Heat & Glo LifeStyle 6000GCF-IPI Vent Clearances and Framing, Pipe Clearances to Combustibles

Page 17

6 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

WARNING

Fire Risk. Explosion Risk.

Maintain vent clearance to combustibles as specified.

Do not pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause fire.

3 in. TOP CLEARANCE

1 in. CLEARANCE AROUND VERTICAL SECTIONS

1 in. SIDE AND BOTTOM CLEARANCE

Figure 6.1 Pipe Clearances

WARNING

Fire Risk.

Installation of this appliance may require the use of heat shield 385-920 above the first 90º elbow in the venting system.

Heat shield required if vertical distance between top of horizontal elbow and any combustible surface above elbow is less than 4 inches.

Heat shield not required if distance is more than 4 inches.

COMBUSTIBLE

SURFACE

3 IN MIN.

(76 mm)

HEAT

SHIELD

Figure 6.2

Fasten the shield in place using the four pilot holes pro- vided in the part.

Position the shield so the longest dimension (13 1/2 inch) is placed in same direction the elbow is pointing.

Center the shield directly above the elbow with a 1/2 inch air space between shield and combustible surface (see Figure 6.3).

 

COMBUSTIBLE SURFACE

CORRECT

INCORRECT

 

DIRECTION

 

UP

 

HEAT SHIELD

 

90º ELBOW

Figure 6.3

 

Attach elbow heat shield to the exhaust pipe if combusti- ble materials are not present at install (see Figure 6.4).

Cut the tabs as shown and bend down. Using the screws found in the manual bag secure the heat shield to the pipe maintaining 3 to 4 inches between the pipe and shield.

SCREW

3in.

(76 mm)

Figure 6.4

Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP2110-900 Rev. F • 6/08

17

Image 17
Contents Hot glass will cause burns Models 6000GCF-IPI6000GCF-IPILPHomeowner Reference Information CongratulationsTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsTools and Supplies Needed Getting StartedSelecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseFt. MAX Mantel ProjectionsIn. MIN See .4 for specific clearances Termination LocationsVent Termination Minimum Clearances Alcove Applications Vent Table Key Vent Information and DiagramsUse of Elbows Measuring StandardsTop Vent Horizontal Termination One Elbow Vent DiagramsTwo Elbows Minimum MaximumTop Vent Horizontal Termination Three Elbows H1 Maximum V1 + Minimum H1+ H2 V1+ V2 Minimum H1+ H2 Maximum Top Vent Vertical Termination Three ElbowsPipe Clearances to Combustibles Vent Clearances and FramingNon-Combustible Wall Penetration Wall Penetration FramingCombustible Wall Penetration Vertical Penetration Framing Installing the Ceiling FirestopInstalling Attic Shield Attaching Sheetrock Ledges Temporary Access PanelAppliance Preparation Securing and Leveling the Appliance Installing the Flue RestrictorVertical Top Vent Installing the Fiberglass GasketAssembly of Vent Sections Installing Vent PipeAttaching Vent to the Firebox Assembly Assembling Pipe SectionsAssembling DVP-12A Slip Sections Assembling Minimum Installations MI SectionsHorizontal Sections Disassembly of Vent SectionsSecuring the Vent Sections Vertical Sections Heat Shield Requirements for Horizontal Termination Installing Heat Shield and Horizontal Termination CapInstalling the Horizontal Termination Cap Roof Pitch Min. Ft Installing Roof Flashing and Vertical Termination Cap17 Assembling the Storm Collar Around the Pipe Assembling and Installing Storm CollarFuel Conversions Gas Connection Gas InformationGas Pressures Pressure Natural Gas PropaneHigh Altitude Installations Wall Switch Recommendation for WireOptional Accessories Requirements Electrical InformationIntellifire Pilot Ignition IPI Wiring Diagram Wall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingClean the Appliance Appliance SetupAccessories Remove Shipping MaterialsPlacing the Ember Material Install the RefractoryEmber Placement Log #1 SRV2103-107 Positioning the Logs12 Front View Air Shutter Setting Glass AssemblyScreen Mesh Grilles and TrimBefore Lighting Appliance Operating InstructionsOn position. The ON/OFF switch may Turn off all electric power to the applianceLighting Appliance IPI Ignition Final inspection byAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Sympton Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Symptom Possible Cause Corrective Action Maintaining and Servicing Appliance Maintenance TasksDoors, Surrounds Inspect Maintenance TasksLocation Inches Millimeters Appliance Dimension DiagramReference Materials DVP vent components Vent Components DiagramsWall Shield Firestop Horizontal Termination CapHeat Shield Horizontal Termination Cap KitNot for use on these models Extended Heat ShieldDVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP Log Set Assembly Part number list on following Service PartsAt Depot Service Parts ListStocked 6000GCF-IPI IPI Valve AssemblyLimited Lifetime Warranty Heat & GLO GAS Appliance Products Limited Lifetime WarrantyDo not Discard this Manual Contact Information