maximum

1 ft

305 mm

Cannot do

 

 

 

 

1-1/2 ft

457 mm

1-1/2 ft

457 mm

 

 

 

 

2 ft

610 mm

3 ft

914 mm

3 ft

914 mm

6 ft

1.8 m

4 ft

1.2 m

9 ft

2.7 m

 

 

 

 

V1 + H1+ H2 = 50 ft (15.2 m) Maximum

H1 + H2 = 17 ft (5.2 m) Maximum V1 = 1-1/2 ft (457 mm) Minimum

Figure 5.4

INSTALLED

HORIZONTALLY

Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP2110-900 Rev. F • 6/08

13

Image 13
Contents Hot glass will cause burns Models 6000GCF-IPI6000GCF-IPILPHomeowner Reference Information CongratulationsTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsTools and Supplies Needed Getting StartedSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseIn. MIN Mantel ProjectionsFt. MAX Vent Termination Minimum Clearances Termination LocationsSee .4 for specific clearances Alcove Applications Vent Table Key Vent Information and DiagramsUse of Elbows Measuring StandardsTop Vent Horizontal Termination One Elbow Vent DiagramsTwo Elbows Minimum MaximumTop Vent Horizontal Termination Three Elbows H1 Maximum V1 + Minimum H1+ H2 V1+ V2 Minimum H1+ H2 Maximum Top Vent Vertical Termination Three ElbowsPipe Clearances to Combustibles Vent Clearances and FramingCombustible Wall Penetration Wall Penetration FramingNon-Combustible Wall Penetration Installing Attic Shield Installing the Ceiling FirestopVertical Penetration Framing Appliance Preparation Temporary Access PanelAttaching Sheetrock Ledges Securing and Leveling the Appliance Installing the Flue RestrictorVertical Top Vent Installing the Fiberglass GasketAssembly of Vent Sections Installing Vent PipeAttaching Vent to the Firebox Assembly Assembling Pipe SectionsAssembling DVP-12A Slip Sections Assembling Minimum Installations MI SectionsSecuring the Vent Sections Vertical Sections Disassembly of Vent SectionsHorizontal Sections Installing the Horizontal Termination Cap Installing Heat Shield and Horizontal Termination CapHeat Shield Requirements for Horizontal Termination Roof Pitch Min. Ft Installing Roof Flashing and Vertical Termination Cap17 Assembling the Storm Collar Around the Pipe Assembling and Installing Storm CollarFuel Conversions Gas Connection Gas InformationGas Pressures Pressure Natural Gas PropaneHigh Altitude Installations Wall Switch Recommendation for WireOptional Accessories Requirements Electrical InformationIntellifire Pilot Ignition IPI Wiring Diagram Wall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingClean the Appliance Appliance SetupAccessories Remove Shipping MaterialsEmber Placement Install the RefractoryPlacing the Ember Material Log #1 SRV2103-107 Positioning the Logs12 Front View Air Shutter Setting Glass AssemblyScreen Mesh Grilles and TrimBefore Lighting Appliance Operating InstructionsOn position. The ON/OFF switch may Turn off all electric power to the applianceLighting Appliance IPI Ignition Final inspection byInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Intellifire Ignition System TroubleshootingSympton Possible Cause Corrective Action Symptom Possible Cause Corrective Action Maintaining and Servicing Appliance Maintenance TasksDoors, Surrounds Inspect Maintenance TasksReference Materials Appliance Dimension DiagramLocation Inches Millimeters DVP vent components Vent Components DiagramsWall Shield Firestop Horizontal Termination CapHeat Shield Horizontal Termination Cap KitNot for use on these models Extended Heat ShieldDVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP Log Set Assembly Part number list on following Service PartsStocked Service Parts ListAt Depot 6000GCF-IPI IPI Valve AssemblyLimited Lifetime Warranty Heat & GLO GAS Appliance Products Limited Lifetime WarrantyDo not Discard this Manual Contact Information