D.Installing Roof Flashing and Vertical Termination Cap

To install roof flashing see Figure 8.13.

For installation of vertical termination cap see minimum vent heights for various pitched roofs (see Figure 8.13).

HORIZONTAL

OVERHANG

Caulk the gap between the roof flashing and the outside diameter of the pipe. Also caulk the perimeter of flashing that contacts roof surface as shown in Figure 8.15.

To attach the vertical termination cap, slide the inner col- lar of the cap into the inner flue of the pipe section and place the outer collar of the cap over the outer flue of the pipe section.

Secure with three screws into the outer flue. Secure the cap by driving the three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer

2FT.

MIN.

GAS DIRECT VENT

TERMINATION CAP

20 INCHES MIN.

VERTICAL

LOWEST

WALL

 

DISCHARGE

 

OPENING

 

X

12

ROOF PITCH

IS X/ 12

H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

flue of the pipe (see Figure 8.14).

TERMINATION CAP

(1 of 3)

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 6/12 to 7/12

1.25*

Over 7/12 to 8/12

1.5*

Over 8/12 to 9/12

2.0*

Over 9/12 to 10/12

2.5

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

* 3 foot minimum in snow regions

Figure 8.13 Minimum height from roof to lowest discharge opening

WARNING

Fire Risk.

Explosion Risk.

Inspect external vent cap regularly.

Ensure no debris blocks cap.

Combustible materials blocking cap may ignite.

Restricted air flow affects burner operation.

STORM

COLLAR

SCREWS

CAULK

Figure 8.14

CAULK

Figure 8.15

Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP2110-900 Rev. F • 6/08

27

Image 27
Contents Hot glass will cause burns Models 6000GCF-IPI6000GCF-IPILPHomeowner Reference Information CongratulationsTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsTools and Supplies Needed Getting StartedSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseMantel Projections In. MINFt. MAX Termination Locations Vent Termination Minimum ClearancesSee .4 for specific clearances Alcove Applications Measuring Standards Vent Information and DiagramsVent Table Key Use of ElbowsMinimum Maximum Vent DiagramsTop Vent Horizontal Termination One Elbow Two ElbowsTop Vent Horizontal Termination Three Elbows H1 Maximum V1 + Minimum H1+ H2 V1+ V2 Minimum H1+ H2 Maximum Top Vent Vertical Termination Three ElbowsPipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationNon-Combustible Wall Penetration Installing the Ceiling Firestop Installing Attic ShieldVertical Penetration Framing Temporary Access Panel Appliance PreparationAttaching Sheetrock Ledges Securing and Leveling the Appliance Installing the Flue RestrictorVertical Top Vent Installing the Fiberglass GasketAssembling Pipe Sections Installing Vent PipeAssembly of Vent Sections Attaching Vent to the Firebox AssemblyAssembling DVP-12A Slip Sections Assembling Minimum Installations MI SectionsDisassembly of Vent Sections Securing the Vent Sections Vertical SectionsHorizontal Sections Installing Heat Shield and Horizontal Termination Cap Installing the Horizontal Termination CapHeat Shield Requirements for Horizontal Termination Roof Pitch Min. Ft Installing Roof Flashing and Vertical Termination Cap17 Assembling the Storm Collar Around the Pipe Assembling and Installing Storm CollarPressure Natural Gas Propane Gas InformationFuel Conversions Gas Connection Gas PressuresHigh Altitude Installations Electrical Information Recommendation for WireWall Switch Optional Accessories RequirementsIntellifire Pilot Ignition IPI Wiring Diagram Wall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingRemove Shipping Materials Appliance SetupClean the Appliance AccessoriesInstall the Refractory Ember PlacementPlacing the Ember Material Log #1 SRV2103-107 Positioning the Logs12 Front View Grilles and Trim Glass AssemblyAir Shutter Setting Screen MeshBefore Lighting Appliance Operating InstructionsFinal inspection by Turn off all electric power to the applianceOn position. The ON/OFF switch may Lighting Appliance IPI IgnitionFrequently Asked Questions Initial Break-in ProcedureAfter Appliance is Lit Troubleshooting Intellifire Ignition SystemSympton Possible Cause Corrective Action Symptom Possible Cause Corrective Action Maintaining and Servicing Appliance Maintenance TasksDoors, Surrounds Inspect Maintenance TasksAppliance Dimension Diagram Reference MaterialsLocation Inches Millimeters DVP vent components Vent Components DiagramsHorizontal Termination Cap Kit Horizontal Termination CapWall Shield Firestop Heat ShieldNot for use on these models Extended Heat ShieldDVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP Log Set Assembly Part number list on following Service PartsService Parts List StockedAt Depot 6000GCF-IPI IPI Valve AssemblyLimited Lifetime Warranty Heat & GLO GAS Appliance Products Limited Lifetime WarrantyDo not Discard this Manual Contact Information