B. Wall Penetration Framing
NOTE: Heat shields MUST overlap by a minimum of
The heat shield is designed to be used on a wall 4 in. to
mm)the existing heat shields must be field trimmed. If wall thickness is greater than
|
|
|
| 3 IN. TOP |
HEAT |
|
| CLEARANCE | |
SHIELD |
|
| HEAT | |
|
|
|
| |
|
|
|
| SHIELD |
|
|
|
|
|
|
|
|
|
|
12 in.
10 in.
B
A
WALL WALL SHIELD
FIRESTOP
1 IN. CLEARANCE BOTTOM SIDES
A* | B |
*Shows center of 10” x 12” vent framing hole for top venting. The center of the hole is (1) inch (25.4 mm) above the center of the horizontal vent pipe. With minimum vertical or 12 inch and 90º elbow.
Figure 6.6 Exterior Wall Hole
Figure 6.5 Horizontal venting clearances to combustible materials
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall shield firestop, (Figure 6.3) whenever a wall is penetrated. Use same size framing materials as those used in the wall construction. The wall shield firestop maintains minimum clearances and prevents cold air infiltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus- tible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.
Whenever a
If your local inspector requires the wall shield firestop on both sides, then both wall shield firestops must have a heat shield attached to them.
18 | Heat & Glo • |